You are on page 1of 11

ADJUSTMENT AND REPAIR PROCEDURES

TO MINIMIZE CARBON MONOXIDE (CO)


LEVELS IN GAS OVENS
INTRODUCTION and on the surface above it. The baffle also reduces the
amount of air going to the bake burner, so that the com-
The maximum carbon monoxide (CO) levels allowed bustion process tends to increase the level of carbon
in gas ovens are as follows: dioxide (CO2). This increase typically results in higher
• Non-self-cleaning ovens = 200 PPM, stabilized amounts of air-free carbon monoxide, and is the reason
after 5-minutes of operation. for the higher allowable level of CO for self-cleaning
• Self-cleaning ovens = 300 PPM, stabilized af- ovens.
ter 5-minutes of operation. The standard location used for measuring the maximum
The reason for the differences in the maximum allow- allowable CO levels is at the oven’s exhaust vent, rather
able CO levels is due to the differences in construction than from inside the room. This is because of the dif-
between the non-self-cleaning (see Figure 1), and the ferences in room sizes, the airtightness of the living area,
self-cleaning ovens (see Figure 2). Self-cleaning ovens and the number of air exchanges. The readings are also
have an additional baffle that is located below the bake intended to minimize the amount of time that the tech-
burner. This baffle is included to help vent hot air from nician will have to spend at the location, and still be
inside the oven during the self-clean cycle, and reduce able to determine the acceptability of the oven’s com-
the temperature buildup from inside the storage drawer, bustion process.

OVEN BOTTOM
OVEN BOTTOM

HEAT BAFFLE
UPPER HEAT SHIELD

UPPER HEAT SHIELD

FIGURE 1 FIGURE 2
Non-Self-Cleaning Oven Self-Cleaning Oven

Page 1
SURFACE BURNERS Air Shutter Adjustment
Most concerns about the maximum allowable CO lev- If the cooktop flame is not properly set, perform the
els have been with the oven, and not with the surface following steps, and adjust the air shutter:
burners. Taking field CO measurements on surface burn- 1. Locate the air shutter for the burner (see Figure 4).
ers that relate directly to the AGA (American Gas As-
sociation) requirements and methods, (i.e. chrome- 2. Loosen the air shutter locking screw and turn the
plated “pots” and a hood to place over the collective shutter over the orifice hood in either direction un-
burners), is currently impractical. Surface cooktop burn- til the proper flame appears.
ers and all standing pilots should, however, be checked 3. Retighten the air shutter locking screw.
by the technician before making any CO measurements. NOTE: To replace a burner or an orifice hood, see “Re-
Procedures for making these checks, and any adjust- placing A Cooktop Burner & Orifice Hood” on page 3.
ments, are described in the following sections. These
are typical procedures, and some may not apply to your
particular oven.
Check each cooktop burner for the proper flame. Typi- BURNER
cally, the flame should be 5/8" long with an inner cone
PILOT
that is bluish-green in color, and a dark-blue mantle (see
Figure 3). There should be no yellow tips, blowing, or
lifting of the flame.
5
/ 8"

VENTURI ORIFICE HOOD


COOKTOP BURNER
AIR SHUTTER

FIGURE 4
FIGURE 3 The Burner Air Shutter
Cooktop Burner Flame

Page 2
Low-Flame Adjustment Replacing A Cooktop Burner
Some burners have a low flame (simmer) adjustment & Orifice Hood
that is located inside the gas valve stem. If the low set- A burner venturi or orifice can become damaged,
ting is unsteady, or goes out, use the following proce- (plugged or deformed), and cause improper combus-
dure to adjust it. tion, or proper adjustment of the burner flame. As a
1. Turn the burner knob to the “low” setting. result, carbon monoxide levels may substantially in-
crease. If this occurs, replace the burner or orifice.
2. Remove the knob from the burner valve shaft.
To replace a venturi or an orifice hood, (see Figure 6),
3. Use a small-bladed screwdriver, and insert it into
use the following procedure:
the opening of the burner valve (see Figure 5).
1. Remove any mounting screws holding the burner
4. Turn the burner valve adjustment screw until there
to the cooktop.
is a steady blue flame.
2. Lift the burner from the cooktop and slide the end
5. Replace the knob.
of the venturi off the orifice hood.
6. Turn the burner knob to its “hi” setting and check
3. Use a 1/2" socket, remove the defective orifice hood
for the proper flame. If the proper flame is not
from the front panel, and replace it with a new ori-
present, adjust the air shutter, using the procedure
fice hood.
outlined in the “Air Shutter Adjustment” section,
or replace the burner. 4. Slide the end of the venturi over the orifice hood
and secure the burner to the cooktop.
ADJUSTMENT
SCREW INSIDE 5. If necessary, adjust the air shutter for the proper
BURNER VALVE pilot flame (see “Standing Pilot (Cooktop),” page
STEM
4).

BURNER

PILOT
FIGURE 5
Burner Flame Adjustment

VENTURI ORIFICE HOOD

AIR SHUTTER

FIGURE 6
Burner & Orifice Hood Replacement

Page 3
COOKTOP GAS
STANDING PILOT (COOKTOP ) VALVE KNOB

Flame Adjustment
Check each standing pilot for the proper flame. Typi- PILOT
cally, the flame should be 1/4" to 3/8" long. The inner BURNER BURNER
cone should be bluish-green in color, with a dark-blue
mantle (see Figure 7). There should be no yellow tips,
blowing, or lifting of the flame.

FIGURE 8A
MANTLE
Lighting The Pilot

INNER CONE

ADJUSTMENT
FIGURE 7 SCREW
The Standing Pilot Flame PILOT GAS
LINE
The adjustment control for a cooktop burner pilot flame
is located on the manifold pipe. To light and adjust the
standing pilot ranges, perform the following steps.
1. Make sure that the cooktop gas valve control knobs
are turned off (see Figure 8A).
2. Raise the cooktop.
3. Place a lighted match near the opening of the pilot
between the two burners, and the pilot should light FIGURE 8B
(see Figure 8A). Pilot Adjustment
4. Adjust the pilot adjustment screw (see Figure 8B)
so that the flame is between 1/4" to 3/8" high and
centered in the hole in the pilot housing.
5. Lower the cooktop.

Page 4
GUIDELINES FOR MEASURING
CARBON MONOXIDE (CO)
TEST EQUIPMENT 2. In the home:
When making CO measurements, use a meter* that has a) Read and record the room CO level.
the following features: • Record whether any gas appliances were op-
a) Portable and battery-operated. erating, either during this initial measuring
b) Zeroing control. time, or just prior to it.
c) Digital display. • Note whether any of the occupants smoke, and
d) Minimum tolerance of ± 10 PPM +5%. if so, how often.
e) Pump that can obtain air samples. b) Turn down the furnace or air conditioner.
f) 40-second minimum response time.
c) Turn off any gas cooking products.
* Recommended: Bacharach Monoxor II or Kane-May KM SGA 90 Series
d) Turn the gas water heater to the “pilot” setting.
SETUP PROCEDURE e) Cease all tobacco smoking.
1. Set the test meter: f) If possible, evacuate the air in the room.

a) The operating temperature of meter should be g) Read and record the room level once again.
from 23˚F to 104˚F. 3. Inspect all of the appliances:
b) Turn the meter on and allow it to warm up for a) Check the operation of any standing pilots on
approximately 1-minute. the appliances and adjust them, if necessary (see
c) If necessary, zero the meter. page 4).
NOTE: When you zero the meter, you have to b) Verify whether the appliance was either in use
be outside the house. Also, keep the meter away when the CO alarm sounded, or whether it had
from operating vehicles, and there should be been in use just prior to the alarm sounding.
NO smoking.
• Record the time lapse from the end of the
product’s use to when the alarm sounded.
• Identify the modes of operation that were in
use, and use the appropriate test procedure on
the following page to test the operation.
4. Fill out the “Whirlpool Repair Services Carbon
Monoxide Investigation Form.” A sample of this
form is shown on pages 9 and 10.

Page 5
BAKE OPERATION TEST 3. When the time has elapsed:
a) Place the probe tip of the meter inside the oven’s
1. Set the temperature to 500˚F and start the bake op-
vent.
eration (this temperature will prevent the oven
burner from cycling on and off during testing). Al- b) Allow the reading to stabilize.
low the oven to operate for 5-minutes. c) Record the reading.
2. When the time has elapsed: 4. Remove the probe tip from the vent, and:
a) Place the probe tip of the meter inside the oven’s a) Allow the reading to stabilize at room level.
vent. b) Record the reading.
b) Allow the reading to stabilize. If the CO readings are higher than the levels established
c) Record the reading. by the manufacturer, refer to “Corrective Action” on
3. Remove the probe tip from the vent, and: the next page.
a) Allow the reading to stabilize at room level. SELF-CLEAN OPERATION TEST
b) Record the reading.
1. Start the self-clean operation and allow the oven to
If the CO readings are higher than the levels established cycle for 1-hour.
by the manufacturer, refer to “Corrective Action” on
the next page. 2. When the time has elapsed:
a) Place the probe tip of the meter inside the oven’s
BROILER OPERATION TEST vent.
1. If the bake operation was previously used, open the b) Allow the self-clean operation to cycle two or
oven door, and allow the oven to cool for a mini- three additional times.
mum of 10-minutes. c) Record the reading.
2. Set the temperature to 500˚F and start the broil op- 3. Remove the probe tip from the vent, and:
eration (this temperature will prevent the oven a) Allow the reading to stabilize at room level.
burner from cycling on and off during testing). Al- b) Record the reading.
low the oven to operate for 5-minutes.
If the CO readings are higher than the levels established
by the manufacturer, refer to “Corrective Action” on
the next page.

Page 6
CORRECTIVE ACTION

PROBLEM SOLUTION

Incoming air is blocked. Remove the source of the blockage (i.e. shag carpet-
ing is covering the bottom vent intake openings).

The vent (flue) is plugged. Remove the source of the blockage.

Adjust the air shutter to obtain the proper flame set-


The air shutter is set incorrectly.
ting (see page 2 ).

The burner orifice venturi is misaligned (see page 3). Adjust the venturi.

The oven is dirty (grease and other food products are Clean the oven.
burning).

The gas line pressure is incorrect (too high or too low). Use a manometer and check the gas line pressure.
Verify the gas regulator operation at the proper pres-
sure setting.

NOTE: The following two corrective actions may require the removal of the burner.

The wrong burner orifice is being used. Adjust or install the correct orifice (see page 3).

The burner orifice is burred causing the incoming gas Replace the orifice (see page 3).
to scatter in the venturi.

NOTE: The following two corrective actions may require the removal of the oven bottom and the flame spreader.

The burner flame is restricted (misaligned ignitor, Realign/replace the ignitor or the flame spreader.
warped flame spreader, blocked ports, etc.).

The burner ports are blocked. Clean the ports or replace the burner.

NOTES:
1. After you perform a corrective action, repeat the CO measurement to make sure that the problem was corrected.
2. If the corrective action does not fix the CO level problem, the product should be traded out.

Page 7
WHIRLPOOL REPAIR SERVICES
CARBON MONOXIDE INVESTIGATION FORM

SECTION 1 — INFORMATION

Customer Name Date Time


Address Service Order No.
City State Zip Code Technician Name
Phone ( )

SECTION 2 — TEST EQUIPMENT

Brand: Type: Model No.: Serial No.:


Battery Test: OK Warmup Time: (Minutes) Calibrate: Y N Outdoor Temperature: ˚F
Page 9

SECTION 3 — CUSTOMER INTERVIEW

Reason For Call:

Was Gas Company Called?: Y N Respond? Y N If Yes - Report No.


Date: Time: Utility Name:
Their Recommendations:

SECTION 4 — SITE SURVEY/CO DETECTORS Ambient Indoor CO Level: (PPM)


Indoor Temperature ˚F
DETECTOR(S):
NUMBER BRAND LOCATION OPERATIONAL DETECTOR SENSOR COMMENT
1.
2.
3.
(over)
SECTION 5 — POTENTIAL CO SOURCES

SOURCE LOCATION BRAND FUEL CONDITION OPERATION FLUE CO (PPM)


Cooktop
Range, Gas
Oven, Gas
Dryer, Clothes

How many fans are installed? Location(s)


Attached Garage? Y N If yes, are the vehicles ever started for warmup purposes? Y N
Additional Comments:
Page 10

SECTION 6 — EXTENDED MONITORING

Datalogger Brand: Model No:


Start Date: Start Time: Stop Date: Stop Time: TWA: Peak:

SECTION 7 — CONCLUSIONS

SECTION 8 — ACTION TAKEN


TEST PROCEDURES FOR MEASURING
CARBON MONOXIDE (CO) LEVELS IN GAS OVENS
BAKE OPERATION TEST
SETUP PROCEDURE
1. Set the temperature to 500˚F and start the bake operation (this
1. Set the test meter:
temperature will prevent the oven burner from cycling on and off
a) The operating temperature of meter should be from 23˚F to during testing). Allow the oven to operate for 5-minutes.
104˚F.
2. When the time has elapsed:
b) Turn the meter on and allow it to warm up for approximately 1-
a) Place the probe tip of the meter inside the oven’s vent.
minute.
b) Allow the reading to stabilize.
c) If necessary, zero the meter.
c) Record the reading.
NOTE: When you zero the meter, you have to be outside the
house. Also, keep the meter away from operating vehicles, and 3. Remove the probe tip from the vent, and:
there should be NO smoking. a) Allow the reading to stabilize at room level.
2. In the home: b) Record the reading.
a) Read and record the room CO level. If the CO readings are higher than the levels established by the
• Record whether any gas appliances were operating, either manufacturer, refer to “Corrective Action” on the other side of the
during this initial measuring time, or just prior to it. sheet.
• Note whether any of the occupants smoke, and if so, how BROILER OPERATION TEST
often.
1. If the bake operation was previously used, open the oven door, and
b) Turn down the furnace or air conditioner.
allow the oven to cool for a minimum of 10-minutes.
c) Turn off any gas cooking products.
2. Set the temperature to 500˚F and start the broil operation (this
d) Turn the gas water heater to the “pilot” setting.
temperature will prevent the oven burner from cycling on and off
e) Cease all tobacco smoking. during testing). Allow the oven to operate for 5-minutes.
f) If possible, evacuate the air in the room.
3. When the time has elapsed:
g) Read and record the room level once again.
a) Place the probe tip of the meter inside the oven’s vent.
3. Inspect all of the appliances: b) Allow the reading to stabilize.
a) Check the operation of any standing pilots on the appliances c) Record the reading.
and adjust them, if necessary. 4. Remove the probe tip from the vent, and:
b) Verify whether the appliance was either in use when the CO a) Allow the reading to stabilize at room level.
alarm sounded, or whether it had been in use just prior to the b) Record the reading.
alarm sounding.
If the CO readings are higher than the levels established by the
• Record the time lapse from the end of the product’s use to
manufacturer, refer to “Corrective Action” on the other side of the
when the alarm sounded.
sheet.
• Identify the modes of operation that were in use, and use the
appropriate test procedure to test the operation. SELF-CLEAN OPERATION TEST
4. Fill out the “Whirlpool Repair Services Carbon Monoxide 1. Start the self-clean operation and allow the oven to cycle for 1-
Investigation Form.” hour.
2. When the time has elapsed:
a) Place the probe tip of the meter inside the oven’s vent.
b) Allow the self-clean operation to cycle two or three additional
times.
c) Record the reading.
3. Remove the probe tip from the vent, and:
a) Allow the reading to stabilize at room level.
b) Record the reading.
If the CO readings are higher than the levels established by the
manufacturer, refer to “Corrective Action” on the other side of the
sheet.
CORRECTIVE ACTION

PROBLEM SOLUTION

Incoming air is blocked. Remove the source of the blockage (i.e. shag carpeting is
covering the bottom vent intake openings).
The vent (flue) is plugged. Remove the source of the blockage.

The air shutter is set incorrectly. Adjust the air shutter to obtain the proper flame setting.
The burner orifice venturi is misaligned. Adjust the venturi.

The oven is dirty (grease and other food products are burning). Clean the oven.
The gas line pressure is incorrect (too high or too low). Use a manometer and check the gas line pressure. Verify the
gas regulator operation at the proper pressure setting.

NOTE: The following two corrective actions may require the removal of the burner.

The wrong burner orifice is being used. Adjust or install the correct orifice.

The burner orifice is burred causing the incoming gas to scatter Replace the orifice.
in the venturi.

NOTE: The following two corrective actions may require the removal of the oven bottom and the flame spreader.

The burner flame is restricted (misaligned ignitor, warped Realign/replace the ignitor or the flame spreader.
flame spreader, blocked ports, etc.).

The burner ports are blocked. Clean the ports or replace the burner.

NOTES:
1. After you perform a corrective action, repeat the CO measurement to make sure that the problem was corrected.
2. If the corrective action does not fix the CO level problem, the product should be traded out.

You might also like