You are on page 1of 1

T YPE CK16

Dry Type High Speed Resistor Tapchanger

Tapchanger

Remote Tapchange Control Cubical

GENERAL INFORMATION On Load Tap Changer (OLTC) also suitable for Off Circuit application. Fitted with changeover selector enabling utilisation in Coarse-Fine or reversing winding configuration of Transformer. Fully bidirectional. Flange mounted, comprising driving mechanism and high speed selector switch. Local manual and electrical control, with provision for remote electrical operation. Optional equipment includes Remote Tapchange Control Cubical (RTCC) with indicating apparatus, Parallel operation control using group simultaneous scheme, Automatic, etc. TECHNICAL DATE Rated voltage Max. system voltage Max. voltage per step Max. No. of Steps Max. No. of positions TEST VOLTAGE : To Earth Between Phases Between Adjacent Contacts Across Tapping range Over Changeover Selector contact : : : : : Power Freq. (KV) 28 28 10 10 10 Impulse (KVPeak) 75 75 25 30 30 : : : : : 11KV 12 KV 220 V 16 17 Max. Rated through current Time per tap change. Total weight Short Circuit withstand : : : : 100 A 4-6 Secs. 470 Kgs. 2 KAmps. For 2 Secs.

Selector Switch SERVICING

Local Control Panel

Experienced Service Technicians available to attend to repairs. While requesting for such services, kindly indicate Tapchanger and Remote Tapchange Control Cubicle serial numbers. Price lists for recommended spares available on request. ORDER INFORMATION Please provide information as required in our data sheet PTTC 1007 to enable correct equipment to be offered. Our communications will use nomenclature as per exaple shown below :

1. VOLTAGE C = 11 KV 2. CONTAINER K

TAPCHANGER DIVISION CTR MANUFACTURING INDUSTRIES LTD. NAGAR ROAD, POONA - 411 014, INDIA

PHONE : (020) 26633402/05 FAX : 91 (020) 26633425 E-MAIL : tapchangers@ctr.in

PMTC. : 1023

3. CONTROL SCHEME MMC : Mechanical Manual Cranking ERI : Electrical Remote Independent EAR : Elctrical Automatic Remote ERG : Electrial Remote Group Simultaneous Parallel ARG : Automatic Remote Group Simultaneous Parallel

4. NO. OF STEPS 5. STEP VOLTAGE

6. PHASE CURRENT 7. USED ONLY EXCEPTIONALLY eg. OC : Off. Circiut OL : Off Load Tapchanger Fitted to Secondary Side

Rights reserved to amend design data without prior notification

JULY 2009