*Type of building: Large commercial buildings (150,000 ft2 and above) in Singapore Ashrae 90.1-2007 Baseline building Type Condition Min eff Units Remarks Chillers Full load @ ARI std condn 6.1 COP Refer to table 6.8.1J for non std conditions
0.58
Kwi / TON
Part load
6.4
COP
IPLV @ ARI std condn Refer to table 6.8.1J for non std conditions
0.55
Kwi / TON
CHWP
Full load
22
W / GPM
CHW 44/56F
0.044
KWi / TON
Part load
CNWP
Full load
19
W / GPM
Decoupled system where sec pumps must modulate to min 50% of design flow @ no more than 30% of design KWi CNW: 85/95F & chiller COP: 6.1
0.053
Kwi / TON
Part load
CT
Full load
38.2
GPM / HP
0.06
Kwi / TON
Part load
0.58
Kwi / TON
Part load
CHWP
Full load
30
KWc / Kwi
0.117
Kwi / TON
Part load
CNWP
Full load
40
KWct / Kwi
0.088
Kwi / TON
Part load
CT
Full load
3.23
L/S / Kwi
0.06
Kwi / TON
Part load
0.11 0.128258542
0.90 AHU>= 20,000cfm & constant volume Full load 1.1 0.82 AHU / FCU < 20,000cfm & variable volume Full load 1.7
KWi / 1000cfm W/ CMH KWi / 1000cfm No requirement for part load performance
KWi / 1000cfm VSD fan with static pressure reset control HP/1000cfm KWi / 1000cfm VSD fan with static pressure reset control
Full load
1.5 1.12
Part load