Professional Documents
Culture Documents
ASCE 7-02 Solved Problem #1: Analytical Method 2 (for buildings < 60 feet high).
L. Prieto-Portar - 2008
This lecture applies the ASCE 7-02 code requirements for wind (Section 6.0) to a simple structure and analyzes it with, The ASCE 7-02 Method 2, the Analytical Method for buildings smaller than 60 feet in height. The structure chosen is a warehouse-office building in downtown Tampa. Its dimensions are 100 feet long by 50 feet wide by 20 feet tall. A drawing is shown on slide #3 depicting the location of all the windows and doors. The location of these windows and doors are either in the field (or internal) zones or in the end (or external) zones. The analysis consists of finding all pressures affecting every part of this structure that come from all four directions. Finally, when all the pressures have been calculated, the engineer will choose the largest positive pressure and the largest negative pressure for the design of the building.
The example: a single-story warehouse building, 100 feet long, 50 feet and 20 feet tall.
The location of the windows and doors are critical: are they in the field or in the end zones; are they debris resistant or not, in which case, this face of the building is breached during a hurricane.
The basic formula used to compute the wind design pressure p that is applied to a structure or a portion of a structure is,
p = 0.00256 K z K zt K dV 2 I GC p GC pi
)(
) (
A constant / Table 6-3 pg 75 / Figure 6-4 pg 47+48 / Table 6-4 pg 76 / Table 6-1 pg 73 The wind velocity comes from County maps in lieu of Fig 6-1b pg 73 A constant = 0.85 or Equation 6-4 pg 30 / Fig 6-6 to 6-8 pg 50-53 / Fig 6-5 pg 49
where
p = qz GC p GC pi
) (
This formula is performed upon 10 different zones of the structure in 4 different wind directions for both the transverse and the buildings longitudinal directions. The analysis is also performed for both the MWFRS and C&C. Therefore, there are a total of 160 calculated pressures. From these, the engineer will choose the largest positive and negative pressures for the final design.
p = 0.00256 K z K zt K dV 2 I
) ( factor )
The wind exposure category coefficient Kz shall be taken from ASCE 7-02, Section 6, page 75, Table 6-3. The Exposure Category is discussed in ASCE 6.5.6, pages 28 and 29. 6.5.6 Exposure. For each wind direction considered, an exposure category that adequately reflects the characteristics of ground roughness and surface irregularities shall be determined for the site at which the building or structure is to be constructed. Account shall be taken of variations in ground surface roughness that arises from natural topography and vegetation as well as constructed features.
6.5.6.1 Wind Directions and Sectors. For each selected wind direction at which the wind loads are to be evaluated, the exposure of the building or structure shall be determined for the two upwind sectors extending 45 degrees either side of the selected wind direction. The exposures in these two sectors shall be determined in accordance with Sections 6.5.6.2 and 6.5.6.3 and the exposure resulting in the highest wind loads shall be used to represent the winds from that direction. 6.5.6.2 Surface Roughness Categories. A ground surface roughness within each 45-degree sector shall be determined for a distance upwind of the site as defined in Section 6.5.6.3 from the categories defined below, for the purpose of assigning an exposure category as defined in Section 6.5.6.3. This Example Surface Roughness B: Urban and suburban areas, wooded areas or other terrain with numerous closely spaced obstructions having the size of single-family dwellings or larger. Surface Roughness C: Open terrain with scattered obstructions having heights generally less than 30 ft (9.1 m). This category includes flat open country, grasslands, and all water surfaces in hurricane-prone regions. Surface Roughness D: Flat, unobstructed areas and water surfaces outside hurricane-prone regions. This category includes smooth mud flats, salt flats, and unbroken ice.
This Example
Kh = Kz = 0.70
The Wind Directionality Factor is obtained from ASCE Table 6-4, page 76:
Within the State of Florida the wind speeds are obtained from the local county where the project is located through the countys wind maps, through, www.dca.state.fl.us/fbc/maps/2_maps.htm Some counties allow interpolation between wind speed lines, whilst others do not. To obtain a wind map of this specific example in downtown Tampa (Hillsborough County), use this address, www.dca.state.fl.us/fbc/index_page/maps/county_maps/hillsborough2.pdf
Hillsborough County does allow interpolation, although it is not practical. This Example #1s site. Use V = 120 mph.
where I is the Importance Factor, and is based on the use of the structure as well as the Nature of Occupancy (ASCE 7-02, Section 6.5.5, page 28).
V = 120 mph
Category II
Thus, the raw wind pressure (also known as qz, the velocity pressure) is,
This raw wind pressure now needs to be modified by the internal and external pressure coefficients (the factor) in order to determine what is the actual pressure that is going to be applied at different points of the structure.
WIND
An unbreached house is subjected to positive and negative pressures from the external wind.
WIND
When the house is breached (a broken window, or a door that loses its latch, etc) the wind entering the house will quickly increase the loads on the remaining windows, doors and roof until they too, fail.
WIND
The pressure coefficients will add pressure on some walls and roof (see the wind effect upon the right side wall and roof) and subtract on others. The analysis searches for the largest positive and negative pressures on the structure.
Now the raw pressure (also known as qz, the velocity pressure) must be modified by the pressure coefficients,
p = qZ GC p GC pi
) ( ) p = ( 21.9 psf ) ( GC ) ( GC )
pi
where GCpi is the Internal Pressure Coefficient and is based on the Building Enclosure Classification (ASCE 07-2, Section 6.5.11.1, page 31). What is the wind pressure doing internally? How does the wind affect an Enclosed Building, which is the case for this example? Even enclosed buildings have cracks around the doors and the windows, so that the building breaths and feels a portion of the raw pressure.
A Building Enclosure is defined in ASCE 7-02, Section 6.2, page 23, Building, open: A building having each wall at least 80% open. This condition is expressed for each wall by the equation Ao 0.8 Ag where: Ao = total area of openings in a wall that receives positive external pressure, in ft2 (m2) Ag = the gross area of that wall in which Ao is identified in ft2 (m2). Building, partially enclosed: A building which complies with both of the following conditions: 1. The total area of openings in a wall that receives positive external pressure exceeds the sum of the areas of openings in the balance of the building envelope (walls and roof) by more than 10%, and 2. The total area of openings in a wall that receives positive external pressure exceeds 4 ft2 (0.37 m2), or 1% of the area of that wall, whichever is smaller, and the percentage of openings in the balance of the building envelope does not exceed 20%.
These conditions are expressed by the following equations: 1. Ao > 1.10 Aoi 2. Ao > 4 ft2 (0.37 m2) or > 0.01Ag, whichever is smaller, and Aoi /Agi 0.20 where: Ao, Ag are as defined for Open Building Aoi = the sum of the areas of openings in the building envelope (walls and roof) not including Ao, in ft2 (m2) Agi = the sum of the gross surface areas of the building envelope (walls and roof) not including Ag, in ft2 (m2).
Building, enclosed: A building that does not comply with the requirements for open or partially enclosed buildings. This Example.
The distance a of the end zones corresponds to the Components and Cladding case:
a = 0.10L = 0.10B = 0.40h a = 0.04L = 0.04B = 3 feet but not less than these
An expanded view of the ten (10) zones of a building under a Transverse A loading:
The calculations of GCpf for the MWFRS case involve these ten (10) zones; notice the values given in the Table for our Example #1s flat roof ( = 0): This Example: a flat roof.
This line of coefficients are now used to calculate the pressures shown on the spreadsheet shown on the next slide.
The design pressures for the MWFRS at all ten zones for a Transverse A are:
Building zone
Velocity pressure qz
GCpf
1 2 3 4 5 6 1E 2E 3E 4E
21.9 psf 21.9 psf 21.9 psf 21.9 psf 21.9 psf 21.9 psf 21.9 psf 21.9 psf 21.9 psf 21.9 psf
0.40 -0.69 -0.37 -0.29 -0.45 -0.45 0.61 -1.07 -0.53 -0.43
4.82 -19.10 -12.00 -10.30 -13.80 -13.80 9.40 -27.40 -15.50 -13.40
12.70 -11.20 -4.20 -2.40 -5.90 -5.90 17.30 -19.50 -7.70 -5.50
Consider the first line of calculations for the buildings zone #1,
p = (21.9 psf ) ( GC pf ) ( 0.18 ) = (21.9 psf ) ( 0.40 ) ( 0.18 ) Using the positive value of GC pi yields, p = (21.9 psf ) ( 0.40 ) ( 0.18 ) = 4.82 psf Using the negative value of GC pi yields, p = (21.9 psf ) ( 0.40 ) ( 0.18 ) = 12.70 psf
Thus, for zone #1, the pressures range from +4.82 psf to +12.70 psf; therefore, we would choose +12.70 psf for our design pressure. This procedure now continues for all ten zones in four (4) directions for the transverse wind loading and the four (4) directions for the longitudinal wind loading, or a total 80 calculated pressures for the MWFRS case. Choose the largest positive and the largest negative pressures.
The ten zones for the Transverse A can now be shown with their calculated design pressures: -13.80 psf -10.30 psf
-12.00 psf
-15.50 psf
-19.10 psf -13.40 psf -13.80 psf +17.30 psf Wind direction +12.70 psf -27.40 psf
Consider now, what would happen to the design pressures if the roof had a small pitch of = 20 (which corresponds roughly to a pitch of 5:12), This new variant of Example #1 with = 20,
Notice the slight increase in pressure due to the increase in the roofs pitch, although zone #2E has not changed,
Building zone
Velocity Pressure qz
GCpf
Design pressures
positive negative
1 2 3 4 5 6 1E 2E 3E 4E
21.9 psf 21.9 psf 21.9 psf 21.9 psf 21.9 psf 21.9 psf 21.9 psf 21.9 psf 21.9 psf 21.9 psf
0.53 -0.69 -0.48 -0.43 -0.45 -0.45 0.80 -1.07 -0.69 -0.64
7.70 -19.10 -14.50 -13.40 -13.80 -13.80 13.60 -27.40 -19.10 -18.00
15.50 -11.20 -6.60 -5.50 -5.90 -5.90 21.50 -19.50 -11.20 -10.10
The main wind force resisting system (MWFRS) design pressures just found are used as the lateral forces upon the structural skeleton frame of the building, such as the steel frame, the reinforced concrete columns, beams and slabs, shear walls, etc. The design pressures from the MWFRS portion are applied to the columns and beams through the use of the tributary areas. For example, if the columns are spaced at 30foot intervals, and the floor-to-floor height is 10-feet, the tributary area is 10 x 30 = 300 SF multiplied by the largest positive or negative design pressures found in the two previous tables. Now we will calculate the design pressures for the Components and Claddings (C&C). The components and cladding are, for example, the roof coverings, wall coverings, awnings, canopies, etc, anything that is not affected by the internal pressure GCpi = 0. These C&C external pressures are applied to single components, a stand-alone (one canopy, one door, etc) and are a function of the surface effective area of that component. The smaller the effective area, the more intense the pressure, versus, the larger the effective area, the pressure becomes smaller, etc. In the ASCE Method 1: The Simplified Method these two separate procedures (MWFRS and C&C) are united into a single procedure.
Consider now the External Pressure Coefficients for the walls in the C&C case (ASCE 7-02, Figures 6-1a and 6-1b, pages 57 and 58): Wall coefficients
Consider the External Pressure Coefficients for a wall component that has an area of only 10 square feet:
The design pressures for a C&C of only 10 SF of wall effective area are,
Building zone 4(+) 4(-) 5(+) 5(-) Velocity Pressure GCpf Design pressures
qz
21.9 psf 21.9 psf 21.9 psf 21.9 psf -1.10 1.00 -1.40 1.00
Now what happens when the components area is increased to 100 square feet? component
Velocity Pressure qz 21.9 psf 21.9 psf 21.9 psf 21.9 psf
GCpf
Design pressures Using +GCpi -0.95 0.80 -1.05 -0.80 -22.30 12.20 -24.20 12.20 Using -GCpi -15.20 19.30 -17.10 19.30
Similarly, for a roof effective area of only 10 square feet, the coefficients are,
Contrast the high pressures on a roof component 10 SF with the same component that is 100 SF,
Notice the drop in design pressures for this case of a 100 SF roof component,
Velocity Pressure qz 21.9 psf 21.9 psf 21.9 psf 21.9 psf 21.9 psf 21.9 psf
GCpf
Design pressures Using +GCpi 0.20 -0.90 0.20 -1.10 0.20 -1.10 0.40 23.70 0.40 -28.00 0.40 -28.00 Using -GCpi 8.30 -15.80 8.30 -20.10 8.30 -20.10
References.
1. American Society of Civil Engineers, Publication ASCE 7-02, Minimum Design Loads for Buildings and Other Structures, Washington DC, 2002; 2. W. C. Bracken PE, Wind Load Design, Florida Engineering Society, Tallahassee, 2007; 3. K.C. Mehta, J.M Delahey, Guide to the Use of the Wind Load Provisions of ASCE 7-02 ASCE Press, Washington DC, 2003.