1 ALARMS P-TYPE SEPARATION SYSTEM ALARMS AND FAULT FINDING
1 Alarms
1.1 Alarm Functions
The alarm system is designed to ensure a safe
separation system.
All alarms are shown on the operator panel
display, and most of them are complemented by
light emitting diodes (LEDs).
The alarms are displayed in order of occurrence.
2 1810898-02
P-TYPE SEPARATION SYSTEM ALARMS AND FAULT FINDING 1 ALARMS
ING
WARN
!
Breakdown hazard
Never reset an alarm without first finding and
remedying the cause.
G001648A
ALARM
2 Remedy the cause.
G001649A
ALARM
ON
CAUTI
!
Risk of injury
Never return to the operator panel to acknowledge or
reset an alarm if doing so is by any means
hazardous.
1810898-02 3
1 ALARMS P-TYPE SEPARATION SYSTEM ALARMS AND FAULT FINDING
Why? What to do
• Oil level in oil sump too low. Check oil level and add oil if
necessary.
Noise • Height position of paring disc is Stop the separator, measure and
incorrect. adjust the height.
4 1810898-02
P-TYPE SEPARATION SYSTEM ALARMS AND FAULT FINDING 2 DISPLAY ALARMS AND ACTIONS
on page on page
The display The display
shows shows
10 Local OP in control 16
Bowl speed sensor - ERROR
15 POWER FAILURE 16
Feed pressure PT1 - LOW
8 Service alarm 17
High vibration - WARNING
1810898-02 5
2 DISPLAY ALARMS AND ACTIONS P-TYPE SEPARATION SYSTEM ALARMS AND FAULT FINDING
on page
The display
shows
6 1810898-02
P-TYPE SEPARATION SYSTEM ALARMS AND FAULT FINDING 2 DISPLAY ALARMS AND ACTIONS
High vibration - SHUTDOWN • Sludge remaining in part of the Dismantle, clean and check the
bowl bowl before restart. See Service
Manual.
ING
WARN
!
ING
WARN
!
Disintegration hazards
If excessive vibration occurs, stop Disintegration hazard
separator and keep bowl filled with
The separator bowl must be
liquid during rundown.
manually cleaned before starting
The cause of the vibration must be
identified and corrected before the up again.
separator is restarted.
• The frame feet are worn out. Renew the frame feet.
High frequency xxxx Hz • Frequency deviation more than Check power supply
+ 5%
1810898-02 7
2 DISPLAY ALARMS AND ACTIONS P-TYPE SEPARATION SYSTEM ALARMS AND FAULT FINDING
High vibration - WARNING • Sludge remaining in part of the Dismantle, clean and check the
bowl bowl before restart.
ING
WARN
!
Disintegration hazard
The separator bowl must be
manually cleaned before starting
up again.
• The frame feet are worn out. Renew the frame feet.
Vibration sensor - ERROR • Sensor or cable damaged Replace sensor. If no spare sensor
available, set parameter Fa 16 =
0.0 to be able to run the system.
8 1810898-02
P-TYPE SEPARATION SYSTEM ALARMS AND FAULT FINDING 2 DISPLAY ALARMS AND ACTIONS
Bowl speed - HIGH • High power (net) frequency Check power supply before
restart.
Disintegration hazard
Stop and change the belt
transmission to suit the power
supply frequency.
Disintegration hazard
Stop and change the belt
transmission to suit the power
supply frequency.
1810898-02 9
2 DISPLAY ALARMS AND ACTIONS P-TYPE SEPARATION SYSTEM ALARMS AND FAULT FINDING
Bowl speed sensor - ERROR • Sensor or cable damaged Replace sensor. If no spare sensor
available set parameter In 6 = No
to be able to run the system.
Sludge tank level - HIGH • Pump has not drained the tank Check the pump function.
• Height position of paring disc is Stop. Check and adjust the height.
incorrect.
10 1810898-02
P-TYPE SEPARATION SYSTEM ALARMS AND FAULT FINDING 2 DISPLAY ALARMS AND ACTIONS
Emergency stop - BUTTON PUSHED • Emergency button pushed Remedy cause for pushing button.
Reset push button.
Oil feed temperature - HIGHxxxxx • Steam supply valve faulty Investigate cause and remedy.
1810898-02 11
2 DISPLAY ALARMS AND ACTIONS P-TYPE SEPARATION SYSTEM ALARMS AND FAULT FINDING
Oil feed temperature - LOWxxxxx • Heater clogged Investigate cause and remedy.
• Steam supply insufficient
• Steam trap faulty
• Steam supply valve faulty
Temperature alarm sensor - ERROR • Short circuit / broken sensor or Disconnect cable at sensor.
cable. Measure resistance between 1-3.
Resistance shall be within 100-142
ohms = 0-110 C / 32-230 F.
Test of EPC 50 input:
• Disconnect cables from sensor,
(terminal X 5:1-2-3).
• Move jumpers Xj1 and Xj2
upwards - from Normal to Test.
(The jumpers can be found in
the upper left corner of the I/O
Board)
• Indication within 50-60 C when
OK.
• If no spare sensor available set
parameter Pr 16 = 0, or if control
sensor free, move connection
to that one.
12 1810898-02
P-TYPE SEPARATION SYSTEM ALARMS AND FAULT FINDING 2 DISPLAY ALARMS AND ACTIONS
Temperature control sensor - ERROR • Short circuit / broken sensor or Disconnect cable at sensor.
cable. Measure resistance between 1-3.
Resistance shall be within 100-142
ohms = 0-110 C / 32-230 F. If no
spare sensor available set
parameter Pr 18 = 0. Heater is then
out of function.
Feed flow PT1 - ERROR DURING Tixx • Pump not working Check pump.
• Pressure in feed line too low Check feed line.
Separator motor - FAILURE • Feedback signal from contactor Check the contactor function.
K 2 missing Input terminal
X 6:5 in EPC 50.
1810898-02 13
2 DISPLAY ALARMS AND ACTIONS P-TYPE SEPARATION SYSTEM ALARMS AND FAULT FINDING
Oil pressure sensor PT4 - ERROR • Sensor or cable damaged Replace sensor. If no spare sensor
available set parameter Pr 10=0.0
to be able to run the system.
14 1810898-02
P-TYPE SEPARATION SYSTEM ALARMS AND FAULT FINDING 2 DISPLAY ALARMS AND ACTIONS
OIL PRESSURE PT4 HIGH DURING Ti70 • No decrease in oil pressure Check function of change over
during this timer valve V1.
Feed pressure PT1 - HIGH • Pipe restricted Check recirculation for restriction
Feed pressure PT1 - LOW • Low flow Check pump and flow regulation.
Feed pressure sensor PT1 - ERROR • Sensor or cable damaged Check cable connections
Pump starter - FAILURE • Feedback signal from contactor Check the contactor function.
K 3 missing
Check input terminal X 9:1 in the
EPC.
Parameters changes - LOCKED • A code has been set to make Unlock the code.
parameter changes not possible
1810898-02 15
2 DISPLAY ALARMS AND ACTIONS P-TYPE SEPARATION SYSTEM ALARMS AND FAULT FINDING
NO SIGNAL FROM EXTRA INPUT X6:8 • Depends on use of the input Depends on use of the input
Heater - FAULT • 0V in cable heater X 12:3 to EPC Check the power supply to the
50 X 51:4 heater.
(electric heater)
Local OP in control • Attempt to operate remote OP Not legal when local OP is active.
POWER FAILURE • Black-out has occurred with EPC Check plant conditions and
in operation restart.
16 1810898-02
P-TYPE SEPARATION SYSTEM ALARMS AND FAULT FINDING 2 DISPLAY ALARMS AND ACTIONS
Parameter xx:xx - ILLEGAL • If parameters are changed Switch EPC50 power off. Move
automatically by "thunderstorm" X J4 on I/O board to position right.
type influence, alarm is given to Switch power on. Parameters are
indicate out of range. now all set to default values. Move
X J4 back to original position.
Adjust all parameter settings to
correct value.
xxxxx board - ERROR • OP (Operator Panel board), Check cables to board or replace
I/O board or OPr (Operator Panel the board (see Change of Circuit
remote board) in EPC not Board in the Service Manual
working booklet).
Heater board - ERROR • Optional heater board in EPC not Check cables to board or replace
working the board (see Change of Circuit
Board in the Service Manual
booklet).
IO expansion board - ERROR • X71:2 and X71:3 are both set to Set X71:2 to X41 and jumper
0 or both set to 1 between X71:3 and X40
Vibration board - ERROR • Optional vibration board in EPC Check cables to board or replace
not working the board (see Change of Circuit
Board in the Service Manual
booklet).
Temperature increase - TOO SLOW • Insufficient heating during start Check heater function.
(Ti 53)
Switch power off/on • Alarm is displayed at standstill Investigate the cause for the stop
after emergency or vibration shut and switch the power off and then
down on to the EPC 50.
Level switch - DISABLED • If Pr 25=0 the high level alarm is Warning to operator only.
disabled
Service alarm • If Pr 5 is used, the text in Pr 6 is Take action according to what the
displayed text means (plant dependant).
1810898-02 17
3 ALARM TESTS PA PURIFIER SYSTEM ALARMS AND FAULT FINDING
3 Alarm Tests
NOTE
18 1810898-02