You are on page 1of 1

The following article was published in ASHRAE Journal, May, 2002.

© Copyright 2002 American Society of Heating, Refrigerating and Air-


Conditioning Engineers, Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in
paper form without permission of ASHRAE.

Duct Design Issues

Kitchen Hood Exhaust Fan

4,200 cfm
3,000 cfm 3,000 cfm
Adjustable Discharge
Kitchen Damper — Open Kitchen
Damper
0 cfm 6,000 cfm Return Air Fan
6,000 cfm
Return Air Figure 1: Preheat
Damper — Open 1,200
Minimum Discharge
Dining Room cfm
coil in normal lo-
Air Damper Adjustable OA Damper cation (kitchen
3,000 cfm 8,000 cfm operating).*
AHU 800
5,000 cfm 8,000 cfm
cfm
Preheat Coil
Minimum AHU Contains Freezestat, Fan, Face and
OA Damper Bypass Dampers, Heating and Cooling Coils

Innovative Preheating of Outside Air


By William F. Albern, P.E., Fellow/Life Member ASHRAE

ecently, I reviewed the HVAC system for the dining coil in an outdoor air intake. Cold air, –10°F (–23°C) in Ithaca,

R room at the McGraw House. This seven-story senior


citizen housing building in Ithaca, N.Y. was constructed
in 1972. The owner was dissatisfied with the ventila-
tion of the facility’s kitchen. The 1972 drawings indicated
that return air was taken from the dining room and part of it
is introduced to the coil in the middle of winter and heated to
about 50°F (10°C) before entering the air handling system for
final conditioning to meet the needs of the space.
Figure 2 is a schematic sketch of the “preheat coil” located
in the return air duct from the space as engineered by Galson &
was introduced into the kitchen to supply makeup air to the Galson for McGraw House. In this scheme, the 70°F (21°C) air
kitchen range exhaust hood. Additional air was directly in- is heated to about 120°F (49°C)and this hot air then heats the
troduced to the kitchen through the doors between the cold outside air to the mixed temperature of 50°F (10°C). The
kitchen and the dining room. end result is the same as Figure 1. However, the “preheat coil”
This was a typical method of providing makeup air to a hood does not encounter –10°F (–23°C) cold air and therefore, should
in a restaurant, institutional dining room, and similar facilities. not be subject to freezing.
While several pages of discussion could be devoted to the Unfortunately, if the “preheat coil” is located very close to
modifications to the kitchen hood exhaust/makeup air system the connection with the outside air duct, there still could be a
over the years, this column discusses what I consider an inno- frozen coil. And, that is just what happened! However, that
vative approach to preheating outside air. The system was de- does not detract from this different approach to preheating
signed by Galson & Galson Consulting Engineers, Syracuse, outside air. Simply remember to keep the coil a foot (0.3 m) or
N.Y. The architect was Egner Associates, Ithaca, N.Y. more upstream from the connection to the outside air duct and
Figure 1 is a schematic with the normal location of a preheat install a freezestat downstream from the coil.

Kitchen Hood Exhaust Fan

4,200 cfm
3,000 cfm

Adjustable Discharge 3,000 cfm Kitchen


Kitchen Damper — Open Figure 2: Preheat
Damper
6,000 cfm Return Air Fan 6,000 cfm coil in return air
0 cfm
Return Air duct (kitchen op-
Minimum Discharge 72°F Damper — Open 1,200 cfm erating).*
Air Damper Dining Room
122°F
Adjustable 3,000 cfm 8,000 cfm * cfm × 0.4719 =
OA Damper 5,000 cfm 8,000 cfm
AHU 800 L/s; (°F – 32) ÷ 1.8
cfm = °C
Minimum OA AHU Contains Freezestat, Fan, Face and
Damper Bypass Dampers, Heating and Cooling Coils

48 M ay 2 0 0 2 | A S H R A E J o u r n a l
ThisfileislicensedtoMirzaSajjal(ms2995@gmail.com).ThisdownloadwasmadeavailablewithsupportfromASHRAE.CopyrightASHRAE2020.

You might also like