345kV Substation Protection Overview
345kV Substation Protection Overview
REVISIONS
0.3B1.8 SEL-735
WIL.EHVB-1, 27, 51, 59, 87, 94
87.L-1, MET-1
TRF=2.0 345A-VT "X" 87.B2-BC SEL-487B
345A-CT2
1200:5A MR MET-2 PPC
345A-VT (3-1Ø CTVT) 30A 120V 1200:5A TAP
87.BT BE1-FLEX 87,51,SC
ELSPEC
199,000:120V "X" 0.3B1.8 ION8650 G4430
1660:1:1 TRF=2.0 345A-VT "Y" 345A-VT "Y"
11.F2# SEL-351 27, 51, 59, 81, BF, BWM, SC, TCM, SOTF
0.15% @ W,X,Y,Z 30A 120V H1 345KV HIGH VOLTAGE BUS CONTINUED ON
"Y" A SHEET 2
BLOCK OPEN/CLOSE
87.T1-2, 87.T2-2, K020.52b
87.L-2, MET-2, PPC, K021 OPEN/CLOSE 87.L1 SEL-411L 21, 51, 87-FIBER, DTT, SB, SC, TCM
WIL.T1, WIL.T2 345KV M 89CS.K021
1200A 74-2
6,4,2 OPEN 21, 51, 79, 87-FIBER, BF, DTT, SB, SC,
87.L2 SEL-411L
1200:5A MR
63GX1.K020 BWM
CT2X
1200:5A TAP
RF=2.0
C800 WHITE INDICATING LIGHT FOR 345KV
WIL.EHVB-1
BUS POTENTIAL
1200:5A MR
CT2Y
1200:5A TAP 52CS.K020 WHITE INDICATING LIGHT FOR BUS 1
FROM C800
RF=2.0 87.L-1 WIL.B1-1
DWN. CHK.
87.T1-2
K020
TRIP 1
87.L-2
POTENTIAL
87.T2-2 TRIP 2 87.T2-1
345KV
2000A CLOSE 87.T2-2
WHITE INDICATING LIGHT FOR BUS 1
WIL.B1-2
87.B2-BC POTENTIAL
87.L-2 1200:5A MR BLOCK CLOSE
345A-VT "Y" CT1Y 52CS.K020
SEL-411L 1200:5A TAP 86.T2, 86.L WHITE INDICATING LIGHT FOR XFMR KT1
C800 87.L-1
RF=2.0 87.L-2
WIL.T1
TRIP & BLOCK CLOSE 86.L
F
FROM K010 POTENTIAL
K010-TC2 TRIP SHEET 2 86.L
BFI 1200:5A MR 86.T2
DATE
K020-TC2 K010-TC1, K010-TC2, CT1X
1200:5A TAP
WHITE INDICATING LIGHT FOR XFMR KT2
87.T1-2
K020-TC1, K020-TC2 C800 52CS.K020
WIL.T2
87.T2-2 RF=2.0 POTENTIAL
5,3,1 87.T2-1
TRANSFER TRIP TO INTERCONNECT (87.L-1)
DTT TX FIBER TO REMOTE TERMINAL
TRANSFER TRIP TO INTERCONNECT (87.L-2) SA.T2-1 83.BT LJ-23
86.L FOR DTT & DIFFERENTIAL
220KV
O.
H1,H2,H3 MCOV
87.L-1 345A-VT "X"
SEL-411L TRANSFORMER KT2
FROM K010
E TRIPS TO
SHEET 2 63PR1 87.T2-2
BFI .MT
TRIP
87.T1-2 TRIPS TO 600:5A MR CT-H-2
K010-TC1, K010-TC2,
87.T2-2 63B 87.T2-1 SHORTED 0.15B1.8
CROSS-TRIP SUPERVISORY K020-TC1, K020-TC2
86.T1 600:5A MR CT-H-1
DTT TX 63PR1 CT-H0
86.T2 FIBER TO REMOTE TERMINAL .LTC SHORTED C800
86.L LOW GAS TRIP FROM 63GX1.K020 C800
FOR DTT & DIFFERENTIAL H0
TRANSFORMER KT2
CROSS TRIP FROM 87.B1-BC
345/34.5/13.8 KV 600:5A MR
136.2/181.6/227 MVA 600:5A TAP
CØ CØ
CONTINUED ON 4 3 CONTINUED ON
SHEET 1 SHEET 4
TO 345KV BUS BØ BØ TO KT1
6 5
AØ AØ
M
2X1
4X1
6X1
6X5
2Y1
4Y1
6Y1
6Y5
5Y5
5Y1
3Y1
1Y1
5X5
5X1
3X1
1X1
CK010X2N
CK010Y2N
CK010Y1N
CK010X1N
CK010X2B
CK010Y2B
CK010Y1B
CK010X1B
CK010X2A
CK010Y2A
CK010Y1A
CK010X1A
CK010X2C
CK010Y2C
CK010Y1C
CK010X1C
TO 87.T1-1 TO 87.T1-2 TO 87.L-2 TO 87.L-1
DWG_HVS_103000010_2 DWG_HVS_103000010_2 DWG_HVS_103000010_1 DWG_HVS_103000010_1
This is a good illustration of how symmetrical components as a mathematical tool is used in an actual project.
In the above snapshots I am showing you the line protection for the 345kV transmission line going out of the solar farm Ground distance
substation. elements for Zone 2
was enabled
Look at the current transformers used for the line protection relays (87L-1 and 87L-2). The CTs from two incomers are
all connected in Wye formation, one CT in each phase. Notice that there is no zero-sequence CT but these relays have
enabled the Ground Distance (21G) function.
The question - How then these relays extract the zero sequence currents when there is no zero-sequence CT?
The answer - The relays takes in Line Currents (which are the physical parameters) and then inside the relay's
algorithm, it mathematically calculates for the different sequence quantities and compare with the settings to make
tripping decisions.
Look at the snapshot of the relay settings for Ground Distance (21G) function at the right side taken from SEL
AcSELerator Quickset software.