Flexible Lead of generator are broken. Rotor winding and insulation resistance is infinite. The weight of the two side flexible leads should be approximately equal in order to avoid the mass unbalance during operation. Flexible Lead is able to hold centrifugal force when the generator rotor operates.
Flexible Lead of generator are broken. Rotor winding and insulation resistance is infinite. The weight of the two side flexible leads should be approximately equal in order to avoid the mass unbalance during operation. Flexible Lead is able to hold centrifugal force when the generator rotor operates.
Flexible Lead of generator are broken. Rotor winding and insulation resistance is infinite. The weight of the two side flexible leads should be approximately equal in order to avoid the mass unbalance during operation. Flexible Lead is able to hold centrifugal force when the generator rotor operates.
GTG 2.1 Tambak Lorok Combined Cycle By . Embun K Rita Triani Dwi Handoyo Background The unit was prepared for charging the bus bar A. After finishing its, they has loss voltage. That caused by a capacitive load received by the generator. 1. Making Electrical and Mechanical test, It founds that the value of the rotor winding and insulation resistance is infinite. By using the boroscope it founds that flexible lead of generator are broken 2. Drawing of Collector end of Generator Field Scope of Work Rotor Winding assy & Diss asy a. Disconnect Interpole Connection, Spacer Block and Wedges b. Dismantling Bar Coil c. Assembly Bar Coil d. Assy Flexible Lead Fabrication a. Flexible Lead b. Material Insulation
Evaluation and Analysis Peformance Test after unit Syncron
Fabrication Flexible Lead and Material Insulation
Flexible Lead Fabrication
1. Preparing tools for flexible lead 2. Preparing Material flexible lead 3. Manufacturing plate flexible lead 4. Brazing plat flexible lead 5. Repairing isolator flexible lead 6. Ultrasonic Test brazing Flexible Lead 7. Contact Resistance Test brazing of Flexible Lead
Fabrication Flexible Lead and Material Insulation The weight of the two side flexible leads should be approximately equal in order to avoid the mass unbalance during operation. The manufacturing process of flexible lead is performed with quality control as follows. a. Quality control of Cu material test of copper plate Cu material composition (99 % Cu). b. Quality control of brazing preformed brazing procedure specification (WPS) c. Quality control of brazing result nondestructive test (Ultrasonic test , megger test and contact resistance)
Manufacture of flexible lead was adjusted with dimensions required by considering aspects as follows. a. Electric current-carrying capability, a primary function of flexible leads. b. The mechanical strength is able to hold centrifugal force when the generator rotor operates. From the whole set of material selection, manufacturing and testing, then the flexible lead is ready to be installed on the generator rotor.
Re-Engineering Flexible Lead Fabrication Flexible Lead and Material Insulation Material Insulation Fabrication
1. Preparing tools for insulation profile 2. Preparing Material insulation 3. Manufacturing insulation profile 4. Monitoring and testing insulation profile
Fabrication Flexible Lead and Material Insulation Evaluation and Analysis MEASUREMENTS Standard of Measurement EASA AR 100 2010 (Recommended practice for repair of rotating electrical apparatus) 1. Insulation resistance test ( megger ) 2. Winding resistance test (tools micro ohm meter programma ) 3. Surge comparison test ( surge test, tools D12R ) 4. Voltage drop test ( dc or ac voltage ) coil in series ( ac voltage test ) 5. Checking and testing sistem AVR excitation System 6. Recurrent Surge Ocillograph ( RSO ) 7. Rotor Temperature Sensitifity ( RTS ) Measurement Results Measurement Results Performance Test After Unit Syncron Performance Test After Unit Syncron Performance Test After Unit Syncron Performance Test After Unit Syncron Performance Test After Unit Syncron Performance Test After Unit Syncron CONCLUSION 1. The reinsulation and replacement of flexible lead can be done through a careful material selection and method that used in the Overall. Material insulation is using NOMEX class while for flexible lead using material Cu 90% .
2. Parameter Quality is based on std EASA AR 100-2012
3. Re insulation and replacement of flexible lead can be performed by several steps including its quality testing method. Until now, the generator of Gas Turbine 2.1 can operate normally.
Recommendation 1. Always monitor the operating parameters of the generator rotor to avoid the force outage. The parameter as follows : Vibration, MVAR, temperature, excitation current and etc.
2. Always operate the power plant on its capability curve, to minimize the risk of rotor generator breakdown.