Load Model Motor Protection, Drives and Lighting J ohn Kueck 2 A Range of Applicable Standards Most Small Motors Only Have Over-current and Overload Protection Newer Standards Are Requiring Under-voltage The Ice Cube Relay Is the real culprit Point of Wave Has More Effect than Voltage Dip Magnitude Motor Protection and Control 3 Many Well Known Standards: Buff Book IEEE Std 242-2001 Protection and Coordination of Industrial and Commercial Power Systems Gray Book IEEE Std 241-1990 Electric Power Systems in Commercial Buildings Red Book IEEE Std 141-1993 Electric Power Distribution for Industrial Plants Gold Book IEEE Std 493-2007 Design of Reliable Industrial and Commercial Power Systems Blue Book IEEE Std 1015-2006 Applying Low Voltage Circuit Breakers Used in Industrial and Commercial Power Systems The National Electrical Code (NEC, 2011) The above standards provide little guidance on the suggested setpoint for undervoltage trip for various types of equipment, especially for equipment under 600 volts. There is significant latitude allowed to the designer, and really no requirement that the designer rigorously follow the standard. Biggest problem may be the common ice cube relay. A Range of Standards for Equipment Protection and Voltage Tolerance 4 Thermal capability (overload) Locked Rotor Short Circuit (Instantaneous) Single Phasing Undervoltage Unbalance Protection setting with new motor starters is much easier than it used to be. Basic Motor Protection 5 Voltage Unbalance Has a Major Impact on Motor Efficiency 6 Motor Torque Induction motor electrical torque is a function of the terminal voltage squared. During a rapid dip, the motor goes into regeneration and will be slowed. A stiff system or dc offset slows the motor faster Low inertia in the driven equipment means even faster deceleration 7 NEMA Torque Designs B Most common by far. Normal starting torque for fans, pumps, miscellaneous machinery. Medium starting torque, high breakdown torque. C High starting torque, medium breakdown torque for high inertia loads such as conveyors, positive displacement pumps. D Extra high starting torque, low breakdown torque for very high inertia loads, may have high slip. Used for motor operated valves. E No longer included, but was for high efficiency motors, similar to shape of B, but lower. 8 NEMA Design Motor Speed Torque Curves 9 For this Hypothetical Motor, the Torque Available at 75% Voltage May Fail to Accelerate the Load Percent Full Load Torque Percent Full Load Speed 60 0 40 80 120 160 200 20 40 80 100 Motor Torque Rated V Motor Torque 75% V Load Torque Motor May Fail to Accelerate Load Synchronous motors run without slip and do not have torque curves like induction motors; if the "pull out" torque is exceeded, the motor will pull out of step Armature Amps % Power Factor Field Amps 15 0 20 40 60 80 10 0 5 10 20 Full Load Power Factor Full Load Current Lagging PF Leading PF 11 Representative Speed Torque Curves for Various Types of Loads Percent Full Load Torque Percent Full Load Speed 60 0 40 80 120 160 200 20 40 80 100 Centrifugal Pump or Fan (Open Discharge) Axial Pump or Fan Centrifugal Pump or Fan (Closed Discharge) 12 The IEEE Buff Book (242, 2001) Section 10.3.2.1 Purposes of Under-voltage Protection To prevent a motor from automatically restarting when voltage returns. To avoid excessive inrush to the total motor load on the power system. To avoid reaccelerating motors before their fields collapse. Time delay undervoltage protection will often not be satisfactory because magnetically held contactors may drop out before the undervoltage protection. 13 Very Few Other Standards Mention Undervoltage Protection for Motors For large motors, the IEEE Red Book (IEEE_Standard_141, 1993) states in Section 5.6.3.1 motor protection may include: Internal fault protection - either overcurrent relays or percentage differential relays; sometimes ground fault protection is provided using a zero sequence approach. Sustained overloads and locked rotor - Conventional over current relays may provide too much margin between the motor thermal capability curve and the relay operating time characteristic. Overcurrent relays do, however, provide excellent locked rotor and short circuit protection. Thermal relays will give adequate protection for light and medium overloads. Under voltage - Large motors and medium voltage motors should have separate undervoltage protection. For small motors, the Red Book and the NEC do not require undervoltage protection. 14 Emerson Secure Start and ComfortAlert for Air Conditioning Compressors ComfortAlert will flash an alert if the voltage is below 71% Secure Start Monitors supply voltage in air conditioning compressors and protects against low voltage or locked rotor. Also provides a reduced voltage soft start. Can be used in areas with problems in voltage variation. 15 Programmable Logic Controllers Adjustable Speed Drives Personal Computers Fluorescent Lighting Power Electronic Loads 16 0 200 400 600 800 Duration of Sag (milliseconds) Upper Range Average Lower Range % V 80 60 40 PLC Power Supply Voltage Sag Tolerance (CIGRE 412) 20 10 0 Voltage Tolerance of Programmable Logic Controllers, A Wide Range 480 V Circuit Breaker VFD Controls Voltage and Frequency Motor VFD to Control Fan Speed Instead of Dampers 18 Useful Work Controller losses <1 to ~5% for ASD Motor losses 3.5 to >10% Coupling device losses <1 to >10% for large speed reduction Driven load losses 30 to 50% for pumps and fans Load modulation devices 0 to >50% Typical Motor System Losses 19 Controlling Speed and Torque with a VFD Is More Efficient than Valves or Dampers Power Required to Achieve Needed Flow Percent of Full Flow Vane Adjustment VSD Control 20 Variable Frequency Drive (VFD) Tolerance and Protection 0 200 400 600 800 Duration of Sag (milliseconds) Upper Range Average Lower Range % V 80 60 40 ASD Voltage Sag Tolerance (Djokic, 2005) 20 10 0 Overcurrent Protection Undervoltage Protection 21 VFD Voltage Sag Test Our data comes from a test at which the vfd frequency reference was set to 30 Hz. v p v dc 20% voltage drop, held for 10 seconds, and then ramped back over 10 seconds. Voltage Sag Test Contd. Power is roughly constant, except at the point of voltage drop. Speed is almost constant Power is not strongly dependent on voltage in this data. 23 Lighting Incandescent filament lamps are quite tolerant to voltage sags, but the light output and lifetime are dramatically impacted by sustained voltage deviations. Fluorescent lamps: Electronic ballast ( vast majority today) o tend to drop out at lower voltages 10 to 20%, o have nearly constant current characteristic at the fundamental frequency, dim at lower voltages o Current contains significant harmonics o New dimmable fluorescent lamps with electronic ballasts are controlled with either a 0 to 10 volt dc signal or a digital signal, not by varying voltage Magnetic ballast o Usually drop out between 70 and 80% in as little as 10 milliseconds o Highly non-linear reactive power characteristic 24 Electronic Ballast Fluorescent Lights 4 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.1 -200 -100 0 100 200 Time V o l t a g e Fluorescent Voltage and Current 4 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.1 -4 -2 0 2 4 C u r r e n t 25 Electronic Ballast Fluorescent Lights 0 20 40 60 80 100 120 140 -10 0 10 20 30 40 50 60 Voltage [V] R e a l
P o w e r
[ W ] 0 20 40 60 80 100 120 140 -30 -25 -20 -15 -10 -5 0 5 R e a c t i v e
P o w e r
[ V A R ] Fluorescent Power Reactive Power Active Power 26 Compact Fluorescent Lights 0 20 40 60 80 100 120 -10 0 10 20 30 Voltage [V] R e a l
P o w e r
[ W ] 0 20 40 60 80 100 120 -15 -10 -5 0 5 Compact Fluorescent Power R e a c t i v e
P o w e r Reactive Power Active Power 27 Magnetic Ballast Fluorescent Lights 4 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.1 -200 -100 0 100 200 Time [sec] V o l t a g e
Fluorescent Old-Ballast Voltage and Current 4 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.1 -2 -1 0 1 2 Time [sec] C u r r e n t 28 Magnetic Ballast Fluorescent Lights 0 20 40 60 80 100 120 140 -50 0 50 100 Voltage [V] R e a l
P o w e r
[ W ] Fluorescent Old-Ballast Power 0 20 40 60 80 100 120 140 -20 0 20 40 Voltage [V] R e a c t i v e
P o w e r
[ V A R ] Active Power Reactive Power 29 Ice Cube Relay, the Achilles Heel These relays are commonly used in 120 volt control circuits, for example: Emergency stop circuits for pumps and fans Door interlock circuits Air compressor starter controls Chiller controls Conveyor controls Oven controls PLC - Motor interface circuit ASD start circuit Vending machines 30 31 32 0 200 400 600 800 Duration of Sag (milliseconds) Upper Range Lower Range % V 80 60 40 20 10 0 Ice Cube Relay Voltage Sag Tolerance (EPRI) 33 Contactors Large Motor Starter Contactors Motor starter contactors may open at 65 to 75% voltage in the case of 2300 or 4600 Volt motors and 55 to 65% in the case of 460 Volts and below. The contactor dropping out or control relays dropping out is often the only fast undervoltage protection that motors under 600 volts typically have. Large Air Conditioners Large three phase air conditioning in industrial or commercial applications typically have undervoltage relays which trip in perhaps six cycles after the voltage drops below 0.6 pu. 34 0 200 400 600 800 Duration of Sag (milliseconds) Upper Range DC Lower Range % V 80 60 40 20 10 0 AC Upper Range AC Lower Range DC Contactors Voltage Sag Tolerance (CIGRE 412) 35 Other Parameters Are Probably More Important than the Dip Magnitude More recent studies have shown that there are a number of parameters which have a major impact the capability of a device to ride through an interruption than just the dip magnitude and duration. (CIGRE_Voltage_Dip_Immunity_of_Equipment_and_Installations 2010 Voltage Dip Immunity of Equipment and Installations C4.110) These parameters include: Pre dip voltage magnitude and distortion of sine wave. Unbalance during dip for three phase devices, dip shape, and point on the sine wave where the dip starts. Speed of recovery of dip. Source impedance (distribution transformer). Other equipment connected close by. 36 Point on Wave The point on the sine wave is important because of the energy stored in the magnetic circuit. The stronger the field when the dip begins, the more likely the contactor or relay will ride through the dip. Because of the lagging current drawn by the contactor coil, contactors are most sensitive to dips that begin at 90 degrees and least sensitive to dips that begin at zero crossing. Dips initiated at 90 degrees may drop out a contactor in less than 10 msec. Dips initiated at 0 degrees may not drop out the same contactor for 80 msec even at zero volts. 37 0 20 40 60 80 Duration of Sag (milliseconds) 90 Degree Point on Wave of Sag Initiation 0 Degree Point on Wave of Sag Initiation % V 40 20 60 Pass Fail Contactor Point on Wave Influence, CIGRE Data 38 Conclusions Point on wave may have a greater impact on motor contactors than magnitude and duration. High efficiency motors are more prone to stall. Ice cube relays are used in many motor control circuits and will drop at 70% V in one cycle. Voltage drop in branch circuits and other parasitic drop in low voltage systems may be a growing problem. Motors at 600 volts and below in the past did not have undervoltage protection unless supplied by manufacturer (air conditioning compressor). Motor contactors will typically provide the undervoltage protection by dropping out.