Transformer Load Loss Calculations

This document contains load loss calculations for a power plant with two 25 MVA transformers. It provides calculations for the transformers operating at 75% and 37.5% load. The key details are: - At 75% load and 660C, the total load losses are 51,894 watts for one transformer and the total losses for the two transformers including one on standby is 64,200 watts. - At 37.5% load and 500C, the total load loss per transformer is 25,116 watts and the total losses for both transformers is 50,232 watts.

Uploaded by

bob
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views4 pages

Transformer Load Loss Calculations

This document contains load loss calculations for a power plant with two 25 MVA transformers. It provides calculations for the transformers operating at 75% and 37.5% load. The key details are: - At 75% load and 660C, the total load losses are 51,894 watts for one transformer and the total losses for the two transformers including one on standby is 64,200 watts. - At 37.5% load and 500C, the total load loss per transformer is 25,116 watts and the total losses for both transformers is 50,232 watts.

Uploaded by

bob
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd

Power Plant 2 x 25 MVA Transformer

LOAD LOSS CALCULATIONS


% LOAD

75

KVA

20,000

IL(HV)

251.02

IL(LV)

1312.16

LOAD LOSS CALCULATIONS @ 50 HZ


I2R loss @ 280C

31,659.78 watts

I2R loss @ 310C

32,020.92 watts

Observed losses @ 310C

44,326.92 watts

Stray losses @ 310C

12,306.00 watts

LOAD LOSS CALCULATIONS @ 60 HZ


I2R loss @ 310C

32,020.92 watts

Stray losses @ 310C

17,720.64 watts

I2R loss @ 660C

36,234.20 watts

Stray losses @ 660C

15,660.10 watts

Total load losses @ 660C

51,894.30 watts

No load loss for S/B Transformer

Losses for 1 X 20/25 MVA @ 75% load


+ 1 x 20/25MVA @ standby mode

12,306.00 watts

64,200.30

watts

Power Plant 2 x 25 MVA Transformer


LOAD LOSS CALCULATIONS
% LOAD
KVA

37.5
20000 /25000

IL(HV)

125.511

IL(LV)

656.080

LOAD LOSS CALCULATIONS @ 50 HZ


I2R loss @ 280C

7,914.95 watts

I2R loss @ 310C

8,005.23 watts

Observed losses @ 310C

20,311.23 watts

Stray losses @ 310C

12,306.00 watts

LOAD LOSS CALCULATIONS @ 60 HZ


I2R loss @ 310C
Stray losses @ 310C
I2R loss @ 500C

8,005.23 watts
17,720.64 watts
8,577.03 watts

Stray losses @ 500C

16,539.26 watts

Total load loss for 1 transformer @ 500C

25,116.30 watts

Losses for 2 X 20/25 MVA @ 37.5% load


per transformer unit

50,232.59

watts

LOAD LOSS CALCULATIONS 
% LOAD
75
KVA
20,000
IL(HV)
251.02
IL(LV)
1312.16
LOAD LOSS CALCULATIONS @ 50 HZ
I2R loss @ 280C
31,6
LOAD LOSS CALCULATIONS 
% LOAD
37.5
KVA
20000 /25000
IL(HV)
125.511
IL(LV)
656.080
LOAD LOSS CALCULATIONS @ 50 HZ
I2R loss @