Professional Documents
Culture Documents
00101VIP
TABLE OF CONTENTS
Section 1 INTRODUCTION......................................................................................................6
GENERAL................................................................................................................6
NOMENCLATURE..................................................................................................6
GENERAL..............................................................................................................26
FUNCTION ............................................................................................................26
SYSTEM DETAILS ..............................................................................................28
2 YORK INTERNATIONAL
FORM 155.16-OM1
GENERAL..............................................................................................................29
Cleanliness ..........................................................................................................29
Types of Lubricants ............................................................................................29
PURGE PUMP PIPING AND OPERATING VALVES........................................29
The Principle of Gas Ballast ..............................................................................29
OIL LEVEL DETERMINATION ..........................................................................29
INTRODUCTION ..................................................................................................34
TROUBLESHOOTING ........................................................................................34
Pump Tripping On Overloads ............................................................................34
Pump Tripping On Thermal Protection ..............................................................34
Unusual Noise/Vibration ....................................................................................34
Pump Overhaul ....................................................................................................34
GENERAL ................................................................................................................36
STEAM/CONDENSATE OR HOT WATER QUALITY ........................................36
TUBE CLEANING....................................................................................................37
GENERAL..............................................................................................................38
START-UP (NORMAL) ........................................................................................38
SHUTDOWN (NORMAL) ....................................................................................39
Manual Shutdown................................................................................................39
OPERATING DATA ..............................................................................................39
General ................................................................................................................39
Performance Data and Calculations....................................................................40
YORK INTERNATIONAL 3
Section 9 PTX CHART ............................................................................................................42
APPENDIX
Glossary Of Terms..................................................................................................61
LIST OF ILLUSTRATIONS
Fig. 1 – Basic Cycle Diagram ......................................................................................................................8
Fig. 2 – Typical Power Panel......................................................................................................................11
Fig. 3 – Model YIA Absorption Unit, Front View ....................................................................................13
Fig. 4 – System Control Components Location ........................................................................................15
Fig. 5 – Evaporator ....................................................................................................................................16
Fig. 6 – Absorber........................................................................................................................................16
Fig. 7 – Solution Pump ..............................................................................................................................16
Fig. 8 – Generator ......................................................................................................................................16
Fig. 9 – Condenser......................................................................................................................................17
Fig. 10 – Cycle Diagram (Hot Water Units and Steam Units) ....................................................................18
Fig. 11 – IsoFlow Absorption System Solution Concentration Average in System Solution Circuit ........19
Fig. 12 – Solution and Refrigerant Level Variation With Load ..................................................................20
Fig. 13 – Automatic Decrystallization Feature (Hot Water Units & Steam Units with ADC Control) ......25
Fig. 14 – Bubble Testing for Leaks..............................................................................................................26
Fig. 15 – IsoFlowTM Purge System ............................................................................................................27
Fig. 16 – Purge Drum Details ......................................................................................................................28
Fig. 17 – The Complete Purge System ........................................................................................................28
Fig. 18 – Purge Pump Piping & Valves - Normal Operation ......................................................................29
Fig. 19 – Model 1402 Vacuum Pump for YORK ........................................................................................33
Fig. 20 – Flow of Refrigerant Water or Lithium Bromide through Pump ..................................................35
Fig. 21 – Acceptable Unit Internal Pressures ..............................................................................................38
Fig. 22 – Operating Data Sheet ....................................................................................................................41
Fig. 23 – PTX Chart ....................................................................................................................................43
Fig. 24 – Pressure Drop Curves ..................................................................................................................46
Fig. 25 – Pressure Equivalents ....................................................................................................................65
Fig. 26 – Vacuum Units of Measurement ....................................................................................................65
Fig. 27 – Complete Cycle Diagram..............................................................................................................67
4 YORK INTERNATIONAL
FORM 155.16-OM1
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. personal injury or death to themselves and people at
During installation, operation, maintenance or service, the site.
individuals may be exposed to certain components or
conditions including, but not limited to: refrigerants, This document is intended for use by owner-author-
oils, materials under pressure, rotating components, ized operating/service personnel. It is expected that
and both high and low voltage. Each of these items this individual possesses independent training that
has the potential, if misused or handled improperly, to will enable them to perform their assigned tasks prop-
cause bodily injury or death. It is the obligation and erly and safely. It is essential that, prior to performing
responsibility of operating/service personnel to identi- any task on this equipment, this individual shall have
fy and recognize these inherent hazards, protect them- read and understood this document and any refer-
selves, and proceed safely in completing their tasks. enced materials. This individual shall also be familiar
Failure to comply with any of these requirements with and comply with all applicable governmental
could result in serious damage to the equipment and standards and regulations pertaining to the task in
the property in which it is situated, as well as severe question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard:
YORK INTERNATIONAL 5
SECTION 1 – INTRODUCTION
GENERAL NOMENCLATURE
This manual contains instructions and information re- A system of nomenclature used for identification pur-
quired by the operator for proper operation and preven- poses of Model YIA Absorption Chillers is described
tative maintenance of the YORK IsoFlow Absorption as follows.
Liquid Chillers.
It is imperative that the operator know
Included in this instruction are discussions of the basic the designation of any given unit in-
principles of operation of Lithium Bromide Absorption tended to be operated in accordance
Systems and descriptions of the functional operation of with this instruction; this is necessary
major components and sub-systems. Instructions relat- to ensure that the appropriate sections
ed to the controls and normal operating sequence of the
of this manual are applied. The unit
various modifications of the IsoFlow units can be
found in Form 155.16-O3 "Operators Manual – designation can be determined from
Control Panel" and Form 155.16-N3, “IsoFlow the unit data plate on the side of the
Installation Manual”. control panel. The unit serial number
is also shown.
Procedures and checks to be conducted by the operator
are described extensively for all areas of operation.
These involve the Pre-Start modes of units, normal op-
eration of units and operational functions related to
general performance of the system. Information and
guides are given pertaining to care and general mainte-
nance of the unit.
NOMENCLATURE
YIA – ST – 8E1 – 46 – B – S
6 YORK INTERNATIONAL
FORM 155.16-OM1
YORK INTERNATIONAL 7
MODEL YIA STANDARD STEAM CYCLE DIAGRAM
KEY
CONCENTRATED CONDENSER CONDENSER
SOLUTION (LI.BR.)
INTERMEDIATE
SOLUTION (LI. BR.)
REFRIGERANT
(WATER) STEAM
CONTROL
ORIFICE
CHILLED LIQUID
VALVE
CONDENSER GENERATOR
WATER
STEAM STEAM
EVAPORATOR ORIFICE
AUTOMATIC DE-CRYSTALLIZATION PIPE
CONDENSER WATER
ORIFICE
ABSORBER
(2SOL)
(3 SOL)
SOLUTION
SOLUTION PUMP
HEAT EXCHANGER
ORIFICE REFRIGERANT
EDUCTOR PUMP
LD04763
Note: Some orifices may differ between various models.
8 YORK INTERNATIONAL
FORM 155.16-OM1
YORK INTERNATIONAL 9
CONTROL DESCRIPTIONS
4. Functional controls which permit operation over a units and 50 HZ, 380 volts units.
wide range of condenser water temperatures.
2CB – Circuit Breaker
COMPONENTS IN THE CONTROL CENTER
Takes the place of 3FU on 60 Hz NEMA 4 units and 50
Hz, 380 volts units.
See IsoFlow Panel Instruction, Form 155.16-O3.
1M – Starter/Contactor for Solution Pump
COMPONENTS IN POWER PANEL (See Figure 2)
Used on all units.
1SW – Service Disconnect Switch
This is a non-fused, service disconnect switch. The 2M – Starter/Contactor for Refrigerant Pump
incoming power lines from the customer-supplied Used on all units.
fused disconnect switch or circuit breaker should be
connected to terminals L1, L2, and L3 of this switch. 3M – Starter/Contactor for Purge Pump
Used on all units.
1T – Transformer
This is a step-down transformer that reduces the unit's 1OL thru 3OL – Overloads
incoming power (primary) down to the required control
Each starter/contactor is accompanied by a heater ele-
voltage of 120/115-1-50/60 (secondary).
ment overload with resetting capability. The designa-
tion number of the overload matches the designation
1FU, 2FU, 3FU – Control Fuses
number of the starter/contactor.
Used on all 60 Hz standard (NEMA 1) units. 1FU and
2FU are on the primary side of the 1T transformer. The MTH1 and MTH2 – Motor Thermostats
amperage rating of these fuses depends on the unit's
Used on all units with Buffalo Pumps. These Klixon
voltage. The 3FU fuse is always a 10-amp fuse and is
type thermostats are imbedded in the motor windings
on one leg of the secondary coil of the 1T transformer.
and will open when the motor internal temperature
It is used for the control panel voltage.
reaches 300°F (150°C) to 392°F (200°C), depending
on pump type. The thermostats will automatically
1CB – Circuit Breaker
reset when the motor windings cool down 27°F (15°C)
Takes the place of 1FU and 2FU on 60 Hz NEMA 4 from the trip point.
10 YORK INTERNATIONAL
FORM 155.16-OM1
1FU
2FU
3FU
2OL
26897A
1OL
1M 2M 3M TB2 GROUND
FIG. 2 – TYPICAL POWER PANEL (60 HZ, NEMA 1 STANDARD UNIT POWER PANEL SHOWN)
YORK INTERNATIONAL 11
CONTROL COMPONENTS EXTERNAL TO THE 2SOL – Stabilizer Refrigerant Solenoid Valve
CONTROL CENTER (See Figure 3)
Basically, the 2SOL works in conjunction with the
Automatic Decrystallization mode of the unit. When
Hermetic Motor Thermostats (Not Shown) –
RT2 senses an increase of temperature to 160°F
The Buffalo Solution and Refrigerant pump motors (71.1°C) in the ADC line, the stabilizer refrigerant
are cooled by the circulating fluid. In the case of inad- solenoid valve is energized for 2 minutes. This trans-
equate cooling, each motor has an internal motor pro- fers refrigerant to the generator's drain line and thus
tector of the Klixon type imbedded in the motor wind- to the shell side of the heat exchanger to dilute the
ings to protect the motor from damage if overheating solution.
occurs.
A second function of this solenoid valve is to manu-
1F – Refrigerant Level Float Switch ally energize it from the micro control panel to act as
a refrigerant "blow down". For further details of this
This float switch is installed in a separate chamber on
valve and its operations, refer to Form 155.16-O3,
the side of the refrigerant outlet box, hanging off the
“Operators Manual – Control Panel”.
evaporator. It senses when the refrigerant level is low
enough that the refrigerant pump could cavitate and
3SOL – Refrigerant Level Solenoid Valve
cease to sustain the flow of refrigerant to the evapora-
(Unloader Valve)
tor sprays. Should this occur, as it will at low loads
with low tower water temperature to the absorber, The function of this valve is two-fold: 1. It transfers
3SOL will be energized to permit solution to come diluted solution from the discharge of the solution
into the refrigerant circuit to satisfy the pump needs pump to the evaporator refrigerant outlet box. When
and sustain unit operation. float 1F opens, 3SOL energizes to allow solution to
flow, thus keeping the refrigerant pump from cavitat-
3F – Refrigerant Pump Cutout Float Switch ing. This might occur at light loads and with low tem-
perature tower water to the absorber shell. 2. When
This float switch is installed in a separate chamber
the solution is allowed to mix with the refrigerant, the
located on the refrigerant pump suction line just up-
contamination decreases the refrigeration effect
stream of the refrigerant pump inlet. It is used in con-
through the evaporator, thus allowing the unit to stay
junction with 1F to detect insufficient refrigerant to
online longer during periods of low loads.
the Buffalo refrigerant pump. When the refrigerant
level has decreased below the level that allows refrig-
4SOL – Automatic Shut-Off Valve (Not Shown)
erant pump cutout float 3F switch to open and it
remains open continuously for the duration of the pro- This valve is a customer supplied and installed valve.
grammed preset time, the refrigerant pump will be It is located upstream of the YORK-supplied control
shut down. valve. It ensures 100% shut-off during a cycling/safe-
ty shutdown or a power failure. It works in conjunc-
FLS – Flow Switch (Chilled Water)(Not Shown) – tion with the 6SOL steam condensate drain solenoid
valve. For details on this valve, refer to Form 155.16-
The purpose of this switch is to stop the unit when N3, “IsoFlow Installation Manual”.
insufficient chilled water is flowing to provide satis-
factory operation. The switch is customer-installed in 5SOL – Purge Solenoid Valve
either the chilled inlet or outlet line and wired to the
control panel. For instructions on how to install this This valve is no longer used with units that have
switch, refer to Form 155.16-N3, “IsoFlow Welsh vacuum pumps installed from the factory.
Installation Manual”.
6SOL – Steam Condensate Drain Solenoid Valve
1SOL – Motor Coolant Solenoid Valve (Steam units only) (Not Shown)
Not used on units with Buffalo Pumps. This valve is located on the condensate outlet box of
the generator shell, opposite the steam inlet. It is a
12 YORK INTERNATIONAL
YORK INTERNATIONAL
RUPTURE CONDENSER
SOLUTION SUPPLY DISK BUNDLE
PURGE VALVE HIGH-TEMPERATURE
LINE TO GENERATOR
CUTOUT SWITCH (HT1)
REFRIGERANT
PURGE DRUM ANTI-FREEZE LINE
REFRIGERANT
CONDENSATE
LINE TO
INITIAL EVAPORATOR
PURGE
VALVE
GENERATOR
OUTLET BOX
POWER
GENERATOR
PANEL
BUNDLE
CONTROL
PANEL
REFRIGERANT
LINE TO
ABSORBER
EVAPORATOR
SIGHT GLASS
SPRAYS
REFRIGERANT
LEVEL
SOLENOID ABSORBER
(3 SOL) BUNDLE
SOLUTION RETURN
SERVICE LINE FROM
VALVE GENERATOR
SOLUTION
PURGE PUMP
SOLUTION LINE PUMP REFRIGERANT
RERIGERANT REFRIGERANT 00101VIP
OUTLET BOX
FORM 155.16-OM1
TO ABSORBER PUMP CUTOUT LEVEL FLOAT REFRIGERANT
SPRAYS FLOAT SWITCH CHAMBER (1F) PUMP AUTOMATIC
(3F) DECRYSTALLIZATION
PIPE
13
normally closed (NC) valve and is energized at all switch. It has an attached thermistor, which is insert-
times during unit operation. The function of this valve ed into a thermowell that is located on the refrigerant
is to stop all steam flow through the generator when line leading out of the bottom of the refrigerant outlet
the unit is off or during a power failure. This valve is box. The switch protects the unit from freezing refrig-
shipped loose with the unit for field installation. See erant. It is factory preset to trip at 39.1°F (3.9°C). It
Form 155.16-N3, “IsoFlow Installation Manual” for will automatically reset when the temperature differ-
details on installing this valve. ence increases 5°F (2.78°C).
HP1 – High Pressure Cutout Switch (Not Shown) Control Valve (Not Shown)
This digital safety switch is located directly off the This valve is used to control the amount of heat ener-
top of the condenser shell, control panel side, and is gy (steam or hot water) that enters the generator sec-
hardwired directly into the control panel. It is factory tion of the unit.
preset to trip the unit when the unit internal pressure
reaches 710 mm Hg Abs. It will automatically reset It receives a control signal (115VAC) from the
itself when the units pressure reduces to 40 mm Hg Control Panel to open or close to control the Leaving
Abs. Chilled Water Temperature (LCWT) to the Leaving
Chilled Water Temperature Setpoint. If the heat
HT1 – High Temperature Cutout Switch source is steam, the maximum inlet temperature is
337°F (169°C). If the heat source is hot water, the
This digital safety switch is located on the control maximum inlet temperature is 266°F (130°C).
panel side of the generator shell with an accompany-
ing thermistor inserted into an adjacent thermowell. It
is hardwired directly into the control panel and facto-
CONTROL SEQUENCE
ry set to trip the unit when the generator shell skin
temperature reaches 330°F (165.6°C). It has a manu-
For Control Sequence, see Form 155.16-O3,
al reset push button and an amber light on the control
“Operators Manual – Control Panel”.
to indicate it is functioning.
14 YORK INTERNATIONAL
FORM 155.16-OM1
LD05990
YORK INTERNATIONAL 15
SYSTEM OPERATION
GENERAL
ABSORBER
CHILLED LIQUID
SOLUTION
PUMP
SOLUTION
HEAT EXCHANGER
ORIFICE LD05993
EDUCTOR
CONDENSATE
LD05994
FIG. 8 – GENERATOR
16 YORK INTERNATIONAL
FORM 155.16-OM1
CONDENSER COOLING
WATER
Concentrated solution flows by gravity and pressure
differential through the heat exchanger, where it is
cooled regeneratively by cooler dilute solution. The
heat exchanger has thus improved the efficiency of the
system by reducing the amount of steam or hot water G
required to heat the dilute solution in the generator and
the amount of concentrated solution cooling required in
the absorber.
LD05995
YORK INTERNATIONAL 17
KEY
CONCENTRATED CONDENSER CONDENSER
SOLUTION (LI.BR.) MAIN
DILUTE SOLUTION WATER AIR
(LI.BR.)
INTERMEDIATE
SOLUTION (LI. BR.)
REFRIGERANT
(WATER)
*
CHILLED LIQUID
CONDENSER
WATER
STEAM
STEAM
CHILLED LIQUID
IT
ONTROL
RT8
RT2
CONDENSER WATER
RT3
ABSORBER
3SO
REFRIGERANT LEVEL
VALVE (UNIT UNLOAD)
SOLUTION SOLUTION
HEAT EXCHANGER PUMP
REFRIGERANT
EDUCTOR PUMP
* Mild Solution at Low Loads & Low Condensing Water Temperatures except where shaded. LD04764
Note: Orifices may differ between various models.
18 YORK INTERNATIONAL
FORM 155.16-OM1
CAPACITY CONTROL
General On the chart below, these limits are indicated by lines
B and C for their corresponding ranges. The chart
The YIA control panel operates to control the capacity
assumes that the unit is free of scale and non-condens-
of the system by the throttling action of the steam
ables.
valve.
YORK INTERNATIONAL 19
solution quantity in the solution circuit, as the per- a reduction in water content as shown in Item 5. At
cent load varies. The values shown are approxi- 100% capacity, only 129 pounds of water would
mate only, and are to be taken only as indicating a still exist in the drum of solution as charged into
general trend rather than a guide for absolute set- the system. Item 6 shows that the total weight of
tings. solution would then be 341 pounds, for each drum
In Item 2, Table 1, it is noted that concentration charged into the system, and that 59 pounds of
leaving the absorber at 100% load is approximate- water would have been driven off.
ly 59.3%. At 25% load the concentration must Figure 12 shows in a rough way what happens to
drop, and would be in the order of 54.0%. By refrigerant and solution levels as the system ca-
reducing the concentration, the capacity of the pacity changes. The top view shows the levels in
absorber falls off and thus the absorption system the lower shell at 25% load. Much of the water is
capacity is reduced. back in the solution, so the solution level is cor-
This of course, as explained above, is brought respondingly high in the bottom of the shell. The
about mainly by throttling of the steam valve, so refrigerant level in the refrigerant drain pan,
that the concentration leaving the generator is as however, is relatively low. On the bottom view,
shown in Item 1, where the concentration drops also showing the lower shell, but at a 100% load
from 64.3% at peak capacity to approximately condition, much of the refrigerant has been driv-
59.0% at the 25% load condition. en from the solution, and consequently the vol-
ume of solution in the bottom shell is reduced. At
Item 3 shows rough average solution concentration
the same time there is more refrigerant in the
throughout the entire system.
refrigerant circuit and the evaporator drain pan
level is consequently high.
20 YORK INTERNATIONAL
FORM 155.16-OM1
Refrigerant Overflow – An auxiliary refrigerant of lithium bromide from the solution circuit, send-
overflow pan is located near the tube sheet in such ing this lithium bromide under a controlled basis to
a way that it can be witnessed through the evapora- the refrigerant circuit, for unlimited capacity con-
tor sight glasses. trol possibilities.
Since the amount of refrigerant in the refrigerant The amount of actual lithium bromide transferred is
circuit is at a maximum of 100% capacity, overflow kept to a minimum by introducing this lithium bro-
would normally start to take place at the 100% con- mide only when the refrigerant level in the refriger-
dition or slightly above. This overflow and sight ant circuit is at a minimum operational level, at
glass arrangement therefore provides a method which time float switch 1F signals 3SOL to open and
of charging the correct amount of refrigerant transfer solution to the refrigerant pump circuit.
into the system, provided 100% load is obtain- During normal summer operation where at least me-
able. Add refrigerant to the system until the dium load prevails, lithium bromide transfer to the
evaporator pan is at the point of overflow at this refrigerant circuit is not required and the YIA panel
100% load. Charging to this condition has the prevents transfer of solution at possible low refriger-
added advantage of providing a safety feature ant level at startup. The function blocks out operation
against over-concentration. Any tendency to of 3SOL until the chilled water temperature is with-
over-concentrate, as might be the case if the absorb- in range of normal operation.
er section operation is faulty (such as with air in the
To provide for lithium bromide removal from the
system), would be prevented to some degree by
refrigerant circuit as the system proceeds from low
overflow refrigerant into the solution.
load, low condensing water temperatures to higher
Absorber Solution Level – A large sight glass is load, higher condensing water temperatures, the sys-
provided near the bottom of the absorber shell to tem automatically transfers the lithium bromide from
observe the dilute solution level in the absorber. At the refrigerant circuit, using a combination of various
steady full load conditions, the level in the absorber means.
will be at its lowest, since the maximum amount of
1. To assist in the lithium bromide removal from the
water (removed from the solution) will be in the
refrigerant circuit as required under increasing load
refrigerant circuit. Under these conditions, the level
conditions, the IsoFlow design utilizes on its stan-
in the sight glass should be just visible at the bot-
dard unit a small amount of continuous refrigerant
tom of the sight glass. As the load decreases, less
blowdown.
refrigerant is generated out of solution and the level
in the absorber will increase until (at very light 2. The action of the system stabilizer (refrigerant valve
loads) the level in the absorber is at its maximum 2SOL) has the effect of transferring from the refrig-
(near the top of the sight glass). erant circuit.
If there is any doubt whether the unit is operating 3. At high loads and high condensing water tempera-
normally, a solution concentration check will indi- tures approaching design conditions, any residual in
cate whether excessively high solution concentra- the refrigerant circuit will be removed by a tempo-
tions are being encountered. rary evaporator pan overflow, if the lithium bromide
has not previously been removed by the combination
2. Solution and refrigerant variation with load
of the continuous blowdown and action of 2SOL.
variations at lower cooling water temperatures –
IsoFlow systems are equipped with provisions to 4. The refrigerant is gradually purified as refrigerant
accommodate low load operation (down to 10%) condensate makeup is accelerated with the increase
with cooling water temperature as low as 45°F. in load and cooling water temperature.
Referring again to Figure 11, achievement of low When it is desired to reduce the content of lithium
capacity at low cooling water temperature involves bromide in the refrigerant circuit more rapidly than
reduction of concentration in the solution circuit. would automatically occur, the service engineer
YORK is able to achieve considerable reduction of can enter the electronic panel and energize 2SOL
concentration of solution by generous use of addi- manually.
tional refrigerant in the basic design. Thus, water is It should be noted that the conditions during which
removed from the refrigerant circuit and is added to the lithium bromide content appears high are at low
the solution circuit for dilution. In the IsoFlow load and low cooling water temperature, at which
design, further dilution is brought about by removal time the evaporator pan is essentially empty and the
YORK INTERNATIONAL 21
need for the more efficient evaporation is insignifi- Capacity Control Valve Override
cant. At higher loads and cooling water tempera- Under startup conditions, and again during normal
ture, the evaporator automatically becomes totally operation with changing load or changing cooling
efficient. water temperatures, a signal may be sent to the capac-
ity control valve for maximum opening, simultaneous
ANTI-FREEZE LINE with a relatively low cooling water temperature. An
unnecessarily high solution concentration and exces-
For sustained operation at low loads and low condens- sive violent action in the generator can result. IsoFlow
ing water temperature, the concentration of lithium units provide an override control, to automatically
bromide by weight in the refrigerant circuit may reduce the maximum setting of the steam valve related
approach 35% - 40%. With conditions such as these, to cooling water temperature.
the pressures in the lower shell are reduced. The pure
water refrigerant entering the evaporator from the con- Automatic Decrystallization Control
denser would at these times be below the freezing
point of water (32°F) by as much as 12%, and could The operation of units with the ADC control circuit is
cause ice to hang up in the refrigerant condensate lines described in detail in the section "Discussion of Sub-
from the condenser after the orifices. System Operation" below.
22 YORK INTERNATIONAL
FORM 155.16-OM1
155.16-O3.1
YORK INTERNATIONAL 23
to permit refrigerant to be pumped into line (1) via con- 2SOL – Refrigerant Valve Blowdown
nection (15). The cycle will be repeated until line (8)
Manual operation of the refrigerant valve (2SOL) may
cools to approximately 150°F, or lower, signifying ease-
be selected by using the manual pump key in the
ment of the crystallization condition and normal circu-
Program mode. When this valve is energized, refriger-
lation of solution from the generator such that overflow
ant will flow through the line, into the shell side of the
into line (9) has ceased.
heat exchanger and ultimately into the absorber shell,
It must be noted that the ADC operation will continue thus transferring refrigerant back into the solution side
for at least 10 minutes regardless of a shutdown or sub- of the system.
sequent restart.
LEGEND TO FIG. 13
24 YORK INTERNATIONAL
FORM 155.16-OM1
KEY
CONCENTRATED CONDENSER CONDENSER
SOLUTION (LI.BR.)
DILUTE SOLUTION
WATER
(LI.BR.)
INTERMEDIATE
SOLUTION (LI. BR.)
REFRIGERANT
(WATER)
CHILLED LIQUID 1
CONDENSER
WATER
STEAM STEAM
C
CHILLED LIQUID
A
8
18
11
CONDENSER
13 ABSORBER
WATER
15 16
PURGE
10 DRUM 3SOL
REFRIGERANT
6 LEVEL VALVE
3
SOLUTION SOLUTION
HEAT PUMP
2
EXCHANGER ORIFICE
REFRIGERANT
4 PUMP
EDUCTOR LD04768
YORK INTERNATIONAL 25
SECTION 3 – PURGE SYSTEM OPERATION (Refer To Figure 15)
Each system is equipped with a purge pump for
removing any air and other noncondensable gases
from the system. A minimum purging sequence of
once per week is recommended.
Leak Rate Test Valve
(close for test)
Do not operate purge pump until Oil
Trap
pump has been properly charged
Gas Ballast Valve
with DUOSEAL Purge Pump Oil. (close for test)
Oil
Drain
Do not operate purge pump during Valve
LD06050
The purge system is operated as follows:
1. Start the Purge pump through the control panel.
Run the pump for 10 minutes with the gas ballast FIG. 14 – BUBBLE TESTING FOR LEAKS
valve open and check the vacuum on the gauge. It
must be 2mm Hg or less. 3. To verify the effects of the purging performed on
2. Establish the leakage rate of the purge pump and the unit:
the unit using the bubble test procedure, Fig. 14. a. After clean-up sequence, close the ballast valve
a. Purge Pump - After reading the 1-2mmHg of and proceed as mentioned in 2a. The purge
mercury vacuum that the pump is capable of pump rate should have returned to the same rate
attaining, close the ballast valve and the leak for the pump that you recorded earlier. If not,
rate test valve. Place the hose from the dis- an oil change or more clean up time may be
charge of the pump into a small container of required.
water. Insert the tube approximately 1/4" in the b. If so, then open the unit manual hand valve.
water. Wait about 5 minutes to allow all residu- After waiting 5 minutes, read the unit bubble
al air in the pump to be removed. Then count rate again. Bubble rate change from 2b to 3b
the number of bubbles leaving the hose in 1 equals the effect of purging.
minute. There should be no more than 1 to 2 c. Close the unit manual hand valve, remove dis-
bubbles. charge hose from container, and open the ballast
b. Unit - Without changing the position of the bal- valve. Stop vacuum pump via the control panel.
last valve, open the manual purge valve to the d. Repeat purging operation at each start up.
unit. Wait about 5 minutes before reading the Check unit bubble rate periodically to deter-
unit bubble rate. Usually a quantity of non-con- mine required frequency of purging. If exces-
densables have accumulated in the purge drum sive purging is required, the unit must be shut
prior to opening the unit valve. This allows down. Contact the nearest YORK Field
them to be removed so you can obtain a more Representative.
true reading of any leakage that exists in the e. If the purge pump fails to produce the desired
unit. vacuum, refer to the Purge Pump Maintenance
Then open the ballast valve on the purge pump section for details.
and purge unit for approximately 30 minutes.
Close the manual purge valve on the unit and FUNCTION
let the purge pump run for 30 minutes. This
will help to remove any condensation that Since this type of chiller operates at very low levels of
became entrained in the oil, cleaning it up. If vacuum, if there is the slightest leak in the piping
this clean-up period is not followed, the oil will some non-condensables will infiltrate the system.
have to be changed more often to maintain When this happens, there is a purging system in place
pump efficiency. for removing these non-condensable materials.
26 YORK INTERNATIONAL
FORM 155.16-OM1
PURGE DRUM
NON-CONDENSABLES
TO PURGE PUMP
COOLING COIL
U-TUBE
VAPOR RELIEF LINE U-TUBE MANOMETER
INTO EVAPORATOR ISOLATION
HAND VALVE
UNIT INITIAL
COMISSIONING
HAND VALVE
INTO SIDE
OF ABS./EVAP.
SHELL
AUX. CONNECTION
PUMP CHECK VALVE
DISCHARGE SUCTION
HOSE
LEAK RATE
TEST VALVE
GAS BALLAST VALVE
MOTOR
BUBBLE
TEST HOSE
PURGE
PUMP
OIL DRAIN
LD05998
YORK INTERNATIONAL 27
The most common non-condensables found in the COOLING WATER
FROM CONDENSER
purge exhaust of an absorption-type chiller are as fol- CIRCUIT
lows: nitrogen (N ), anhydrous ammonia (NH ),
2 3
SYSTEM DETAILS
CONDENSER
WATER CONNECTIONS
FOR THE COOLING COIL
OPEN ONLY
WHEN PURGING
FROM UNIT
PURGE
OPEN ONLY ON INITIAL START-UP HAND VALVE
DRUM
TO PURGE FROM UPPER PORTION
OF ABSORBER SHELL AND EVAPORATOR
U-TUBE
MANOMETER
U-TUBE
VAPOR RELIEF LINE
VALVE
INTO EVAPORATOR
RELIEF LINES
INTO EVAPORATOR
DILUTE
SOLUTION
FROM DISCHARGE OIL
LINE OF SOLUTION PUMP TRAP
GAS SAMPLE DISCHARGE
FROM ABSORBER
PURGE HEADER
MOTOR PUMP
SOLUTION RETURN
TO ABSORBER
28 YORK INTERNATIONAL
FORM 155.16-OM1
Cleanliness
Take every precaution to prevent foreign particles Purge
from entering the pump. A fine mesh screen is pro- Pump
Oil Drain
vided for this purpose in the intake passage of all
LD06051
YORK Vacuum Pumps.
FIG. 18 – PURGE PUMP PIPING AND VALVES -
NORMAL OPERATION
Types of Lubricants
All YORK mechanical vacuum pumps are tested with
DUOSEAL® oil and shipped with a full charge to pre- The Presence and Removal of Condensate -
vent unnecessary contamination. DUOSEAL® oil has Condensation takes place particularly in the compres-
been especially prepared and is ideally suited for use sion stroke of the second stage of a two-stage pump.
in mechanical vacuum pumps because of its desirable The compression stroke is that portion of the cycle
viscosity, low vapor pressure and chemical stability. during which the gas drawn from the intake port is
compressed to the pressure necessary to expel it past
The vacuum guarantee on all YORK vacuum pumps the exhaust valve. Condensation takes place when the
applies only when DUOSEAL® oil is used. ratio between the initial pressure and the end pressure
of the compression is high, that is, when the mixture
PURGE PUMP PIPING AND OPERATING VALVES of vapor and gas drawn from the intake port is com-
pressed from a low pressure to a high pressure. By
The purge pump piping and valves, illustrated in adding air through the gas ballast valve to the mixture
Figure 15, is installed at the factory and can be used of vapor and gas being compressed, the pressure
for several functions. During normal operation, both required for delivery past the exhaust valve is reached
the gas ballast and the leak rate test valve must be with a considerably smaller reduction of volume of
open at all times. the mixture; thus, depending upon the amount of air
added, condensation of the vapor is either entirely
The Principle of Gas Ballast avoided or substantially reduced.
The Effects of Unwanted Vapor - Systems which
contain undesirable vapors cause difficulty from both OIL LEVEL DETERMINATION
the standpoint of attaining desirable ultimate pres-
sures, as well as contamination of the lubricating The amount of oil suitable for efficient and satisfacto-
medium. A vapor is defined as the gaseous form of ry performance should be determined after the pump
any substance which is usually a liquid or a solid. has reached its operating temperature. Initially, how-
Refrigerant (water) and alcohol vapors are two of the ever, the pump should be filled with fresh oil while
most common vapors encountered in absorption the pump is idle. Fill the pump through the pump dis-
chillers. When such vapors exist in a system, the charge port until the oil level falls halfway up the oil
vapors or mixtures of gas and vapor are subject to level window. If after a short period of operation, the
condensation within the pump. This precipitated liq- level should fall, it is likely the result of oil entering
uid may dissolve or become emulsified with the oil. some of the interior pockets of the pump. If the oil
This emulsion is recirculated to the chambers of the level rises, this signifies oil had drained into the pump
pump where it is again volatized, causing increased cavity while idle. Shut off pump, then drain oil down
pressure within the system. to proper level.
YORK INTERNATIONAL 29
If a gurgling sound occurs, additional oil may need to (3) when a large leak is present in the system; and (4)
be added. Mechanical pumps will gurgle in varying when the gas ballast is open. Best performance of a
degrees under four conditions of performance: (1) mechanical pump is generally obtained after suffi-
when operating at high pressure as in the beginning cient time has been allowed for the pump to come to
cycles of evacuation of the purge drum; (2) when the operating temperature.
oil level in the pump reservoir is lower than required;
30 YORK INTERNATIONAL
FORM 155.16-OM1
YORK INTERNATIONAL 31
DRIVE PROBLEMS operates properly try hand-rotating the pump in the
proper direction with the pump intake port open. If
When troubleshooting drive prob- both turn freely, then replace the belt and check the
lems or checking belt tension, belt tension. The tension should be sufficient to drive
always shut-off and lock out power the pump without visible slippage. Any greater ten-
at the main disconnect switch. sion will cause noise and possible damage to the bear-
ings of both the motor and pump. Make certain that
both pulley grooves are clean and free from oil. The
If for any reason the pump will not operate, turn off pulleys must be fastened securely on their respective
and lock out the power at the main circuit breaker or shafts, and in parallel alignment. Re-install the belt
disconnect. Check the overload assembly and electri- guard and check for proper operation and amperage.
cal connections. Remove the guard cover followed by
the belt. Re-establish power to the pump. If the motor Replace or re-build any defective components.
32 YORK INTERNATIONAL
FORM 155.16-OM1
19-1/4"
41-2111 BASE
17-3/4"
5-1/2"
3"
11-1/2"
10-1/4"
3"
11"
9-1/2"
6"
5-5/16"
3-13/16"
3/4 - 20 THREAD
1-20 THREAD
15-5/8"
41-0669 MTG. STRIP
2-01-0312 BOLT
2-61-3100 WASHER
11-1/16"
5-5/16"
3-1/2"
2"
2-01-0316 BOLT
4-7/8" 7-3/16" 41-2363 WASHER
41-0929 BUMPER
2-35-3800 NUT
2-02-5708 SCREW
10" (+/-1/4") LD05105B
SPECIFICATIONS:
Free- Air Displacement, L/M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .160
CFM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.6
Guaranteed Partial Pressure
Blankoff, millitorr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.1
Pump Rotational Speed, RPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .525
Number of Stages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Oil Capacity, qts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1/4
Net Weight, Pump Only, lbs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82
Net Weight, Mounted Pump, lbs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112
Shipping Weight, Mounted Pump, lbs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125
YORK INTERNATIONAL 33
SECTION 6 – BUFFALO PUMPS
34 YORK INTERNATIONAL
FORM 155.16-OM1
LD05106A
YORK INTERNATIONAL 35
SECTION 7 – STEAM AND WATER QUALITY CONTROL
36 YORK INTERNATIONAL
FORM 155.16-OM1
It is equally important that the owner (operator) of the A build-up of scale on the tubes can cause a wide
equipment performs an inspection of the generator range of problems including:
tubes at the frequencies recommended in the Tube
Bundle Section of the "Preventive Maintenance • Reduced chilling capacity
Schedule" located in this manual. In addition to peri- • High solution concentration and
odic cleaning with tube brushes, tubes must be crystallization.
inspected for wear and corrosion. Tube failures usu-
ally occur due to corrosion, erosion, and fatigue due • Pitting and corrosion of tubes
to thermal stress. Eddy current analysis and visual • Reduced efficiency.
inspection by boroscope of all tubes are invaluable
preventative maintenance methods. These provide a The first step in trying to clean scales from tubes is to
quick method of determining steam generator tube brush clean them. Only soft nylon brushes should be
condition at a reasonable cost. used, as damage to the copper or CuNi tubes will
result if harder brushes (such as steel) are used.
Your local YORK Service Representative will be
more than happy to supply any or all of these If the brush cleaning is unsuccessful in removing all
services. the scale from the tubes, it will be necessary to chem-
ically clean them. An experienced and reputable con-
TUBE CLEANING tractor should be consulted. If the chemical cleaning
is not performed properly, extensive tube damage may
If during an inspection, scale is identified in any of the result.
tube bundles, it will be necessary to remove this scale
to prevent operational and or corrosion problems.
YORK INTERNATIONAL 37
SECTION 8 – UNIT OPERATING PROCEDURES
GENERAL
Refer to the chart in Fig. 21 to compare the saturation
The YORK recommended installation of these pressure within the unit to the equivalent plant room
absorption systems calls for complete automatic oper- temperature. If the measured internal unit pressure is
ation. The system and all of the auxiliaries are con- within the shaded area of the chart, the start-up may
trolled by a switch on the control panel or by a remote continue. If not, purge the unit until the internal unit
control, such as a thermostat, time clock or other pressure reaches the shaded area of the chart.
external control.
Open the main shut-off valves in condensing water,
It is recommended that Manual/Off/ chilled water, and steam or hot water supply lines to
Automatic switches be used for con- the system.
trol of the condensing water pump,
the chilled water pump, and the Close all disconnect switches to the control panel, the
tower fan motor. However, it is cau- cooling water pump, chilled water pump, and tower
tioned that the chilled water pump fans.
and the condensing water pump
Place the condensing water pump, chilled water
must always be operating when the
pump, and tower fan switches in the "Automatic"
unit is operating, and are thus pre- position. (If manual operation is required for special
ferred in the "Automatic" position. considerations, refer to the NOTE under General).
This is necessary to (1) provide prop-
er dilution of the solution, thus pro-
tecting against crystallization during 50
shutdown, and (2) to avoid freezing
up the evaporator tubes during unit
operation, including the dilution
cycle operation during which refrig-
eration effect still occurs.
PRESSURE IN mm Hg Abs.
10
START-UP (NORMAL)
38 YORK INTERNATIONAL
FORM 155.16-OM1
The Control valve will close and the unit will go into Inadvertent introduction of air into the unit by the
a dilution cycle. operator or the existence of leaks are to be avoided at
all times for the attainment of long life of the unit. The
As there are many types of unit shutdowns possible, proper method of taking samples is tedious and
please refer to Form 155.16-O3, “Control Panel requires special training so that conclusions reached
Operation” for a description of each. concerning the condition of the unit, the solution
chemistry and the cooling water are valid.
OPERATING DATA
For greatest accuracy of the data taken on operating
General units, calibrated 1/5°F increment thermometers
should be used, particularly for measuring tempera-
A complete set of data on operating temperatures and
tures of chilled water and cooling water. Calibrated
pressures should be recorded for the unit regularly
test type pressure gauges and manometers also con-
(every week is suggested as optimum). The purpose is
tribute to the attainment of accurate data. Accurate
to permit early recognition of an abnormal condition
flow meters for water and steam condensate flow
or trend that requires corrective maintenance, before
(with a subcooler) complete the instrumentation
serious damage occurs to the unit. Daily observation
requirements for the attainment of an accurate heat
of the unit is useful to disclose any sudden changes.
balance. This instrumentation is not normally avail-
able in the field. However, it can be obtained by spe-
All measurements that are recorded should be taken
cial arrangements.
as simultaneously as possible with a steady load and a
steady cooling tower water temperature, near the
Nevertheless, a measure of the trend of system per-
design conditions. A progressive gradual deteriora-
formance can be obtained by the systematic measure-
tion in unit performance is an indication that scaling
ment of data taken with instrumentation normally
is occurring, that there is a gradual buildup of inerts or
available in the field. In all cases, however, any analy-
that there is a malfunction of controls. It is mandato-
sis is only as good as the degree of accuracy of the
ry that all performance analyses be based on date, and
data taken. A steady state of operating conditions with
taken on units that are free of leaks. Otherwise, the
all readings taken as simultaneously as possible,
lithium bromide concentrations and the steam pres-
assists in obtaining valid data. All thermometers and
sure and steam flow requirements for a given load, as
pressure measuring devices should be calibrated so
well as a complete set of operating temperatures, will
that readings are corrected to the true values.
be abnormal.
Insulation placed around the pipe and the outside well
will improve the accuracy and validity of readings.
A thorough check of system performance, including
sampling of the unit fluids, requires the services of a
With the assumption that all data taken are accurate
YORK Field Service Representative. He will take
and valid, the following method of analysis for sys-
samples of the refrigerant, the lithium bromide
tem performance is recommended.
charge, and the cooling water, as well as a complete
set of operating data. He can assist in a complete per-
YORK INTERNATIONAL 39
Performance Data and Calculations 100% Design Load 517.9 Tons
Condenser Water Flow 1870 GPM
Refer to the sample operating data sheet in Figure 22.
Entering Condenser Water Temp 85°F
This data is simulated by a computer for a YIA-6C4
Chilled Water Flow 1243 GPM
unit with nominal passes. The assumed operating con- Chilled Water Range 54°F to 44°F
dition is 80% of the design load rating with assumed
fouling factors of .0005, .001 and .0015 in the Passes - Chiller/Condenser/Absorber 2/1/1
absorber and condenser, but with .0005 in the evapo- Fouling Factor for Absorber,
rator tubes. The effect of fouling on all readings is Condenser and Evaporator .0005
readily apparent. This data also assumes that the Steam Pressure at Generator 9.2 PSIG
2-Ethyl-1-Hexanol additive is present in the unit at Steam Flow 9478 lb/hr
the proper concentration to promote optimum shell Valve Inlet Steam Pressure 12PSIG =
side coefficients of heat transfer. This additive is 299°F
charged into the unit upon initial start-up, and rarely Normal Installation Ambient Pressure 29.5" Hg
does more Hexanol have to be added. The effect of (14.5 PSIA)
Hexanol additive on unit performance appears later in Steam Source 15PSIG @ 300°F
this section.
Assume steam condensate is flashed at atmospheric
The design load rating for the YIA-6C4 unit used for pressure before it is weighed for test data purposes.
the data simulation is as follows:
40 YORK INTERNATIONAL
FORM 155.16-OM1
LD04771
42 YORK INTERNATIONAL
FORM 155.16-OM1 FORM 155.16-OM1
TEMPERATURE ˚F
20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230
100
90
80
70
60
R
50 TE
WA E
N LIN
40 PERCENT OF CONCENTRATION (LI. BR. BY WEIGHT) 0 10 15 20 30 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 6 TIO
35 40 45 6 L IZA
AL
YST
CR
30
20
ABSOLUTE PRESSURE M. M. MERCURY
10
9
8
7
6
0 10 1520 30 5 45 51 53 9 61 64
3 3 40 50 52 54 55 56 57 58 5 60 62 63
PTX CHART
2 CRYSTALLIZATION AREA
1.0
.9
.8
.7
.6
.5
.4
.3
20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230
TEMPERATURE ˚F LD05216
Power failures result in the unit pumps stopping com- Non-condensables in the Absorber to make design capacity, the firing rate will be suffi- a. Refrigerant temperature leaving the condenser -
pletely. Without the pumps inducing flow through the cient to raise the solution concentration higher than (RTLC) at RT9.
Non-condensables in the absorber result in less refrig-
various sections of the unit, concentrated solution the design 5%. This will result in even higher solution b. Strong solution temperature at RT3.
erant being absorbed by the solution. The solution
becomes trapped in the generator section and the solu- concentrations leaving the generator. The temperature
never gets as diluted as it should. It leaves the c. Leaving chilled water temperature - (LCWT)
tion-to- solution heat exchanger. If this concentrated of the solution leaving the absorber will also be lower
absorber and is heated in the generator. If the unit's at RT1.
solution is allowed to cool down to a low enough tem- than normal due to the amount of subcooling that will
heat input is at or near full load, the leaving solution RT9 and RT3 have operating ranges in relation-
perature, it may turn to a slushy liquid and eventually be present as a result of the lack of mass transfer tak-
concentration may exceed the level at which it can ship to each other for normal unit conditions. If
to a solid substance. ing place. This will result in a greater potential for
remain liquid when passing through the solution-to- the strong solution temperature exceeds the allow-
over cooling the concentrated solution in the solution-
solution heat exchanger. For example, the normal con- able limit, steam or hot water control valve load-
The potential for a YORK IsoFlowTM Chiller to crys- to-solution heat exchanger.
centration of solution leaving the absorber at full load ing is inhibited and the RTLC/strong solution
tallize during a power interruption is directly related
is between 58% and 59.3%. If there are non-condens- Fluctuating Tower Water Temperature temperature algorithm is enabled to slowly pulse
to the following:
ables present in the absorber, the solution concentra- the valve closed, until the strong solution temper-
tion may exceed 61%. Since the unit is attempting to Rapidly fluctuating tower water temperature can also
1. The concentration of the solution in the solution ature is less than or equal to the limit. See YORK
operate at full load, the firing rate will be sufficient to cause crystallization. The reasons are essentially the
heat exchanger is very important. The higher the Form 155.16-O3 for details on this feature.
raise the solution concentration in the generator by at same as described in the previous example. Rapidly
concentration at the time of power failure, the falling tower water temperature will cause the leaving If the unit is equipped with Eprom A.02F.01:
least the same amount as when the absorber solution
more likely the unit is to crystallize. solution temperature from the absorber to drop quick- Low Entering Condenser Water Temp Load Limit
was normal, which was approximately 5%. Raising
a. The higher the load, the higher the ly. This cool solution may over-cool the concentrated replaces the Strong Solution Temp Control and the
the solution concentration by 5% would result in 66%
concentration. solution leaving the generator as it passes on the shell micro panel will also monitor the Entering Tower
solution leaving the generator. Referring to the PTX
side of the solution-to-solution heat exchanger. This Water temperature through RT5. After a 30 minute
b. A unit with dirty tubes or non-condensables chart in Figure 23, it can be seen that the crystalliza-
can happen at normal generator solution concentra- bypass at unit start, whenever the entering con-
will be more susceptible due to higher concen- tion temperature for 66% solution is approximately
tions, although, of course, the problem would be com- denser water temperature is less than 74°F
trations in the solution heat exchanger. 120°F (49°C). Since the generator temperature is
pounded if there were already abnormally high solu- (23.2°C), the maximum allowed steam/hot water
c. Overfiring the unit will tend to over concen- higher than 120°F (49°C), the solution will be okay
tion concentrations in the generator. valve position is limited. Units equipped with
trate the strong solution and make it more while it is still in the generator. The problem occurs
Eprom A.02F.02 and later: in addition to requir-
susceptible for crystallization. when this over concentrated solution passes through
Features That Will Help Prevent Crystallization ing the entering condenser water temperature to be
the solution-to-solution heat exchanger on its way
2. The ambient temperature of the machine room From Occurring less than 74°F (23.2°C), the strong solution tem-
back to the absorber sprays. Since this solution con-
and the amount of thermal insulation on the solu- perature must be equal to or greater than the Low
centration remains constant as it passes through the YORK IsoFlowTM chillers have several features that
tion-to-solution heat exchanger will also deter- Entering Condenser Water Temperature
solution-to- solution heat exchanger, if it is cooled will help prevent crystallization from occurring. They
mine the likelihood of crystallization. Improper or (ECDWT) Solution temp override setpoint to per-
below 120°F (49°C) at any point in the route, crystal- are as follows:
inadequate thermal insulation on the hot sections form the control valve limiting to approximately
lization will begin. The cool solution leaving the
of the unit will allow heat loss to progress rapidly 60%. For more details on these features, see
absorber is the solution-to-solution heat exchanger's
and therefore shorten the amount of time before 1. The refrigerant charge is adjusted at full load, with YORK Form 155.16-O3.
medium that cools the concentrated solution leaving
the concentrated solution cools down to its crys- no non-condensables present, so that refrigerant is 3. The third type of crystallization prevention is
the generator as it passes on the shell side of the solu-
tallization temperature. just ready to spill over the evaporator pan to the though the Automatic Decrystallization Cycle
tion-to-solution heat exchanger. This relatively cool
Outside air dampers that remain open during a solution's temperature is the determining factor of absorber. Therefore, if the absorber ever begins to (ADC). Essentially, when crystallization starts to
power failure may allow the plant room to cool whether crystallization occurs. Tower water inlet tem- malfunction due to the presence of non-condens- occur, a blockage usually forms in the strong solu-
down quickly, which will hasten crystallization. perature will greatly affect the leaving solution tem- ables or dirty tubes, the solution concentration will tion side of the solution-to-solution heat exchang-
3. The duration of the power interruption is very perature of the absorber. If the tower water tempera- increase (less refrigerant present in solution). er. This blockage inhibits the solution from flow-
important. Although it is very difficult to quantify ture is lower than design or is allowed to fluctuate in Consequently, the refrigerant quantity in the evap- ing through the solution-to-solution heat exchang-
the acceptable time before crystallization occurs, a downward trend fairly rapidly, the potential exists to orator pan will increase and begin to spill over er and the solution starts to back-up into the gen-
it is doubtful that harmful crystallization will over cool the concentrated solution in the solution-to- into the absorber solution, resulting in a concen- erator. Solution starts to fill the generator outlet
occur if the power interruption is less than fifteen solution heat exchanger. Crystallization will then tration reduction. box and begins exiting through the ADC line.
minutes. Thirty minute or longer power interrup- result. 2. For units with Eprom version A.02F.00: RT2, attached to the side of the ADC line senses
tions have been experienced during full load oper- Whenever the unit is running, a feature called the temperature rise in this line due to the high
ation of some machines with no problems. To further compound this type of situation, if the Strong Solution Temperature Control is used. The temperature solution flowing through it. At 160°F
absorber is not performing well due to the presence micro panel software continually monitors three (71.1°C) the micro panel will energize 2SOL
Although a more rare occurrence, units can also crys- of non-condensables, the amount of solution flowing different temperatures throughout the system as (Stabilizer or decrystallize solenoid valve) to
tallize during operation. Two of the chief causes of to the generator will be less than normal since there follows: allow refrigerant to flow from the discharge of the
crystallization during operation are non-condensables is less refrigerant in it. Since the unit is attempting refrigerant pump into the solution-to-solution heat
in the absorber and rapidly fluctuating tower water exchanger, thus diluting the solution.
temperatures.
Power failures result in the unit pumps stopping com- Non-condensables in the Absorber to make design capacity, the firing rate will be suffi- a. Refrigerant temperature leaving the condenser -
pletely. Without the pumps inducing flow through the cient to raise the solution concentration higher than (RTLC) at RT9.
Non-condensables in the absorber result in less refrig-
various sections of the unit, concentrated solution the design 5%. This will result in even higher solution b. Strong solution temperature at RT3.
erant being absorbed by the solution. The solution
becomes trapped in the generator section and the solu- concentrations leaving the generator. The temperature
never gets as diluted as it should. It leaves the c. Leaving chilled water temperature - (LCWT)
tion-to- solution heat exchanger. If this concentrated of the solution leaving the absorber will also be lower
absorber and is heated in the generator. If the unit's at RT1.
solution is allowed to cool down to a low enough tem- than normal due to the amount of subcooling that will
heat input is at or near full load, the leaving solution RT9 and RT3 have operating ranges in relation-
perature, it may turn to a slushy liquid and eventually be present as a result of the lack of mass transfer tak-
concentration may exceed the level at which it can ship to each other for normal unit conditions. If
to a solid substance. ing place. This will result in a greater potential for
remain liquid when passing through the solution-to- the strong solution temperature exceeds the allow-
over cooling the concentrated solution in the solution-
solution heat exchanger. For example, the normal con- able limit, steam or hot water control valve load-
The potential for a YORK IsoFlowTM Chiller to crys- to-solution heat exchanger.
centration of solution leaving the absorber at full load ing is inhibited and the RTLC/strong solution
tallize during a power interruption is directly related
is between 58% and 59.3%. If there are non-condens- Fluctuating Tower Water Temperature temperature algorithm is enabled to slowly pulse
to the following:
ables present in the absorber, the solution concentra- the valve closed, until the strong solution temper-
tion may exceed 61%. Since the unit is attempting to Rapidly fluctuating tower water temperature can also
1. The concentration of the solution in the solution ature is less than or equal to the limit. See YORK
operate at full load, the firing rate will be sufficient to cause crystallization. The reasons are essentially the
heat exchanger is very important. The higher the Form 155.16-O3 for details on this feature.
raise the solution concentration in the generator by at same as described in the previous example. Rapidly
concentration at the time of power failure, the falling tower water temperature will cause the leaving If the unit is equipped with Eprom A.02F.01:
least the same amount as when the absorber solution
more likely the unit is to crystallize. solution temperature from the absorber to drop quick- Low Entering Condenser Water Temp Load Limit
was normal, which was approximately 5%. Raising
a. The higher the load, the higher the ly. This cool solution may over-cool the concentrated replaces the Strong Solution Temp Control and the
the solution concentration by 5% would result in 66%
concentration. solution leaving the generator as it passes on the shell micro panel will also monitor the Entering Tower
solution leaving the generator. Referring to the PTX
side of the solution-to-solution heat exchanger. This Water temperature through RT5. After a 30 minute
b. A unit with dirty tubes or non-condensables chart in Figure 23, it can be seen that the crystalliza-
can happen at normal generator solution concentra- bypass at unit start, whenever the entering con-
will be more susceptible due to higher concen- tion temperature for 66% solution is approximately
tions, although, of course, the problem would be com- denser water temperature is less than 74°F
trations in the solution heat exchanger. 120°F (49°C). Since the generator temperature is
pounded if there were already abnormally high solu- (23.2°C), the maximum allowed steam/hot water
c. Overfiring the unit will tend to over concen- higher than 120°F (49°C), the solution will be okay
tion concentrations in the generator. valve position is limited. Units equipped with
trate the strong solution and make it more while it is still in the generator. The problem occurs
Eprom A.02F.02 and later: in addition to requir-
susceptible for crystallization. when this over concentrated solution passes through
Features That Will Help Prevent Crystallization ing the entering condenser water temperature to be
the solution-to-solution heat exchanger on its way
2. The ambient temperature of the machine room From Occurring less than 74°F (23.2°C), the strong solution tem-
back to the absorber sprays. Since this solution con-
and the amount of thermal insulation on the solu- perature must be equal to or greater than the Low
centration remains constant as it passes through the YORK IsoFlowTM chillers have several features that
tion-to-solution heat exchanger will also deter- Entering Condenser Water Temperature
solution-to- solution heat exchanger, if it is cooled will help prevent crystallization from occurring. They
mine the likelihood of crystallization. Improper or (ECDWT) Solution temp override setpoint to per-
below 120°F (49°C) at any point in the route, crystal- are as follows:
inadequate thermal insulation on the hot sections form the control valve limiting to approximately
lization will begin. The cool solution leaving the
of the unit will allow heat loss to progress rapidly 60%. For more details on these features, see
absorber is the solution-to-solution heat exchanger's
and therefore shorten the amount of time before 1. The refrigerant charge is adjusted at full load, with YORK Form 155.16-O3.
medium that cools the concentrated solution leaving
the concentrated solution cools down to its crys- no non-condensables present, so that refrigerant is 3. The third type of crystallization prevention is
the generator as it passes on the shell side of the solu-
tallization temperature. just ready to spill over the evaporator pan to the though the Automatic Decrystallization Cycle
tion-to-solution heat exchanger. This relatively cool
Outside air dampers that remain open during a solution's temperature is the determining factor of absorber. Therefore, if the absorber ever begins to (ADC). Essentially, when crystallization starts to
power failure may allow the plant room to cool whether crystallization occurs. Tower water inlet tem- malfunction due to the presence of non-condens- occur, a blockage usually forms in the strong solu-
down quickly, which will hasten crystallization. perature will greatly affect the leaving solution tem- ables or dirty tubes, the solution concentration will tion side of the solution-to-solution heat exchang-
3. The duration of the power interruption is very perature of the absorber. If the tower water tempera- increase (less refrigerant present in solution). er. This blockage inhibits the solution from flow-
important. Although it is very difficult to quantify ture is lower than design or is allowed to fluctuate in Consequently, the refrigerant quantity in the evap- ing through the solution-to-solution heat exchang-
the acceptable time before crystallization occurs, a downward trend fairly rapidly, the potential exists to orator pan will increase and begin to spill over er and the solution starts to back-up into the gen-
it is doubtful that harmful crystallization will over cool the concentrated solution in the solution-to- into the absorber solution, resulting in a concen- erator. Solution starts to fill the generator outlet
occur if the power interruption is less than fifteen solution heat exchanger. Crystallization will then tration reduction. box and begins exiting through the ADC line.
minutes. Thirty minute or longer power interrup- result. 2. For units with Eprom version A.02F.00: RT2, attached to the side of the ADC line senses
tions have been experienced during full load oper- Whenever the unit is running, a feature called the temperature rise in this line due to the high
ation of some machines with no problems. To further compound this type of situation, if the Strong Solution Temperature Control is used. The temperature solution flowing through it. At 160°F
absorber is not performing well due to the presence micro panel software continually monitors three (71.1°C) the micro panel will energize 2SOL
Although a more rare occurrence, units can also crys- of non-condensables, the amount of solution flowing different temperatures throughout the system as (Stabilizer or decrystallize solenoid valve) to
tallize during operation. Two of the chief causes of to the generator will be less than normal since there follows: allow refrigerant to flow from the discharge of the
crystallization during operation are non-condensables is less refrigerant in it. Since the unit is attempting refrigerant pump into the solution-to-solution heat
in the absorber and rapidly fluctuating tower water exchanger, thus diluting the solution.
temperatures.
Measures to Prevent Crystallization gauges are not located at the same elevation or level.
Good practices to help prevent crystallization should The conversion from PSI to ft. of water is 2.31 ft. for
be employed. These include: 1 PSI.
1. Insulating the solution-to-solution heat exchang-
REFRIGERANT CONCENTRATION
er, generator solution outlet box and all intercon-
necting piping. Operation at low loads and low condensing water
2. Tower water (absorber cooling water) must temperatures will cause solution to be brought over to
be controlled to prevent rapid fluctuations in the refrigerant circuit to sustain operation and avoid
temperature. extensive cavitation of the refrigerant pump. At such
3. Keep absorber, condenser and evaporator tubes times that a system analysis is conducted at high load
clean. and high condensing water temperature, the solution
4. Do not allow non-condensables to accumulate in in the refrigerant circuit would have been appreciably
the unit. Proper purging techniques and solution diluted, by virtue of the full evaporator pan that devel-
chemistry control will greatly reduce the likeli- ops. With the effect of blowdown and possibly some
hood of crystallization. spillover, the refrigerant concentration level is proba-
bly very near 1.00 S.G. Considering the intent of an
5. Be sure the refrigerant charge is adjusted so that
analysis, it may be desirable to route some of the
refrigerant spill will occur if solution concentra-
refrigerant back to the absorber via the refrigerant
tions exceed the norm. Refrigerant may need to
valve (2 SOL) to establish a still cleaner refrigerant.
be adjusted after several years of operation due to
For refrigerant blowdown, see "Control Components
the amount of refrigerant vapor removed during
External To The Control Center" for this operation.
purging.
During refrigerant blowdown, stop
PRESSURE DROP CURVES
the refrigerant pump immediately
Figure 24 shows the pressure drops for the chilled on pump cavitation noise or from
water, condenser water, and the hot water in relation- indications on a pressure gauge
ship to the rate of flow in GPM. The absorber/con- on pump discharge (fluctuating
denser includes 1 - 2 PSI pressure drop through the wildly).
cross-over line. For construction of the cross-over
line, see YORK Form 155.16-N3. The data shown At minimum loads (10%) and minimum condensing
are for pressure taps on the water boxes near the water temperature, the concentration in this circuit
inlet and outlet nozzles. If pressure gauges are used could reach 35 to 40% by weight lithium bromide. As
to determine pressure drop, they should be calibrated the load increases and the pan fills, this concentration
so that maximum efficiency is obtained. Also, a cor- will diminish and eventually be very slight or non-
rection for static head difference must be made if the existent.
YORK INTERNATIONAL 45
PRESSURE DROP CURVES
MODEL YIA – 1A1 MODEL YIA – 1A2
70
50
S
30
AS
4P
S
AS
20
3P
S
AS
2P
10
S
AS
6
1P
4
1000
1600
100
200
300
400
500
700
GPM
LD01506 CHILLED WATER LD01509
50
40
SS
PA
20 SS 20 3/1
PA ND SS
3/1 SS PA
ND PA S/CO 2/1
O 2/1 AB D
S/C D 10 ON
10 AB ON S/C
BS/C AB
A 7
7
ER
5 ENS
5 ER ND
NS CO
NDE 3
CO
1
200
300
400
500
600
700
1
200
300
400
500
600
700
GPM
GPM LD01511
TOWER WATER *
LD01508 TOWER WATER *
30
20
20
SS
PRESSURE DROP–FT. WATER
SS
PA
PA
3
10
10
SS
SS
PA
PA
7
2
2
5
5
S
SS
AS
PA
1P
3
2
2
1
1
90
100
200
300
400
500
90
100
200
300
400
500
GPM
GPM
HOT WATER LD01507 LD01510
* See Notes on page 56. HOT WATER
SS
40 40
PA
AS
SS
30
4
4P
30
PA
S
AS
3
20
3P
20
SS
S
AS
PA
2P
2
10 10
SS
PA
S
7 7
AS
1
1P
5 5
4
3 3
2 2
1 1
1600
1000
100
200
300
400
500
700
1000
1600
100
200
300
400
500
700
GPM GPM
LD01512
LD01515
CHILLED WATER CHILLED WATER
50 60
40 SS
30 PA PA
3/1
30 3/1
D ND
20 ON SS 20 CO SS
S/C PA BS/ PA
AB 2/1 A 2/1
D D
ON ON
10 S/C 10 S/C
AB 8 AB
7
6
5 R ER
SE 4 ENS
DEN ND
3 3
N CO
CO
2 2
1 1
1000
200
300
400
500
600
800
1000
200
300
400
500
600
700
800
GPM GPM
30 30
20 20 SS
SS
PA
PA
3
PRESSURE DROP–FT. WATER
SS
PA
10 2
SS
10
PA
8
2
7 6 SS
PA
SS
5 1
PA
5
4
1
4
3
3
2
2
1
90
100
200
300
400
500
1
90
100
200
300
400
500
GPM
GPM LD01513 HOT WATER LD01516
HOT WATER
YORK INTERNATIONAL 47
MODEL YIA – 2B1 MODEL YIA – 3B2
80 80
60 60
PRESSURE DROP–FT. WATER
SS
SS
PA
SS
30
SS
PA
30
PA
PA
4
SS
SS
3
20
3
20
PA
PA
2
2
SS
S
10
AS
10
PA
1P
1
7 7
5 5
3 3
2 2
1 1
1000
2100
120
200
300
400
500
600
800
1000
2100
120
200
300
400
500
600
800
GPM LD01518 GPM LD01521
60 60
40 40
PRESSURE DROP–FT. WATER
PRESSURE DROP–FT. WATER
SS SS
PA 30 PA
30 3/1
3/1 D
ND SS SS ON SS
20 CO PA PA 20 S/C PA
/ /1 /1 AB 2/1 SS
BS 2 1 D PA
A ND D N 1/1
CO ON S/C
O D
10 S/ S /C 10 AB ON
AB
AB BS/C
A
7 7
5 5
4 ER
4
3 NS 3 ER
E NS
ND NDE
2 CO 2 CO
1 1
1500
375
500
600
700
800
900
1000
1000
1100
200
300
400
500
600
700
800
GPM GPM
LD01520
LD01523
TOWER WATER * TOWER WATER *
40 40
30 30
SS
PA
SS
20 20 3
PA
PRESSURE DROP–FT. WATER
SS
PA
SS
10 10 2
PA
2
8 8
6
SS
6
SS
PA
5 5
PA
1
1
4 4
3 3
2 2
1 1
100
200
300
400
500
650
100
200
300
400
500
650
GPM GPM
LD01519 LD01522
* See Notes on page 56. HOT WATER HOT WATER
80 80
60 60
SS
SS
40 40
SS
PA
PA
SS
30
PA
30
4
4
PA
SS
3
3
SS
PA
20 20
PA
2
2
SS
SS
PA
10 10
PA
1
1
7 7
5 5
3 3
2 2
1 1
1000
2100
120
200
300
400
500
600
800
1000
2100
120
200
300
400
500
600
800
GPM GPM
LD01524 LD01527
CHILLED WATER CHILLED WATER
60 65
40 SS SS
PA 40
PRESSURE DROP–FT. WATER
1 1
1500
375
500
600
700
800
900
1000
375
500
600
700
800
900
1000
1500
GPM GPM
LD01526 LD01529
TOWER WATER * TOWER WATER *
40 40
30 30
S
AS
20
AS
PRESSURE DROP–FT. WATER
3P
PRESSURE DROP–FT. WATER
3P
20
S
AS
S
AS
2P
2P
10
10
8
8
S
S
AS
AS
6
1P
1P
6
5 5
4 4
3 3
2 2
100
200
300
400
500
650
100
200
300
400
500
650
GPM GPM
LD01525 LD01528
* See Notes on page 56. HOT WATER HOT WATER
SS
40
SS
SS
PA
SS
PA
30 30
PA
4
PA
4
SS
SS
3
3
20
PA
20
PA
2
2
SS
SS
10
PA
10
PA
1
1
7 7
5 5
3 3
2 2
1 1
1000
2000
3000
200
300
400
500
600
800
1000
2000
3000
200
300
400
500
600
800
GPM GPM
LD01530 LD01533
CHILLED WATER CHILLED WATER
65 65
SS
PRESSURE DROP–FT. WATER
1 1
1000
1600
1000
2000
2200
400
500
600
700
800
900
500
600
700
800
900
GPM GPM
LD01532 LD01535
TOWER WATER * TOWER WATER *
40 40
30 30
S
S
AS
AS
20
PRESSURE DROP–FT. WATER
20
PRESSURE DROP–FT. WATER
3P
3P
S
AS
S
AS
2P
2P
10 10
8 8
S
6
AS
S
6
AS
1P
5
1P
5
4 4
3 3
2 2
1000
150
200
300
400
500
600
800
1000
150
200
300
400
500
600
800
GPM GPM
LD01531 LD01534
* See Notes on page 56. HOT WATER HOT WATER
80 80
60 60
PRESSURE DROP–FT. WATER
SS
40
SS
SS
PA
SS
PA
30 30
PA
PA
4
4
SS
SS
3
3
20 20
PA
PA
2
2
SS
SS
10 10
PA
PA
1
1
7 7
5 5
3 3
2 2
1 1
1000
2000
3000
200
300
400
500
600
800
1000
2000
3000
200
300
400
500
600
800
GPM GPM
LD01536 LD01539
CHILLED WATER CHILLED WATER
65
70
SS
40 PA 50 SS
PRESSURE DROP–FT. WATER
/1 PA
1 1
1000
2000
2200
500
600
700
800
900
500
600
700
800
900
1000
2200
GPM GPM
LD01538
TOWER WATER * TOWER WATER * LD01541
40 50
40
30
30
S
AS
S
PRESSURE DROP–FT. WATER
AS
3P
20
3P
PRESSURE DROP–FT. WATER
20
S
S
AS
AS
2P
2P
10 10
S
8
AS
8
1P
S
AS
6 6
1P
5 5
4 4
3 3
2
2
1000
150
200
300
400
500
600
800
1000
150
200
300
400
500
600
800
GPM
GPM LD01537 HOT WATER
* See Notes on page 56. HOT WATER LD01540
80 80
60 60
PRESSURE DROP–FT. WATER
SS
SS
SS
SS
PA
PA
30 30
PA
PA
4
4
SS
SS
3
3
20 20
PA
PA
2
2
SS
SS
10 10
PA
PA
1
1
7 7
5 5
3 3
2 2
1 1
1000
2000
3000
4200
1000
2000
3000
4200
250
400
500
600
800
250
400
500
600
800
GPM GPM
LD01542 LD01545
CHILLED WATER CHILLED WATER
70 70
50 50
PRESSURE DROP–FT. WATER
PRESSURE DROP–FT. WATER
SS SS
PA PA
30 D 3/1 30 L3
ON TA
SS TO SS
20 S/C PA SS 20 PA SS
AB 2/1 PA L2 PA
ND 1/1 TA L1
O D TO TA
S/C ON TO
10 AB S/C 10
AB
7 7
5 5 ER
R NS
4 E 4 NDE
D
NS ON
3 E 3 CCO
ND
CO
2 2
1 1
1000
2000
3100
1000
2000
3100
800
900
800
900
GPM GPM
LD01557
LD01544
TOWER WATER * TOWER WATER *
50
40 40
30 30
S
S
AS
AS
3P
3P
20 20
S
S
AS
AS
2P
2P
10 10
8 8
S
S
AS
AS
6 6
1P
1P
5 5
4 4
3 3
2 2
1000
1200
200
300
400
500
600
700
800
1000
1200
200
300
400
500
600
700
800
GPM GPM
LD01543 LD01546
* See Notes on page 56. HOT WATER HOT WATER
80 80
PRESSURE DROP–FT. WATER 60 60
SS
40
SS
SS
PA
SS
PA
30 30
PA
PA
4
4
SS
SS
3
3
20 20
PA
PA
2
2
SS
SS
10 10
PA
PA
1
1
7 7
5 5
3 3
2 2
1 1
1000
2000
3000
4200
250
400
500
600
800
1000
2000
3000
4000
5500
300
400
500
600
800
GPM GPM
LD01547 LD01550
CHILLED WATER CHILLED WATER
70 70
50 SS 50
PA
PRESSURE DROP–FT. WATER
1 1
1000
2000
3100
800
900
1000
2000
3000
4000
4500
GPM GPM
LD01549 LD01552
TOWER WATER * TOWER WATER *
50 40
40
30
30
S
S
AS
PRESSURE DROP–FT. WATER
AS
3P
3P
20
PRESSURE DROP–FT. WATER
20
S
AS
S
2P
AS
2P
10
AS
1P
10 8
S
AS
8
6
1P
6 5
5 4
4
3
3
2
1000
1700
300
400
500
600
700
800
2
1000
1200
200
300
400
500
600
700
800
GPM
GPM
LD01548 HOT WATER LD01551
* See Notes on page 56. HOT WATER
10
20
30
40
50
10
20
30
40
50
2
3
4
5
6
8
2
3
4
5
6
8
10
20
30
40
60
80
1
2
3
5
7
300 300 300
3 3 400
PA PA
400 SS 400 SS 500 4
GPM
GPM
GPM
2000
HOT WATER
1000 1000 1
PA
CHILLED WATER
1P 1P SS
AS AS
S S 3000
MODEL YIA – 9E2
4000
1700 1700 5500
LD01554
LD01553
LD01555
10
20
30
40
50
2
3
4
5
6
8
10
20
30
50
70
1
2
3
4
5
7
10
20
30
40
60
80
1
2
3
5
7
3P
400 4
AS
500
S
2 PA
CO
N
PA SS
600
D
500 SS 3
PA
EN
800 SS
AB
SE
600
S/
1000
C
2
2000 PA
ON
700 SS
D 2
800
/1
AB
GPM
GPM
GPM
S
PA
/C
2000
SS
HOT WATER
1000
ON
PA
D
1 3000 SS
CHILLED WATER
1/
MODEL YIA – 10E3
PA
1
TOWER WATER *
SS 3000
PA
SS
4000 4000
1700 4500 5500
LD01595
LD01496
LD01494
YORK INTERNATIONAL
FORM 155.16-OM1
80 80
PRESSURE DROP–FT. WATER 60 60
SS
40
PA
PA
30 30
SS
SS
PA
PA
20 20
2
SS
SS
PA
PA
10 10
1
7 7
5 5
3 3
2 2
1 1
1000
2000
3000
4000
5000
7000
500
700
1000
2000
3000
4000
5000
7000
500
700
GPM GPM
LD01497 LD01500
CHILLED WATER CHILLED WATER
70
50
1
1500
2000
3000
4000
5000
6000
LD01499
GPM
LD01502
TOWER WATER *
50 50
40 40
S
S
AS
AS
30 30
3P
3P
PRESSURE DROP–FT. WATER
20 20
S
AS
2P
S
AS
2P
10 10
SS
PA
SS
8 8
1
PA
1
6 6
5 5
4 4
3 3
2 2
1000
2000
2500
1000
2000
2500
400
500
600
700
800
400
500
600
700
800
GPM LD01498
GPM LD01501
* See Notes on page 56. HOT WATER HOT WATER
80
60
PRESSURE DROP–FT. WATER
SS
40
PA
30
3
SS
PA
20
2
SS
PA
10
1
7
5
3
2
1
1000
2000
3000
4000
5000
7000
500
700
GPM
LD01503
CHILLED WATER
70
50
PRESSURE DROP–FT. WATER
SS
PA
30 2/1
D SS
ON PA
20 S/C 1/1
AB D
ON
S/C
10 AB
7
5 ER
4 ENS
ND
3 CO
2
1
1500
2000
3000
4000
5000
6000
GPM
LD01505
TOWER WATER *
60
50
40
SS
PA
30
3
PRESSURE DROP–FT. WATER
SS
20
PA
2
SS
10
PA
1
8
6
5 * Pressure drop curves include 1 psi pressure drop for
4 cross-over line.
3
* Pressure drop curve for the condenser water circuit only
2 is shown as a dotted line. For total tower water pressure
1000
2000
2500
400
500
600
700
800
YORK INTERNATIONAL 57
TROUBLESHOOTING TABLE
2. UNIT CYCLING OR A. Air in water piping causing varying Purge air from the water piping.
ERRATIC CHILLED water flow to the unit.
WATER B. Control valve not functioning Check actuator and linkage. Adjust if necessary.
TEMPERATURE properly (not closing). Check max. rate setting normal 1.0.
C. Low temperature thermostat Check cutout setting using 1/5°F thermometer
not cutting out at correct setting 39°F. (If not working properly, contact
temperature settings. local district office.)
D. Fluctuating steam pressure or Correct supply source.
hot water temperature.
E. Cooling water temp. cycling Readjust settings.
improper tower fan setting.
5. PURGE PUMP OIL A. Faulty shaft seal rubber. Repair with kit in “Renewal Parts” manual.
LEAKAGE
58 YORK INTERNATIONAL
YORK INTERNATIONAL
FORM 155.16-OM1
of pumps
59
60
NOTES:
1. Units that provide year-round cooling: Once every four months, and as required due to excess purge requirements.
Units that provide only seasonal cooling: Once at the beginning of the cooling season, once in the middle, and as needed due to excess purge requirements.
2. Units should be leak-tested when excessive purging is required. Note: The solution chemistry should always be checked (and adjusted as necessary) prior to performing a leak test.
3. More frequent rebuilds will be required if solids and/or dissolved copper is present in the solution.
4. Perform every 2-3 years or as required.
YORK INTERNATIONAL
GLOSSARY OF TERMS
Absorber: tallized heat exchanger from the opposite side of the
tubes and causes the crystallized lithium bromide to
The concentrated solution coming back from the gen-
dissolve back into solution.
erator is pumped to a solution spray header where it is
sprayed over the tubes in the absorber. Refrigerant
Blowdown:
vapor is absorbed into the solution and the solution is
thus diluted. This diluted solution is collected at the While running the unit, refrigerant is intentionally
bottom of the absorber where it is again pumped to dumped into the absorber shell section by opening
the generator. 2SOL (stabilizer solenoid valve). A refrigerant blow-
down will further dilute the solution in the absorber
ADC Flush Line: shell. A blowdown is required before taking a solu-
tion sample for analysis, to separate the alcohol from
This line runs between the solution pump discharge
the refrigerant, and to hasten the refrigerant clean-up
and the ADC line. When the solution pump runs,
procedure.
weak solution is constantly supplied to the ADC line.
This keeps the ADC line from crystallizing, due to it
being exposed to the low pressures generated within C.O.P.:
the absorber while the unit is running.
Coefficient of performance. A means of comparing
the performance of a chiller as the ratio of the cooling
ADVAGuardTM 750:
output divided by the heat input.
YORK's newest Inhibitor. An inorganic inhibitor pro-
viding excellent corrosion protection to the unit's Concentration:
internal steel and copper surfaces. Also see Inhibitor.
The percent by weight of lithium bromide present in
solution. New solution is sent with a concentration of
Alcohol (2-Ethylhexanol): 54% if the inhibitor is ADVAGuard 750, or 55% if the
inhibitor is molybdate.
A liquid added to an absorption chiller to enhance the
heat and mass transfer in the Absorber. It is an octyl
Condensate:
alcohol whose chemical name is 2-Ethyl-1-Hexanol
(C8H18O) with a molecular weight of 130.2, a boil- Condensed steam leaving the unit.
ing point of 364.3°F, and a flash point of 177.8°F @
760 mmHg. Having a colorless, clear appearance, it Condenser:
has a somewhat pungent odor. By adding 2-
Vapor produced by the generator enters the condenser
Ethylhexanol to the absorption cycle, overall unit per-
and is cooled and condensed back into a liquid by the
formance increases by 5-15%. In addition, cycle tem-
tower water flowing through the inside of the con-
peratures, pressures, and concentrations tend to
denser tubes. The condensed vapor liquid drips down
decrease with the addition of 2-Ethylhexanol.
into a collection pan located at the bottom of the con-
denser. From there it flows out of the pan, through an
Automatic De-crystallization Pipe (ADC):
orifice, and into the evaporator.
The automatic de-crystallization pipe is a U-shaped
line coming off the generator solution outlet box and
Condenser (Tower) Water:
terminating in the absorber shell. During normal unit
operation, this line has no flow in it. If crystallization The external water loop which is used to remove heat
were to occur, it would normally be in the strong solu- from the unit. This water passes first through the
tion side of the heat exchanger. This blockage would Absorber, then the Condenser. Typical temperatures
back up solution into the generator solution and into are entering the Absorber at 85°F, leaving the
the automatic de-crystallization pipe. Once the hot Absorber (entering the Condenser, i.e. crossover) at
solution goes into the ADC pipe, it bypasses the heat 92°F, and leaving the Condenser at 95°F. Some exter-
exchanger and goes directly into the absorber shell, nal means of removing this heat is necessary.
thus heating the solution in the absorber shell. The Typically a cooling tower is used for this application.
heated solution in the absorber then heats up the crys-
YORK INTERNATIONAL 61
Crystallization: ing the chilled water to be used to cool a building, a
manufacturing process, or whatever application it is
Under certain conditions, lithium bromide solution
intended. Typically, the chilled water is cooled from
may increase in viscosity and become slush-like, or
54°F to 44°F. In an absorption chiller, the pure refrig-
even solidify. The likelihood of solution crystallizing
erant generated in the generator is cooled and con-
increases as the concentration increases and/or the
densed in the Condenser and supplied to the
temperature decreases. For reference, here are some
Evaporator. Here, it is immediately exposed to a
points where the liquid solution of lithium bromide
much lower pressure which causes some immediate
will crystallize, assuming a saturation condition:
flashing (boiling). Most of the refrigerant cools to the
240°F @ 70%; 207°F @ 69%; 182°F @ 68%; 158°F
saturation temperature and remains in liquid form. It
@ 67%; 138°F @ 66%; and 120°F @ 65%. Typically,
is then pumped and sprayed over the Evaporator tube
crystallization occurs where the heated, high concen-
bundle. As the refrigerant passes over the outer sur-
trated solution leaves the generator and passes through
face of the tubes, it evaporates (i.e. flashes or boils)
the heat exchanger. This is where the solution is at its
because of the low pressure, approximately 5.5-6.5
highest concentration that meets the lowest tempera-
mmHg which is equivalent to a saturation temperature
ture. Under normal running conditions, crystallization
of 36-41°F. The refrigerant vapor is then immediate-
is not a problem. Extreme cold ambient temperatures,
ly drawn through the eliminator towards the Absorber.
power failures, and unit air leakage are the typical
This vacuum is caused by the hygroscopic action, the
causes for crystallization.
affinity Lithium Bromide has for the refrigerant vapor.
Dilution Cycle:
Evaporator Sprays:
Intentionally running the solution, refrigerant, tower
A series of spray nozzles that evenly distribute refrig-
water, and chilled water pumps after unit has been
erant from the refrigerant pump discharge to the evap-
shut down to allow the concentrated solution to
orator section tubes.
become more dilute. Essentially, the cycle continues
without the addition of heat, thus, slowly diluting the
solution to concentration levels where it is more diffi- Float (1F), (3F):
cult to crystallize. The dilution cycle will shut off after
There are two floats that sense liquid levels on the
the solution temperature reaches 136°F. Note: The
IsoFlow units. Both are located in the refrigerant cir-
dilution cycle is dependent upon many factors.
cuit. Float (1F) is at the side of the evaporator refrig-
Please see the micropanel instructions for details.
erant outlet box, and senses the level in the box. At
low levels in this box, the 1F float will open, causing
Eductor: the micropanel to initiate corrective procedures to
keep the unit from running out of refrigerant. For
An eductor is a liquid-powered jet pump. Jet pumps
more details, see YORK Form 155.16-O3.
have no moving parts and use a high-pressure stream
of liquid to pass through a nozzle, causing a portion of
Float (3F) is located just before the inlet of the Buffalo
of a low-pressure stream coming into the side of the
refrigerant pump. It's main purpose is to keep the
pump to combine with the nozzle stream. This causes
Buffalo pump from cavitation and eventual overheat-
a reduction in pressure at the low-pressure inlet and
ing. For more details on the operation of this float, see
induces the rest of the low-pressure inlet substance to
YORK Form 155.16-O3.
flow into the body of the pump.
Generator:
On IsoFlowTM units, an eductor is used in place of a
centrifugal pump to induce strong concentrated solu- This component of the absorption system heats dilut-
tion exiting the generator outlet box to combine with ed lithium bromide solution coming from the absorber
weak concentrated solution exiting the solution pump shell. The generator can receive its heat source from
discharge, before going to the absorber spray header. either hot water to 266°F (130°C) and 300 PSIG or
steam of up to 337°F (169°C) and 15 PSIG. As the
solution is heated, refrigerant vapor is boiled off and
Evaporator:
rises to the condenser. The resulting concentrated
The section of a chiller that is responsible for remov- lithium bromide solution flows back to the absorber
ing the heat from the chilled water circuit, thus cool- sprays.
62 YORK INTERNATIONAL
FORM 155.16-OM1
YORK INTERNATIONAL 63
Orifice: Purge Pump:
A restriction in a liquid line for the purpose of reduc- An external pump connected to the purge system of
ing the internal diameter of the line. Usually created the unit. This pump is used to evacuate non-con-
by a blank piece of metal with a small hole drilled into densables from the unit.
it, to create a pressure differential when a liquid pass-
es through it.
Purging:
Pass Baffle: A process by which non-condensables present in a
unit are removed through the use of a vacuum pump.
A division plate or plates (baffles) inserted into a
water box to create chambers which force the water to
Refrigerant:
pass through different portions of the tube bundle,
called passes. Although the pressure drop increases (Water, H2O). Deionized water is used as the refrigerant.
with increasing passes, the tradeoff for heat transfer
optimization and nozzle locations are justified. Refrigerant Anti-Freeze Line:
This line runs between the outlet of the refrigerant
Power Panel pump and the refrigerant condensate line(s) coming
The power panel serves as single-point wiring loca- down off the condenser. When the refrigerant pump is
tion for the unit’s incoming power wiring. It houses operating, a constant supply of refrigerant is supplied
all the unit pump contactors and overloads, as well as to mix with the refrigerant coming from the condens-
fuses and terminal lugs for ease of serviceability. A er to keep it from freezing during low loads and low
transformer is included to reduce the incoming unit condenser water temperatures.
voltage to the required control voltage to the
micropanel. Refrigerant Pump:
A hermetically sealed, centrifugal pump located
Pressure Drop: downstream of the evaporator outlet box. This pump
The amount of pressure decrease experienced receives liquid refrigerant from the evaporator and
between two locations. Often referred to when discharges it back up to the evaporator sprays. It con-
describing the drop in pressure found while passing tinues to re-circulate the refrigerant while the chiller
water through the tubes in a chiller. Typically meas- is operational.
ured in PSI or Ft H20
Rupture Disk (Hot Water Units Only):
Purge Drum:
Although IsoFlowTM absorption units operate at less
The purge chamber is also sometimes called the purge than atmospheric pressure (a vacuum), if certain
drum. It was designed to produce a low-pressure area safeties fail and/or incorrect valves are closed, the unit
so that non-condensables can be pulled out of the could experience higher pressures in certain cham-
absorption system and expelled to the atmosphere by bers. Therefore, a pressure relief apparatus, a rupture
the purge pump. disk, is added.
The purge drum functions similar to the way that the
absorber section of the system functions. Tower water Sight Glass:
circulates through a coil inside the purge drum while A leak tight port hole used to visually inspect liquid
solution is sprayed over the outside of the coil. This levels within the unit. A threaded design with a
process induces the non-condensables in the absorber quartz glass window is presently being used.
shell to enter a purge header assembly with the
shell and migrate to the purge drum. Once inside the Solution:
purge drum, the vacuum pump can pull the non-con-
A mixture of deionized water with a certain % by
densables out of the drum and expel them to the
weight of dissolved lithium bromide (LiBr).
atmosphere.
Corrosion inhibitors are also added to the solution to
reduce the internal corrosion rates in the unit.
64 YORK INTERNATIONAL
FORM 155.16-OM1
Atmosphere at 32˚F
TORR
(mmHg) Inches Hg (abs) PSIA ABSOLUTE UNITS GAUGE UNITS
760 29.92 14.696 Measured From Absolute Zero Measured From Atmospheric Pressure
700 14
25 PSIA PSIG
600 12
TORR in Hg
500 20 10 14.7 (mm Hg) (Abs.) mm Hg in Hg
ATMOSPHERIC 0
PRESSURE 760 29.92 0
400 8 (0 PSIG)
15 (14.7 PSIA)
– mm Hg
300 6 INCREASING
– in Hg
VACUUM – PSIG
10
200 4
DECREASING
VACUUM
5
100 2
0 0 0 14.7 760 29.92
Absolute Zero Pressure or Perfect Vacuum
0 0 0
LD05113 LD05114
YORK INTERNATIONAL 65
Vacuum: From Figure 25, we can see that a pressure reading of
300 Torr is the same as 11.8 in Hg (abs.) and 5.8 PSI
When the pressure within a vessel is less than stan-
(abs.).
dard atmospheric pressure.
66 YORK INTERNATIONAL
FORM 155.16-OM1 FORM 155.16-OM1
HP1
KEY PT1
CONDENSER
CONCENTRATED TOWER WATER
SOLUTION (LI.BR.)
DILUTE SOLUTION
OUTLET
(LI.BR.)
INTERMEDIATE
SOLUTION (LI. BR.)
CHILLED LIQUID
TOWER
STEAM OR HOT WATER
WATER CONTROL VALVE
REFRIGERANT LIQUID
LOW TEMPERATURE HOT WATER OR
REFRIGERANT LIQUID STEAM
HIGH TEMPERATURE
GENERATOR
GENERATOR
OUTLET
CHILLED
WATER
OUTLET
TO GENERATOR
CHILLED
WATER
INLET
EVAPORATOR
ABSOLUTE
PRESSURE GAUGE
AUTOMATIC DE-CRYSTALLIZATION PIPE
FROM GENERATOR
1F
TOWER
WATER
INLET OIL
TRAP
ABSORBER
2SOL 3F
PURGE
PUMP
REF.
LD06022A
PUMP
SOL 3
SOL
PUMP
Proud Sponsor
of the 2002
U.S. Olympic Team
36USC380
P.O. Box 1592, York, Pennsylvania USA 17405-1592 Tele: 800-861-1001 Subject to change without notice. Printed in USA
Copyright © by York International Corporation 2000 www.york.com ALL RIGHTS RESERVED
67B YORK INTERNATIONAL Form 155.16-OM1 (1200)
New Release