Professional Documents
Culture Documents
R-HG11-172.tif
Contents
Contents
Page
Description
General Construction and mode of operation Switching duties Standards and tests Ambient conditions and dielectric strength Contactor comparison
5
6 7 11 14 15 16
Equipment Selection
Ordering data and configuration example Selection of 3TL6 Selection of 3TL7 Selection of 3TL8 Accessories and spare parts
17
18 19 23 26 29
Technical Data
Electrical data, dimensions and weights Circuit diagrams Transport dimensions and weights
33
34 38 42
Annex
Inquiry form Configuration instructions Configuration aid
45
46 47 Foldout page
R-HG11-173.tif
Description
Contents
Contents
Page
Description
General Switching medium Construction Application examples Design 3TL6 vacuum contactor: Mode of operation Mechanical closing latch Mechanical closing lock-out Installation position
R-HG11-174.tif
5
6 7 7 7 7
8 8 8 8 9 9
Adjustment to the site altitude Blocking element to interlock two contactors 3TL7 vacuum contactor: Construction Mode of operation 3TL8 vacuum contactor: Mode of operation Mechanical closing latch Installation position Switching duties: Utilization categories Application Switching of motors Switching of transformers Switching of capacitors Surge protection via limiters Short-circuit protection Short-circuit protection via HV HRC fuses Short-circuit protection via circuit-breakers Standards and tests Ambient conditions Dielectric strength Contactor comparison
9 9
10 10 10
11 11 12 12 12 12 12 13 14 14 15 15 16
Description
General
3TL vacuum contactors are three-pole contactors with electromagnetic operating mechanism for medium-voltage switchgear. They are load breaking devices with a limited short-circuit making
and breaking capacity for applications with high switching rates of up to 1 million electrical operating cycles or 3 million mechanical operating cycles.
As the operating mechanism is located at the rear, 3TL6 vacuum contactors have a very compact design. This arrangement also enables front access to the main conductor terminals as well as very variable installation options. In 3TL7 (bottom right figure) / 3TL8 (top right figure) contactors, the low-voltage and medium-voltage components are not arranged one behind the other (3TL6), but one above the other. This provides a slim design which can easily be mounted on the different switchgear and frame structures.
R-HG11-119.eps
R-HG11-221.eps
R-HG11-220.tif
Description
Construction and mode of operation
Switching medium The vacuum switching technology, proven and fully developed for more than 30 years, serves as arc-quenching principle by using vacuum interrupters. Construction 3TL vacuum contactors consist of a medium-voltage and a low-voltage part. Together with the main conductor terminals, the vacuum interrupters constitute the medium-voltage part. All components required to operate the vacuum interrupter, such as the operating mechanism, closing latch and control unit make up the low-voltage part. These components can be arranged either one behind the other (3TL6) or one above the other (3TL7 and 3TL8). Application examples The vacuum contactors are suitable for operational switching of alternating current consumers in indoor switchgear, and can be used, e.g., for the following switching duties:
Motor starting Plugging or reversing the direction of rotation of motors Switching of transformers Switching of reactors Switching of resistive consumers such as electrical furnaces Switching of capacitors.
HG11-2625 eps
In contactor-type reversing starter combinations (reversing duty), only one contactor is required for each direction of rotation if HV HRC fuses are used for short-circuit protection. Design 3TL vacuum contactors are designed as an open construction, degree of protection IP00 according to IEC 60529 and DIN EN 60529.
HG11-2627 eps
With these duties, the contactors are used in conveying and elevator systems, pumping stations, air conditioning systems as well as in systems for reactive power compensation, and can therefore be found in almost every industrial sector.
HG11-2626 eps
Description
Construction and mode of operation
10 11 12
3TL6 vacuum contactor Mode of operation The atmospheric pressure exerts a force on the metal bellows of the vacuum interrupter. Without the influence of the operating mechanism, this would close the contact gap. The opening springs (6) keep the moving interrupter contact in open position via the integral rocker (10). To close the vacuum contactor, the compressive force of the opening springs (6) is overcome by the magnet system (2). The magnet armature (4) is attracted, thus moving the integral rocker (10), which releases the moving interrupter contact from the open position. The atmospheric pressure closes the contacts. The integral rocker (10) compresses the contact pressure springs (16), thus generating the necessary contact force. When the magnetic excitation is de-energized, the opening springs (6) open the contact gap via the integral rocker (10) and the moving interrupter contact. The DC magnet system operates as an economy circuit, proving a high mechanical endurance and a low pickup and holding power. Mechanical closing latch The latch (7) holds the vacuum contactor in closed position even without excitation of the magnet system. When the magnet system is energized, the integral rocker is latched mechanically in the CLOSED position through a lever and roller system. The vacuum contactor is released electrically by means of a latch release solenoid (9) or mechanically by the tripping bolt (8). Mechanical closing lock-out
1
HG11-2628 eps
13
14 15
Construction of the 3TL6 vacuum contactor (front view)
Lowvoltage part Mediumvoltage part
HG11-2629_en eps
10 16 12
1 2 3 4 5 6 7 8 9
13 14 15
Construction of the 3TL6 vacuum contactor in OPEN position Side view from the left (section). The arrows show the moving direction for CLOSE
Legend 1 Operating mechanism box 2 Magnet system (magnet coil) with rectifier and economy resistor 3 Terminal strip 4 Magnet armature 5 Mechanical closing lock-out 6 Opening spring 7 Latch 8 Tripping bolt 9 Latch release solenoid with rectifier and varistor module 10 Integral rocker 11 Position indicator O - I 12 Upper main conductor terminal 13 Vacuum interrupter 14 Lower main conductor terminal 15 Molded-plastic housing 16 Contact pressure spring
The mechanical closing lock-out (5) prevents unintentional closing of the vacuum contactor, e.g. due to vibrations or while racking the withdrawable part. During operational switching, the closing lock-out is inactive.
Installation position 3TL6 vacuum contactors can be installed in different positions. Besides wall mounting (vertical arrangement), they can also be mounted on the floor (horizontal arrangement).
HG11-2630 eps
Description
Construction and mode of operation
3TL6 vacuum contactor (continuation) Adjustment to the site altitude At the factory, the vacuum contactor is adjusted to a site altitude of 200 m to + 1250 m above sea level. For other site altitudes, the contactor must be adapted to the corresponding site altitude range by means of adjusters located on the rear side of the device (see figure on the right). Blocking element to interlock two contactors To interlock two contactors mutually for reversing duty, a mechanically operating blocking element is available on request (for 3TL61 only). The blocking element is fixed between the two contactors, blocking the movement of the operating rocker of the two contactors alternatively. This excludes a phase short-circuit that could occur when the two directions of rotation are activated simultaneously as a result of mechanical impact and electrical maloperation.
Adjusters (on the rear side of the device) to set the site altitude Setting ranges above sea level: 1. + 1250 m to + 2500 m 2. 200 m to + 1250 m 3. 1250 m to + 200 m
3TL7 vacuum contactor Construction 3TL7 vacuum contactors have two slim pole shells above the operating mechanism. The vacuum interrupters (2) are fixed between two pole half-shells (1). This design enables easy and universal installation on the different switchgear and frame structures. The low-voltage part contains the magnetic drive, auxiliary contactor and auxiliary contacts. Mode of operation The magnetic drive of the 3TL7 vacuum contactor opens and closes the contacts of the vacuum interrupters. Due to the use of a special double coil, the magnetic drive is designed for the closing and holding process. To implement a mechanical interlocking between the withdrawable part of the switchgear and the vacuum contactor, there is a lug available on the operating shaft which transfers the signalling commands.
Medium-voltage part
HG11-2631 eps
1 2
3 4
Construction of the 3TL7 vacuum contactor (front view)
HG11-2632_en eps
Legend 1 Pole half-shell 2 Vacuum interrupter 3 Mechanism section 4 Auxiliary plug connector
6 7 8 9 10
5 Upper main conductor terminal 6 Lower main conductor terminal 7 Mechanical connection between medium-voltage and low-voltage part 8 Operating shaft 9 Auxiliary contact block 10 Magnet system (magnet coil)
Low-voltage part
R-HG11-224.eps
Description
Construction and mode of operation
1 2
Mode of operation 3TL8 vacuum contactors open and close the contacts of the vacuum interrupters (2). Due to the use of the electronic economy circuit (12), the magnet system (11) is to a large extent independent of the voltage type and level. Mechanical closing latch The mechanical closing latch (6) holds the vacuum contactor in closed position even without excitation of the magnet system (11). The latching module of the mechanical closing latch (6) is accommodated in the mechanism section. When the magnet system (11) is energized, the vacuum interrupter (2) is latched mechanically in CLOSED position through a lever and roller system. The vacuum contactor is released electrically by means of a latch release solenoid or mechanically by a tripping bolt (customer control required). The command duration for the latch release coil must range between 100 ms and 1 s. De-energizing must be provided externally.
1
12
Construction of the 3TL8 vacuum contactor (front view)
3 4 5 6 7
HG11-2634_en eps
Legend
Medium-voltage part
1 Molded-plastic housing 2 Vacuum interrupter 3 Position indicator O - I 4 Operating shaft (short or long version)
9 10 11
5 Drive lever 6 Mechanical closing latch with rectifier module for AC operation 7 Terminal strip 8 Upper main conductor terminal 9 Lower main conductor terminal
Low-voltage part
10 Mechanical connection between medium-voltage and low-voltage part 11 Magnet system (magnet coil) 12 Electronic module (electronic economy circuit) with connection terminals
Installation position 3TL8 vacuum contactors can be installed in different positions. Besides wall mounting (vertical arrangement), they can also be mounted on the floor (vertical or horizontal arrangement).
Horizontal arrangement
10
HG11-2635 eps
Description
Switching duties
Utilization categories In IEC 60470, power contactors are divided into different utilization categories. According to these categories, 3TL vacuum contactors are dimensioned for different electrical consumers and operating conditions. The opposite table shows typical applications in accordance with the respective utilization categories.
Utilization category AC-1 AC-2 AC-3 AC-4 Typical applications Non-inductive or slightly inductive loads, resistance furnaces Slip-ring motors: Starting, switching off Squirrel-cage motors: Starting, switching off during running Squirrel-cage motors: Starting, plugging 1), reversing 1), inching 2)
1) By plugging is understood stopping or reversing the motor rapidly by reversing motor primary connections while the motor is running 2) By inching is understood energizing a motor once or repeatedly for short periods to obtain small movements of the driven mechanism
Application 3TL vacuum contactors are 3-pole contactors with electromagnetic operating mechanism for medium-voltage switchgear. They are load breaking devices with a limited short-circuit making and breaking capacity for applications with high switching rates (> 10000 operating cycles). Vacuum contactors are suitable for operational switching of alternating-current consumers in indoor switchgear, and can be used e.g. for the following switching duties:
Switching of three-phase motors in AC-3 or AC-4 operation Switching of transformers Switching of reactors Switching of resistive consumers Switching of capacitors.
Resistive consumers Reactors
HG11-2549a eps
Symbols
Application examples
M 3~
Transformers
HG11-2548b eps
HG11-2547b eps
Conveyor and elevator systems, compressors, ventilation and heating Ring-main units, industrial system distributions
In contactor-type reversing starter combinations (reversing duty), only one contactor is required for each direction of rotation if HV HRC fuses are used for short-circuit protection.
Capacitors
HG11-2551a eps
HG11-2550b eps
Industrial system distributions, DC-link reactors, reactive power compensation systems Heating resistors, electric furnaces
11
Description
Switching duties
Switching of motors
Circuit diagram Mode of operation Switching of accelerated motors
M 3~
HG11-2552b eps
U1 V1 W1
U1 V1 W1
M 3~
3TL vacuum contactors are especially suitable for frequent operation of motors. As the chopping currents of the contactors are w 5 A, no unpermissibly high overvoltages are produced when accelerated motors are switched during normal operation. However, when high-voltage motors with starting currents of w 600 A are stopped during start-up, switching overvoltages may arise. The magnitude of these overvoltages can be reduced to harmless values by means of special surge limiters. 3EF surge limiters can be arranged in parallel to the cable sealing ends, preferably in the cable compartment. The surge limiters consist of non-linear resistors (metal-oxide varistors SIOV) and a series-connected spark gap. During installation it must be observed that the surge limiter is flexibly mounted on one side for mechanical reasons. Switching of transformers When inductive currents are interrupted, current chopping can produce overvoltages at the contact gap. Such overvoltages can be controlled with a protective circuit composed of 3EF surge limiters. Switching of capacitors 3TL vacuum contactors can interrupt capacitive currents up to 250 A up to the rated voltage of 12 kV without restrikes, and thus without overvoltages. Surge protection via limiters
M 3~
Circuit examples for surge protection of three-phase motors with a starting current w 600 A 1) With surge limiter
HG11-2553b eps
U1 V1 W1
HV HRC fuses
Circuitbreaker
Overvoltages can arise as a consequence of multiple restrikes or by virtual current chopping, e.g. when motors are switched in braked condition or during start-up. Motors with a starting current w 600 A are endangered. Safe protection against overvoltages is ensured by surge limiters; circuit examples are shown above. Short-circuit protection 3TL vacuum contactors are not designed to switch short-circuit currents. It is therefore absolutely essential to provide short-circuit protection. The best protection is provided by HV HRC fuses, but circuit-breakers can also be used under the preconditions described above.
Vacuum contactor
Surge limiter
HG11-2279c_en eps
Consumer
12
Description
Switching duties
Short-circuit protection via HV HRC fuses At high short-circuit currents, HV HRC fuses have a current-limiting effect, i.e. the fuse limits the short-circuit current to the let-through current. When selecting the fuses, the type of consumer must be observed, e.g. motor, transformer, capacitors. The diagram shows an example for the coordination of a HV HRC fuse with an overcurrent-time protection. Co-ordinating the components of the motor circuit:
The time-current characteristic must be located on the right of the motor starting current (point A). The rated current of the HV HRC fuse-link must exceed the normal current of the motor. The current corresponding to the intersection B of the HV HRC fuse-link characteristic and the characteristic of the overcurrent-time protection must be higher than the minimum breaking current of the HV HRC fuse-link. If this is not feasible, it must be ensured that overload currents that are smaller than the minimum breaking current of the HV HRC fuse-link are interrupted by the switching device via the striker. This prevents thermal overloading of the HV HRC fuse-link, which would otherwise be destroyed. The selected HV HRC fuse link limits the sustained symmetrical short-circuit current Ik to the let-through current ID shown in the diagram for the current-limiting characteristics (ID as a function of IK for HV HRC fuse-links with different rated currents). The maximum permissible let-through current is ID = 50 kA.
10 3 s 5 Time 2 10 2 5 2 10 1 5 2 10 0 5 2 10 -1 5 2 10 -2 102 4 3 A 2
125 A
1
HG12-2106_en eps
Example for the coordination of an HV HRC fuse characteristic 125 A with a motor characteristic 1 Characteristic of HV HRC fuse 3GD11258-4D 2 Characteristic of the overcurrent-time protection 3 Motor starting time 4 Motor starting current
Requirements
The let-through current ID must not exceed 50 kA to 7.2 kV In case of low-voltage supply via a control transformer, short-circuit currents ranging above the limit switching capacity must be interrupted within 80 ms. This requirement does not apply if
the mechanical latch is provided, or the opening times have been extended so much, that in the a.m. range the contactor can only open when the fuse has interrupted the current.
Due to the arising motor starting current, the instant when the motor starts represents the maximum stress for the HV HRC fuse. This stress must neither operate nor pre-damage the fuse. Other factors of influence on the stress of the HV HRC fuses are the starting time and the starting frequency of the motors.
13
Description
Switching duties, standards and tests
Short-circuit protection for class E2 controllers according to UL 347/CSA C22.2 For using 3TL6 and 3TL8 vacuum contactors as class E2 controllers for 7.2 kV, Siemens fuses of type 3GD1 150-4D (7.2 kV/250 A) or other fuses with a comparable currenttime characteristic are specified for short-circuit protection. If two fuse-links are connected in parallel, the symmetrical short-circuit current determined has to be divided by two, and the associated let-through current for one fuse-link must be stated. This value must then be multiplied by two in order to obtain the total let-through current, which must not exceed the permissible value for the vacuum contactor. The parallel connection should ensure that the resistance values in the two branches are almost the same. When the fuses operate, the vacuum contactor must be switched off. A suitable device, actuated by the striker of the HV HRC fuse-link, should be provided. Fuse monitoring To prevent a three-phase load (e.g. a motor) from being supplied only by two phases when a fuse has operated, the fuse-bases can be equipped with a fuse trip indicator. This device can be used either to energize a warning signal or to switch off the vacuum contactor. Short-circuit protection by circuit-breakers Consumers for which no suitable fuses are available can also be protected by circuit-breakers. Due to the longer break time of the circuit-breakers (max. permissible 120 ms), the symmetrical short-circuit current must not exceed the maximum permissible value (e.g. 20 kA at 7.2 kV for 3TL6 vacuum contactors). As a consequence of the longer opening time, the interrupters should be replaced immediately by new ones after carrying the maximum permissible symmetrical short-circuit current, as their service life has been considerably reduced. Overload protection For protecting high-voltage motors against overload, it is possible to use thermally delayed overcurrent relays with suitable current transformers. Trip-free mechanism All contacts of the vacuum contactors are trip-free. The OPEN command interrupts the CLOSE command, i.e. the instant of the OPEN command determines whether the contacts will close or not.
Standards 3TL vacuum contactors are designed in open construction, with degree of protection IP00 according to IEC 60529 and DIN EN 60529. They conform to the standards for high-voltage alternating current contactors above 1 kV and up to 12 kV:
IEC 60470 UL Standard 347 CSA C22.2
As there are no standards available for 24 kV, 3TL7 vacuum contactors are designed according to IEC 60470, Edition 05.2000 / DIN EN 60470 Edition 01.2002 DIN EN 62271-100 Edition 01.2004. Tests For the development and type testing of power switching devices, we have accredited testing laboratories at our disposal:
Testing laboratories with a high electrical testing capacity
Testing laboratories to prove the following features: Mechanical operation Reliability Dielectric strength Temperature-rise performance Climatic resistance.
To obtain secure results, comprehensive test series are performed for the type tests defined in the standards. If the customer requests further tests that should not be performed at internal Siemens laboratories, other accredited testing institutes are available as well.
14
Description
Ambient conditions and dielectric stength
Ambient conditions The vacuum contactors are designed for the normal operating conditions defined in the standards. Condensation can occasionally occur under the ambient conditions shown opposite. Vacuum contactors are suitable for use in the following climatic classes according to IEC 60721: Climatic ambient conditions: Class 3K4 1) Class 3K6 2) Class 3Z2 Class 3Z5 Class 3B1 Class 3M2 Class 3C2 3) Class 3S2 4)
see table max. 95% per day max. 90% per month
1
HG11-2636_en eps
Biological ambient conditions: Mechanical ambient conditions: Chemically-active substances: Mechanically-active substances:
Temperature value 3TL6 Maximum value Maximum 24-hour mean value Minimum value + 80 C + 75 C 25 C
1) Low temperature limit: 25 ( 5 for 3TL7) 2) Without icing and wind-driven precipitation 3) Without appearance of saline fog with simultaneous condensation 4) Restriction: Clean insulation parts
The dielectric strength of air insulation decreases with increasing altitude due to low air density. According to IEC 62271-1, the values of the rated lightning inpulse withstand voltage and the rated short-duration powerfrequency withstand voltage specified in the chapter "Technical Data" apply to a site altitude of 1000 m above sea level. For an altitude above 1000 m, the insulation level must be corrected according to the opposite diagram. The characteristic shown applies to both rated withstand voltages. To select the devices, the following applies: U W U0 x Ka
U Rated withstand voltage under reference atmosphere U0 Rated withstand voltage requested for the place of installation Ka Altitude correction factor according to the opposite diagram
1.40
1.30
1.20
1.10
1.00 1000
1500
2000
2500
Example For a requested rated lightning impulse withstand voltage of 60 kV at an altitude of 2500 m, an insulation level of 72 kV under reference atmosphere is required as a minimum: 72 kV W 60 kV x 1.2
HG11-2517c_en eps
Dielectric strength
1.50
15
Description
Contactor comparison
Contactor comparison
3TL6 Rated voltage Rated normal current Switching rate Endurance Contactor Vacuum interrupter Chopping current Economy circuit Auxiliary contacts Operating mechanism Type of construction Main conductor terminals Auxiliary conductor terminals Additional components 7.2/12 kV 400/450 A 1200/600 operating cycles/h Operating cycles Mech. endurance 3/1 mio. Mech. endurance 2/1 mio. Electr. endurance 1/0.5 mio. <5A Via economy resistor Positively driven aux. contacts 8 NO, 7 NC On the rear of the vacuum interrupters Compact At the front of the vacuum interrupters Terminal strip with testing possibilities in built-in condition (optionally withdrawable terminal strip) Mechanical closing latch 1), mechanical closing lock-out, extension or reduction of opening time 3TL7 24 kV 800 A 60 operating cycles/h Operating cycles Mech. endurance 1 mio. Mech. endurance 1 mio. Electr. endurance 0.5 mio. <5A Via automatic coil changeover Positively driven aux. contacts 8 NO, 8 NC Below the vacuum interrupters Slim At the rear of the vacuum interrupters Wiring of auxiliary contacts to central plug connector Reduction of opening time, more on request 3TL8 7.2 kV 400 A 1200 operating cycles/h Operating cycles Mech. endurance 1 mio. Mech. endurance 0.25 mio. Electr. endurance 0.25 mio. w 0.6 A Integrated in electronic module Positively driven aux. contacts 4 NO, 4 NC Below the vacuum interrupters Slim At the rear of the vacuum interrupters Direct tapping at the terminals (optionally, wiring of auxiliary contacts to central terminal strip) Mechanical closing latch 1), long operating shaft for external non-force components, reduction of opening time
1) For operating voltages of the mechanical closing latch under 100 V, a stable power supply must be observed.
16
Equipment Selection
Contents
Contents
Page
Equipment Selection
Ordering data and configuration example Selection of 3TL6: Voltage level 7.2 kV Voltage level 12 kV Terminal strip, auxiliary contacts Additional components Mode of operation for magnet system Operating voltage for magnet system Additional equipment Selection of 3TL7:
R-HG11-220.tif
17
18
19 19 19 20 21 21 22
Voltage level 24 kV Auxiliary switch Mode of operation for magnet coil Operating voltage for magnet coil Language of operating instructions Type of construction Site altitude Additional equipment Selection of 3TL8: Voltage level 7.2 kV Design Auxiliary switch, wiring Operating voltage for magnet coil Operating voltage for closing latch Opening time Language of operating instructions/ routine test certificate
23 23 23 23 24 24 24 25
26 26 26 27 27 27 28 28 29
0R-HG11-221.eps
17
Equipment Selection
Ordering data and configuration example
Order number structure The vacuum contactors consist of a medium-voltage and a low-voltage part. The relevant data make up the 12 to 14-digit order number. The medium-voltage part covers the main electrical data of the contactor poles. The low-voltage part covers the auxiliary devices which are necessary for operating and controlling the contactor. Order codes Individual equipment versions are explained more in detail by a 3-digit order code. Several order codes can be added to the order number in succession and in any sequence.
Special version () In case of special versions, - Z is added to the order number and a descriptive order code follows. If several special versions are required, the suffix - Z is listed only once. If a requested special version is not in the catalog and can therefore not be ordered via order code, it has to be indentified with Y 9 9 after consultation. The agreement hereto is made directly between your responsible sales partner and the order processing department in the Switchgear Factory Berlin.
2
1st position 2nd position 3rd position 4th to 6th position1) Medium-voltage part Superior group Switching devices Main group Contactors Subgroup Vacuum contactors Basic equipment Design and ratings medium-voltage part Low-voltage part Secondary equipment Operating voltages, auxiliary equipment Order codes Group of 3 after the Order No. Format: a n a Special versions () Initiated with -Z Group of 3 after the Order No. Format: a n n 1) Deviation in the distribution for the different contactors
n: numerical
6 7 8 9 10 11 12 13 14 Order codes
n n n
Configuration example In order to simplify the selection of the correct order number for the requested contactor, you will find a configuration example on each page of the chapter Equipment Selection. This example is continued, so that at the end of the equipment selection of a product group (pages 22, 25 and 28) a completely configured contactor results as an example.
On the foldout page we offer a configuring aid. Here you can fill in the order number you have determined for your contactor.
n n n n n n n
18
Equipment Selection
Selection of 3TL6
7.2 kV
50/60 Hz Rated lightning impulse withstand voltage open contact gap Rated lightning impulse withstand voltage to earth Rated short-duration power-frequency withstand voltage to earth Rated short-duration power-frequency withstand voltage open contact gap
Position:
10 11
Order codes
6 n n n n n n n
n n n
Rated voltage
See page 20
See page 21
See page 21
See page 21
Ur kV
Up kV
Up kV 40
Ud kV 20 Ud = 32 kV
Ud kV 20 Ud = 20 kV
Ir A 450 3 T L 6 1 n 3 Z E 1 6
See page 22
12 kV
50/60 Hz Ur kV Up kV Up kV 60 Ud kV 28 Ud = 42 kV Ud kV 28 Ud = 42 kV Ir A 400 3 T L 6 5 n 5 Z E 1 3
12 75 Special version
Terminal strip
Auxiliary contacts
4 NO + 3 NC 6 NO + 5 NC 6 NO + 5 NC 8 NO + 7 NC 2)
1 2 3 8
1) Attention! In 3TL6 contactors with withdrawable terminal strip, the opening time and thus the duration of the coil operation cannot be limited internally for reasons of space. 2) 4th auxiliary contact block not wired
Configuration example 3TL6 vacuum contactor Rated voltage Ur = 12 kV Rated lightning impulse withstand voltage Up (to earth) = 75 kV Rated lightning impulse withstand voltage Up (open contact gap) = 60 kV Rated short-duration power-frequency withstand voltage Ud (to earth) = 28 kV Rated normal current Ir = 400 A Terminal strip, withdrawable, auxiliary contacts 6 NO + 5 NC Special version Ud (to earth) = 42 kV Example for Order No.: Order codes:
5 3
5 Z Z E 1 3
3 E
T 1
L 3
n n n n
19
Equipment Selection
Selection of 3TL6
Position:
10 11
Order codes
Order No:
3 T
See page 22 Z
n n n
Options
Without additional components Mechanical closing latch, 1 NO assigned Mechanical closing lock-out 1) Closing latch and closing lock-out, 1 NO assigned Shunt release with closing latch without closing lock-out, 1 NO assigned Shunt release with closing latch and closing lock-out, 1 NO assigned Requested operating voltage for shunt release (8th position 4 or 5), to be specified in clear text Mechanical closing latch (like 1), but with different operating voltage to the magnet system Mechanical closing latch and closing lock-out (like 3), but with different operating voltage of the latch to the magnet system Requested different operating voltage for closing latch (8th position 6 or 7), to be specified in clear text Undervoltage release 1) Application for wall mounting only
0 1 2 3 4 5 Y 9 9
6 7 8 Z Y 9 9
Configuration example 3TL6 vacuum contactor (Ur = 12 kV, Up (to earth) = 75 kV, Up (open contact gap) = 60 kV, Ud = 28 kV, Ir = 400 A) With mechanical closing lock-out Example for Order No.: Order codes:
3 T
6 5 3 5 2 2 n n n
3 E
T 1
L 3
20
Equipment Selection
Selection of 3TL6
9th/10th/11th position Mode of operation and operating voltage for magnet system and closing latch
AC operation with voltage DC operation with voltage
Position:
10 11
Order codes
Order No:
6 n n n n n n n
See page 22
n n n
A A A A A A B B B B B B B
F G J K L P B C W E F G M
2 2 2 2 2 2 4 4 4 4 4 4 4
Configuration example 3TL6 vacuum contactor (Ur = 12 kV, Up (to earth) = 75 kV, Up (open contact gap) = 60 kV, Ud = 28 kV, Ir = 400 A) Mode of operation DC operation for magnet system and closing latch Operating voltage 60 V DC Example for Order No.: Order codes:
6 5 3 5 2 B E 4 4 Z
3 E
T 1
L 3
21
Equipment Selection
Selection of 3TL6
Additional equipment
Position:
10 11
Order codes
Order No:
6 n n n n n n n
n n n
Options
Surge protection circuit in secondary circuit with varistor module for DC voltage 3AX1526-0F Surge protection circuit in secondary circuit with rectifier module for AC voltage 3AX1525-1F Wiring, halogen-free and flame-retardant Additional rating plate, loose delivery 3TL61 with rating plate 6 kA instead of 5 kA, and 3.3 kV instead of 7.2 kV Seaworthy packing inside Germany Packing in wooden crate incl. built-in equipment Routine test certificate in English enclosed Routine test certificate to customer Routine test certificate in German enclosed Routine test certificate in French enclosed Routine test certificate in Spanish enclosed Customer acceptance test Opening time w 50 ms 1) Opening time w 120 ms 1) Opening time 250 ms 70 ms 1) Opening time 120/50 ms 1) Operating instructions in French/Spanish Operating instructions in German/Russian 1) Opening times cannot be combined with the mechanical closing latch.
Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z
A A A B E F F F F F F F F G G G G L L
0 0 1 0 0 0 0 2 2 2 2 2 5 0 0 0 0 0 0
0 1 0 0 6 2 4 0 3 4 5 6 0 1 2 3 8 1 2
Configuration example 3TL6 vacuum contactor Rated voltage Ur = 12 kV Rated lightning impulse withstand voltage Up (to earth) = 75 kV Rated lightning impulse withstand voltage Up (open contact gap) = 60 kV Rated short-duration power-frequency withstand voltage Ud (to earth) = 28 kV Rated normal current Ir = 400 A Terminal strip, withdrawable, auxiliary contacts 6 NO + 5 NC Special version Ud (to earth) = 42 kV With mechanical closing lock-out Mode of operation DC operation for magnet system and closing latch Operating voltage 60 V DC for magnet system and closing latch Wiring, halogen-free and flame-retardant Customer acceptance test Operating instructions in French/Spanish Example for Order No.: Order codes:
5 3
5 2 B E 4 Z Z Z Z A F L 1 5 0 0 0 1 Z E 1 3
3 E
T 1
L 3
6 +
5 0
2 F
B 5
E 0
4 + L 0 1
A 1
22
Equipment Selection
Selection of 3TL7
24 kV
50/60 Hz Rated lightning impulse withstand voltage open contact gap Rated lightning impulse withstand voltage to earth Rated short-duration power-frequency withstand voltage
Position:
10 11 12
13 14
Order codes
7 n n n n n n n n n n
n n n
Rated voltage
See page 24
See page 24
See page 24
Ur kV 24
Up kV 95
Up kV 75
Ud kV 50
Ir A 800 3 T L 7 1 2
See page 25
2
5 8
Options
4 NO + 4 NC available for customer with 24-pole plug 8 NO + 8 NC available for customer with 64-pole plug
8th/9th/10th/11th position Mode of operation and operating voltage for magnet coil
AC operation with voltage DC operation with voltage
110 V AC 230 V AC
0 0 0 0 0
A G 2 A L 2 B F 4 B G 4 B M 4
Configuration example 3TL7 vacuum contactor Rated voltage Ur = 24 kV Rated lightning impulse withstand voltage Up (to earth) = 95 kV Rated lightning impulse withstand voltage Up (open contact gap) = 75 kV Rated short-duration power-frequency withstand voltage Ud = 50 kV Rated normal current Ir = 800 A Auxiliary switch 8 NO + 8 NC Mode of operation AC operation for magnet coil Operating voltage 110 V AC for magnet coil Example for Order No.: Order codes:
2 8 0 A G 2
A G 2 n n n
23
Equipment Selection
Selection of 3TL7
Position:
10 11 12
13 14
Order codes
Order No:
7 n n n n n n n n n n See page 25 0 0 1 A B D C
n n n
Option
German/English
Options
Version standard/industry (interrupters in vertical position) Version with insulating plate (interrupters in vertical position)
Options
Site altitude 0 1250 m Site altitude 1250 2500 m Site altitude 2500 4000 m Site altitude 4000 5000 m
Configuration example 3TL7 vacuum contactor (Ur = 24 kV, Up (to earth) = 95 kV, Up (open contact gap) = 75 kV, Ud = 50 kV, Ir = 800 A) Language of operating instructions German/English Type of construction, version with insulating plate (interrupters in vertical position) Site altitude 0 1250 m Example for Order No.: Order codes:
7 1 2 8 0 A G 2 0 1 A
A G 2
24
Equipment Selection
Selection of 3TL7
Additional equipment
Position:
10 11 12
13 14
Order codes
Order No:
7 n n n n n n n n n n
n n n
Options
Wiring, halogen-free and flame-retardant Additional rating plate, loose delivery Silver-plated connecting surfaces Seaworthy packing inside Germany Packing in wooden crate incl. built-in equipment Routine test certificate in English enclosed Routine test certificate in German enclosed Routine test certificate in French enclosed Routine test certificate in Spanish enclosed Customer acceptance test Opening time w 50 ms
Z Z Z Z Z Z Z Z Z Z Z
A B D F F F F F F F G
1 0 0 0 0 2 2 2 2 5 0
0 0 9 2 4 0 4 5 6 0 1
Configuration example 3TL7 vacuum contactor Rated voltage Ur = 24 kV Rated lightning impulse withstand voltage Up (to earth) = 95 kV Rated lightning impulse withstand voltage Up (open contact gap) = 75 kV Rated short-duration power-frequency withstand voltage Ud = 50 kV Rated normal current Ir = 800 A Auxiliary switch 8 NO + 8 NC Mode of operation AC operation for magnet coil Operating voltage 110 V AC for magnet coil Language of operating instructions German/English Type of construction, version with insulating plate (interrupters in vertical position) Site altitude 0 1250 m Additional rating plate, loose delivery Example for Order No.: Order codes:
2 8 0 A G 2 0 1 A Z Z B 0 0
3 B
T 0
L 0
A G 2
25
Equipment Selection
Selection of 3TL8
7.2 kV
50/60 Hz Rated lightning impulse withstand voltage open contact gap Rated lightning impulse withstand voltage to earth Rated short-duration power-frequency withstand voltage
Position:
10 11 12
Order codes
8 n n n n n n n n
n n n
Rated voltage
See page 27
See page 27
See page 27
See page 28
Ur kV 7.2
Up kV 60
Up kV 40
Ud kV 20
Ir A 400 3 T L 8 1 0
Options
Short operating shaft Long operating shaft for external non-force components Short operating shaft and site altitude 2000 4100 m Long operating shaft and site altitude 2000 4100 m
0 1 3 4
Auxiliary switch
Wiring
2 NO + 2 NC 4 NO + 4 NC 4 NO + 4 NC 4 NO + 4 NC 4 NO + 4 NC 4 NO + 4 NC
Without additional components Without additional components Without auxiliary contact wiring with closing latch 1) Auxiliary contacts wired to terminal strip incl. latch 1) Auxiliary contacts wired to terminal strip without latch Auxiliary contacts wired without terminal strip
0 1 2 3 5 6
1) The selection of a mechanical closing latch always requires the selection of an operating voltage (10th position) and an opening time with latch (11th position)
Configuration example 3TL8 vacuum contactor Rated voltage Ur = 7.2 kV Rated lightning impulse withstand voltage Up (to earth) = 60 kV Rated lightning impulse withstand voltage Up (open contact gap) = 40 kV Rated short-duration power-frequency withstand voltage Ud = 20 kV Rated normal current Ir = 400 A Design with short operating shaft Auxiliary switch 4 NO + 4 NC without additional components Example for Order No.: Order codes:
0 0 1 1 n n n n
26
See page 28
Equipment Selection
Selection of 3TL8
Position:
10 11 12
Order codes
Order No:
8 n n n n n n n n See page 28
See page 28
n n n
Voltage
DC voltage
AC voltage
Without mechanical closing latch 1) 24 V DC 2) 30 V DC 2) 48 V DC 2) 60 V DC 2) 110 V DC 125 V DC 220 V DC to 250 V 110/115 V AC 120/127 V AC 220/240 V AC 380 V AC 440 V AC 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
A B C D E F G H L M N P Q
Time
Remarks
325 ms 75 ms w 40 ms 3) w 40 ms
Without mechanical closing latch 1) Without mechanical closing latch 1) With mechanical closing latch
0 2 5
1) Without mechanical closing latch can only be selected if the 8th position does not contain any latching option either (0, 1, 5 or 6) 2) For operating voltages of the mechanical closing latch under 100 V, a stable power supply must be observed 3) Implementation by external circuit with control contactor provided by the customer Configuration example 3TL8 vacuum contactor (Ur = 7.2 kV, Up (to earth) = 60 kV, Up (open contact gap) = 40 kV, Ud = 20 kV, Ir = 400 A) Operating voltage of the magnet coil 110 to 250 V AC/DC Without mechanical closing latch Opening time 325 ms 75 ms without mechanical closing latch Example for Order No.: Order codes:
8 1 0 0 1 B A 0 0 n
27
Equipment Selection
Selection of 3TL8
12th position Position: Language of the operating instructions/routine test certificate Order No:
10 11 12
Order codes
8 n n n n n n n n
n n n
Operating instructions
0 1 4 5 6 7
Additional equipment
Options
Wiring, halogen-free and flame-retardant Additional rating plate, loose delivery Seaworthy packing inside Germany Packing in wooden crate incl. built-in equipment Customer acceptance test
Z Z Z Z Z
A B F F F
1 0 0 0 5
0 0 2 4 0
Configuration example 3TL8 vacuum contactor 3 Rated voltage Ur = 7.2 kV Rated lightning impulse withstand voltage Up (to earth) = 60 kV Rated lightning impulse withstand voltage Up (open contact gap) = 40 kV Rated short-duration power-frequency withstand voltage Ud = 20 kV Rated normal current Ir = 400 A Design with short operating shaft Auxiliary switch 4 NO + 4 NC without additional components Operating voltage of the magnet coil 110 to 250 V AC/DC Without mechanical closing latch Opening time 325 ms 75 ms without mechanical closing latch Language of operating instructions in French/Spanish, without routine test certificate Example for Order No.: Order codes: 3
0 0 1 B A 0 1
28
Equipment Selection
Accessories and spare parts
Remark for orders The order numbers are applicable to contactors of current manufacture. When mounting parts or spare parts are being ordered for an existing vacuum contactor, always quote the type designation, serial number and the year of manufacture of the contactor to be sure to get the correct delivery. Note: Vacuum interrupters and other spare parts must only be replaced by instructed personnel.
Designation
Remarks
Operating voltage
Order No.
Magnet coil
For 3TL6 Left 2 NO + 2 NC 1) Left 3 NO + 3 NC 1) Right 2 NO + 2 NC 1) Right 3 NO + 3 NC 1) For 3TL7 4 NO + 4 NC 8 NO + 8 NC For 3TL8 At the top 2 NO + 2 NC Below 2 NO + 2 NC For 3TL6 (from year of manuf. 10/90, from serial no.31 375 035)
3TY7 561-1NA0 3TY7 561-1QA0 3TY7 561-1PA0 3TY7 561-1RA0 3SV9 894-2AA0 3SV9 896-2AA0 3TY7 561-1SA0 3TY7 561-1NA0 3TY5 651-0AG7 3TY5 651-0AL7 3TY5 651-0AN2 3TY5 651-0AN7 3TY5 651-0AQ2 3TY5 651-0AR7 3TY5 651-0AU7 3TY5 651-0BB4 3TY5 651-0BE4 3TY5 651-0BF4 3TY5 651-0BG4 3TY5 651-0BM4 3TY5 741-0AG2 3TY5 741-0AL2 3TY5 741-0BF4 3TY5 741-0BG4 3TY5 741-0BM4 3TY5 811-0BA0 3TY5 664-1DA0 3TY5 664-1EA0 3TY5 664-1FA0 3TY5 664-1GA0 3TY5 664-1HA0 3TY5 664-1JA0 3TY5 664-1KA0 3TY5 664-0AA0 3TY5 664-0CA0 3TY5 664-0DA0 3TY5 664-0EA0 3TY5 664-0FA0
For 3TL7
For 3TL8 For 3TL6 (from year of manuf. 10/90, from serial no.31 375 035)
100/115 V AC , 50/60 Hz 120/125/127 V AC , 50/60 Hz 220 V AC , 50/60 Hz 230/240 V AC , 50/60 Hz 380 V AC, 50 Hz 400/415/440 V AC, 50 Hz 500 V AC, 50 Hz 24 V DC 60 V DC 110 V DC 125 V DC 220 V DC 110 V AC, 50/60 Hz 230/240 V AC, 50/60 Hz 110 V DC 120/125 V DC 220 V DC 110 V 250 V AC/DC 110/115 V AC 120/125/127 V AC 220 V AC 230/240 V AC 380 V AC 400/415/440 V AC 500 V AC 24 V DC 60 V DC 110 V DC 125 V DC 220 V DC
1) The information left/right applies when the vacuum interrupters are observed with the rocker at the top
29
Equipment Selection
Accessories and spare parts
Designation
Remarks
Operating voltage
Order No.
110 V 250 V AC/DC 24 V DC 60 V DC 110 V DC 125 V DC 220 V DC 110 127 V AC , 50/60 Hz 220 240 V AC 24 V DC 110 125 V DC 220 V DC 110 127 V AC, 50/60 Hz 220 240 V AC, 50/60 Hz 110 V DC 220 V DC 230 V AC, 50 Hz 110/115 V AC, 50/60 Hz 120/125/127 V AC, 50/60 Hz 220 V AC, 50/60 Hz 230/240 V AC, 50/60 Hz 380 V AC, 50 Hz 400/415/440 V AC, 50 Hz 500 V AC, 50 Hz 24 V DC 30 V DC 60 V DC 110 V DC 125 V DC 220 V DC 110 V 115 V AC, 50/60 Hz 120 V 127 V AC, 50/60 Hz 220 V 240 V AC, 50/60 Hz 380 V AC, 50/60 Hz 24 V DC 30 V DC 48 V DC 60 V DC 110 V DC 125 V DC 220 V 250 V DC
3TY5 812-0BA0 SWB: 55536 SWB: 55535 SWB: 55534 SWB: 55539 SWB: 55533 SWB: 55537 SWB: 55538 SWB: 55468 SWB: 55467 SWB: 55463 SWB: 55537 SWB: 55538 3RT1526-1BF40 3RT1517-1BM40 3RT1517-1AP00 3TY5 692-0AG7 3TY5 692-0AL7 3TY5 692-0AN2 3TY5 692-0AN7 3TY5 692-0AQ2 3TY5 692-0AR7 3TY5 692-0AU7 3TY5 692-0BB4 3TY5 692-0BC4 3TY5 692-0BE4 3TY5 692-0BF4 3TY5 692-0BG4 3TY5 692-0BM4 3TY5 892-0AG7 3TY5 892-0AL7 3TY5 892-0AN7 3TY5 892-0AQ2 3TY5 892-0BB4 3TY5 892-0BC4 3TY5 892-0BD4 3TY5 892-0BE4 3TY5 892-0BF4 3TY5 892-0BG4 3TY5 892-0BM4 3TY5 693-0AA0 3TX5 111-0AA0 3TY5 694-2AA0 3AX1 525-1F 3AX1 526-0F 3TY5610-1AA0
For 3TL7
For 3TL6
For 3TL8
Mechanical closing lock-out Blocking element Rectifier Rectifier module Varistor module Adjustment parts
For 3TL6 For 3TL61 for mechanical interlocking of two contactors For 3TL6 For 3TL6 / 3TL7 For 3TL6 / 3TL7 To replace 3TL50 and 3TL51 contactors by 3TL60 and 3TL61
30
Equipment Selection
Accessories and spare parts
Designation
Remarks
Ratings
Order No.
Vacuum interrupter
For 3TL6 VS 7202 VS 12003 VS 12003 SP For 3TL8 Up to serial number 31 670 935 From serial number 31 670 936
3TY5 610-2AA0 3TY5 650-1AA0 3TY5 650-2AA0 3TY5 810-0AA0 3TY5 810-1AA0
To select the correct spare interrupter, please specify the type designation, serial number, design code and year of manufacture of the contactor. All data is given on the rating plate.
Vacuum interrupters and other spare parts must only be replaced by instructed personnel.
2
Note: For any query regarding spare parts, subsequent deliveries, etc. the following details are necessary: Type designation Serial No. Year of manufacture
Ur
Ie
Wiring 60/75 C
MADE IN GERMANY
31
32
R-HG11-222.tif
Technical Data
Contents
Contents
Page
Technical Data
Electrical data, dimensions and weights: Medium-voltage part Low-voltage part Short-time withstand current / load time characteristic Operating cycle diagrams Dimension drawings Auxiliary contacts Ambient conditions Circuit diagrams: 3TL6 vacuum contactor
R-HG11-223.tif
33
34 34 35 35 36 37 37
38 40 41
3TL7 vacuum contactor 3TL8 vacuum contactor Transport dimensions and weights: Types of transport Transport by truck or rail Transport by ship Transport by airfreight
Flexible conductor
42 42 43 43
R-HG11-225.tif
33
34
3TL61 ... 3TL81 3TL65 12 3TL71 24 Order No. Ur kV Rated voltage Rated continuous normal current acc. to IEC 60470 Rated normal current 1) at ambient air temperature up to + 55 C Rated normal current 1) at ambient air temperature up to + 80 C Switching capacity 2) Rated making current Switching capacity 2) Rated breaking current Limit switching capacity Rated short-time withstand current (r.m.s. value) 1 s 3) Switching of capacitors Rated normal current of capacitor Switching of capacitors Max. permissible inrush peak Cycles/h Switching rate without mechanical closing latch Mechanical endurance of the contactor Ith A Ir A
3TL61 ...
3TL65
Low-voltage part
Technical Data
Medium-voltage part
3TL81
Order No.
650
650
600
90
90
90
1) According to utilization category AC-1, AC-2, AC-3 and AC-4 2) According to utilization category AC-4 (cos j = 0.35) 3) For short-time withstand current with longer times, see short-time withstand current / load time characteristic
Siemens HG 11.21 2008 Ir A A A 7.2 450 450 315 4500 3600 400 400 315 4000 3200 4500 3600 7.2 400 400 360 4000 3200 7 5 kA 4.5 5 8 8 8 kA 8 A 250 250 200 250 kA 10
0.85 to 1.1 Ua
0.8 to 1.1 Ua
0.85 to 1.1 Ua
0.8 to 1.1 Ua
ms
300
300
100
100
ms
50 ms at 100 ms
Closing time (Interval of time between the closing command and the instant when the contacts touch for the first time)
10
ms
w 100 ms 3 mio 1 mio 1 mio Oper. cycles 1 mio 2 mio 1 mio 1 mio Oper. cycles 1 mio Oper. cycles 0.5 mio 0.5 mio 0.25 mio 0.25 mio kV 60 60 75 95 kV 40 40 60 75 kV 20 20 50 28 kV 20 20 50 28 kg 28 2NM 154 01503 30 2NM 154 01503 3M 154 80 02492 30 3M 154 02090 1 4 2 3 1 3 4 2
325 ms 75 ms or w 50 ms
Opening time (Interval of time between the opening command and the instant when the contacts start to separate)
Mechanical endurance of the vacuum interrupter Electrical endurance of the vacuum interrupter while breaking the rated normal current Rated lightning impulse withstand voltage to earthed parts and between phases Rated lightning impulse withstand voltage across the open contact gap Rated short-duration power-frequency withstand voltage to earthed parts and between phases Rated short-duration power-frequency withstand voltage across the open contact gap Weights Detailed dimension drawing no. (can be ordered) Operating cycle diagram no. (see page 35) Catalog dimension drawing no. (see page 36)
100,000
100,000
Operating cycles
100,000
60
60
Operating cycles / h
60
900
900
900
ms
< 50
< 45
< 45
Technical Data
Electrical data, dimensions and weights
5 4 3 0 1 2 3 4 5 s Load time 6
10 7
Operating cycles
10 2.5
Operating cycles
is shown as a function of the breaking current (r.m.s. value). The curve shape shows average values. The number of operating cycles that can actually be
2 1
10 6 10 5 10 4 10 3 10 2 3 4
10 5 10 4 10 3 10 2
HG11-2638_en eps
3
HG11-2639_en eps
10 1 10 0 10 1
10 1 10 0 10 1
10 4
35
Technical Data
Electrical data, dimensions and weights
Dimension drawings
7 37 37
325
2101)
288 256
391)
265 280
HG11-2640 eps
250 340
Dimension drawing 1
275 M 12
Dimension drawing 2
736 275 60
11
40
3
537 167
40
227
828
248
750 800
14.5
Dimension drawing 3
386 115 200
11
115 30
371
2171)
1301)
126
HG11-2643a_en eps
11
Dimension drawing 4
36
HG11-2642a_en eps
HG11-2641 eps
2361)
42
16
16
12
68
120
11
50
68
288 256
325
42
30 120
120
11
50
Technical Data
Electrical data, dimensions and weights
Auxiliary contacts
Rated normal current Utilization category for AC operation AC-11 at rated voltage Rated normal current Utilization category for DC operation DC-11 at rated voltage Connection cross-sections of the auxiliary contacts acc. to DIN EN 60947 Part 1
Ir A
Ir A
Ir A
Ir A
Ir A 10
Ir A
Ir A
Ir A 4
Ir A 2
Ir A 10
Ir A
Ir A
Ir A 5
Ir A 0.9
Ir A
Ir A
10
0.45 0.25
10
10
10
10
0.9
0.45 0.25
0.2
0.6 4
0.5 2.5
10
10
10
10
2.5
10
10 10
4 5
0.9
0.2
0.6 4 0.6 4
0.45 0.25
Single-wire
Order No.
110 V DC
440 V DC
125 V DC
220 V DC
600 V DC
110 V AC
125 V AC
230 V AC
220 V AC
500 V AC
600 V AC
48 V DC
24 V DC
48 V AC
60 V DC
24 V AC
60 V AC
Ambient conditions
Order No. Service life at ambient air temperature Storage at 40 C to + 65 C 20 years Operation at 5 C to + 55 C 3 mio. oper. cycles 1 mio. oper. cycles Operation at 5 C to + 65 C Operation at + 55 C to + 80 C 1 mio. oper. cycles 1 mio. oper. cycles Operation at 25 C to 5 C 0.5 mio. oper. cycles 0.25 mio. oper. cycles 0.5 mio. oper. cycles 0.5 mio. oper. cycles 1250 m below sea level to 2500 m above sea level 1250 m below sea level to 2500 m above sea level 50 m below sea level to 1250 m above sea level 200 m below sea level to 1250 m above sea level 5 x g, 10 ms or 10 x g, 5 ms 5 x g, 10 ms or 10 x g, 5 ms Site altitude Shock resistance Degree of protection acc. to IEC 60529
3TL61 ...
IP00
3TL65 ...
20 years
IP00
3TL71 ...
20 years
IP00
3TL81 ...
20 years
5 x g, 10 ms or 10 x g, 5 ms
IP00
37
Technical Data
Circuit diagrams
-K1 -X1
-R
17
2 18 A1 A2 A2 A1
-H1 71
-H2
-G -K2S
A2 A1
~ ~
+ -K2E -K2E
44 43 13 14
HG11-2701a eps
-G
~ ~
-K1E
-K1E -K1M
-K1E -X1
A2
72
43
-K2E
A2 A1 E2
84 62 54 122 114
101 93 21 13 31
AC operation
Without mechanical closing latch Opening time w 50 ms approx. 100 ms 250 ms 70 ms Rectifier Resistor for economy circuit
-K2E
S
-K2E
S
-S1Q
-K1
HG11-2702 eps
N(L2,L-)
A2
Opening time w 50 ms
N(L2,L-)
A2
L1(L+)
-K1
-S1Q
HG11-2704 eps
Legend
D F G H1 H2 K1 K1E K1M K2E K2S R S0Q S1Q X1 Free-wheeling diode Fuse Rectifier module Right-hand auxiliary contact block Left-hand auxiliary contact block Vacuum contactor Auxiliary contactor for economy circuit Magnetic drive for vacuum contactor External auxiliary contactor Latch release solenoid (optional) Economy resistor External OFF pushbutton External ON pushbutton Terminal strip for auxiliary conductor connection
N(L2,L-)
A2
N(L2,L-)
A2
L1(L+)
-K1
-S1Q
HG11-2706 eps
-D
N(L2,L-)
A2
-D
A2
The circuit diagrams shown here are examples from the manifold possibilities of contactor wiring
38
HG11-2707 eps
-K2E
-K1M
-K1M
HG11-2705 eps
-K2E
-K1M
-K1M
HG11-2703 eps
-K2E
-K1M
-K1M
Technical Data
Circuit diagrams
-K1 -X1
-R
17
2 18 A1 A2 A2 A1
-H1 71
-K2E -H2
44
44 43 13 14 A1 A2
-K2E -K2S
-K1E
72
43
-K2E
84 62 54 122 114 101 93 21 13 31
A2 A1 E2
-X1
A2
-K2E
S
DC operation
Without mechanical closing latch
-K2E
S
-K1 -R
-S1Q
-K2E
-K1M -K1E
-K1E -K1E
-R
HG11-2710 eps
-S1Q
-K1E -K1E
Opening time w 50 ms approx. 100 ms 250 ms 70 ms Varistor circuit W 60 V DC (optional) Resistor for economy circuit
HG11-2711 eps
-K2E
A2
-K1M
A2
-K1M
A2 A2
N(L2,L-)
Opening time w 50 ms
N(L2,L-)
L1(L+)
-F -S0Q -K2E
A1 A1
L1(L+) -K1 -R
HG11-2712 eps
-F -K2E
A1 A1
-K1 -R
-S1Q
-K2E
-K1M -K1E
-S1Q
-K1E -K1E
A2
N(L2,L-)
A2
A2
HG11-2713 eps
-K2E
-K1M
Legend
D F G H1 H2 K1 K1E K1M K2E K2S R S0Q S1Q X1 Free-wheeling diode Fuse Rectifier module Right-hand auxiliary contact block Left-hand auxiliary contact block Vacuum contactor Auxiliary contactor for economy circuit Magnetic drive for vacuum contactor External auxiliary contactor Latch release solenoid (optional) Economy resistor External OFF pushbutton External ON pushbutton Terminal strip for auxiliary conductor connection
L1(L+)
-F -S0Q -K2E
A1 A1
L1(L+) -K1 -R
HG11-2714 eps
-F -K2E
A1 A1
-K1 -R
HG11-2715 eps
-S1Q
-K2E
-K1M -K1E
-S1Q
-K1M -K1E
-K2E N(L2,L-)
-D
A2
-K2E
-D
A2
The circuit diagrams shown here are examples from the manifold possibilities of contactor wiring
39
Technical Data
Circuit diagrams
-K1 -X0
13
-K3E
-H
A1 A2 B1 B2
13 23 31 43 51 63 71 83 91 103
Auxiliary contact block Vacuum contactor Magnetic drive for vacuum contactor Auxiliary contactor for pick-up coil Auxiliary contactor for holding coil Rectifier module Plug for auxiliary conductor connection -X0
-K2E
3(+) 1(~)
-K1E -K1M
V4
4() 2(~)
-K3E
1
-K2E
-K1E
14 24 32 44 52 64 72 84 92 104 2 3 4 5 6 7 8 9
The circuit diagrams shown here are examples from the manifold possibilities of contactor wiring
40
HG11-2716 eps
Technical Data
Circuit diagrams
-K1 -X1
-R
17
2 18 A1 A2 A2 A1
-H1
71
-H2
-G -K2S
A2 A1
~ ~
AC operation
-K2E -K2E
44 43 13 14
HG11-2717a eps
-G
~ ~
-K1E
-K1E -K1M
Voltage range 110 V to 250 V AC, 50/60 Hz Without mechanical closing latch Opening time w 50 ms by external circuit 325 ms 75 ms Auxiliary contact block 2 NO + 2 NC or 4 NO + 4 NC (optional) With mechanical closing latch (-K2S) only with rectifier and auxiliary contact block 4 NO + 4 NC
-K1E -X1
A2
72
43
-K2E
A2 A1 E2
84 62 54
21 13 31
-K1 -X1
E1
DC operation
Voltage range 110 V to 250 V DC Without mechanical closing latch Opening time w 50 ms by external circuit 325 ms 75 ms Auxiliary contact block 2 NO + 2 NC or 4 NO + 4 NC (optional)
HG11-2718a eps
-R
17
2 18 A1 A2 A2 A1 84 62 54 21 13 31 72 43 A2 A1
-H1
-K2E
71
44 43 13 14 A1 A2
-H2
44
-K2E -K2S
-K1E
-K2E
With mechanical closing latch (-K2S) only with auxiliary contact block 4 NO + 4 NC
-X1
A2
E2
3
Momentary-contact operation -F L1(L+) -K2E
-S0Q -S1Q -K2E
A2
Maintained-contact operation
L1(L+) -F -K2E -K2E
A1 2 2
AC and DC operation
Without mechanical closing latch Opening time w 50 ms by external circuit 325 ms 75 ms
S S
-K2E -K2E
A1 2 2
-K2E
S S
-S0Q -K1
-K2E -K1
HG11-2719 eps
N (L2,L-)
A2
HG11-2720 eps
-K2E
Legend
L1(L+) -F -K2E
A1
L1(L+)
-F -K2E
A1
-S1Q -K1
-K1
HG11-2721 eps
The circuit diagrams shown here are examples from the manifold possibilities of contactor wiring
HG11-2722 eps
A2
A2
Free-wheeling diode Fuse Rectifier module Lower auxiliary contact block Upper auxiliary contact block Vacuum contactor Auxiliary contactor for economy circuit Magnetic drive for vacuum contactor External auxiliary contactor Latch release solenoid (optional) Economy resistor External OFF pushbutton External ON pushbutton Terminal strip for auxiliary conductor connection
41
Technical Data
Transport dimensions and weights
Types of transport
Packing type National Place of destination European countries Transport by truck rail n n n n n n n n Overseas / European countries Transport by airfreight n n n n n Overseas
Transport by truck rail Single packing Lot size packing Cardboard box with inside cardboard suiting the device Cardboard box with sealed packing and inside cardboard suiting the device Latticed crate with cardboard boxes and inside cardboard suiting the device Wooden crate and cardboard boxes with sealed packing and inside cardboard suiting the device n n n possible n n n
Transport by ship n n n n
not possible
Volume m3
Gross weight kg
Volume m3
Gross weight kg
Volume m3
Gross weight kg
1 2 3 4 5 8
32 62 100 130
Cardboard box with sealed packing and inside cardboard suiting the device
1 2 3 4 5 8
800/780/670 1020/620/670
0.42 0.42
45 70 105 135
Latticed crate with cardboard boxes and inside cardboard suiting the device Wooden crate and cardboard boxes with sealed packing and inside cardboard suiting the device
3 8 3 12
1200/800/800
0.77
176 333
1200/800/800
0.77
125 360
1 2 1 3 3 4 5 8 7 10
920/620/720 1020/1020/1020
0.41 1.06
42
Technical Data
Transport dimensions and weights
Transport by ship
Packing type For number of vacuum contactors 3TL6 3TL7 3TL8
Volume m3
Gross weight kg
Volume m3
Gross weight kg
Volume m3
Gross weight kg
Cardboard box with inside cardboard suiting the device Cardboard box with sealed packing and inside cardboard suiting the device
1 2 3 4 5 8
800/780/670 1020/620/670
0.42 0.42
45 70 105 135
Latticed crate with cardboard boxes and inside cardboard suiting the device Wooden crate and cardboard boxes with sealed packing and inside cardboard suiting the device
1 2 1 3 3 4 5 8 7 10
920/620/720 1020/1020/1020
0.41 1.06
Transport by airfreight
Packing type For number of vacuum contactors 3TL6 3TL7 3TL8
3
Gross weight kg 32 62 100 130
Volume m3
Gross weight kg
Volume m3
Gross weight kg
Volume m3
1 2 3 4 5 8
Cardboard box with sealed packing and inside cardboard suiting the device
1 2 3 4 5 8
800/780/670 1020/620/670
0.42 0.42
45 70 105 135
Latticed crate with cardboard boxes and inside cardboard suiting the device Wooden crate and cardboard boxes with sealed packing and inside cardboard suiting the device
1 2 1 3 3 4 5 8 7 10
920/620/720 1020/1020/1020
0.41 1.06
43
44
R-HG11-181.tif
Annex
Contents
Contents
Page
Annex
Inquiry form Configuration instructions Configuration aid
45
46 47 Foldout page
R-HG11-180.eps
45
Annex
Inquiry form
Please copy, fill in and return to your Siemens partner or you can use our prompted online configurator under www.siemens.com/energy
Inquiry concerning
Technical data
Rated voltage Rated lightning impulse withstand voltage o 7.2 kV to earth open contact gap o 12 kV o 60 kV o 40 kV o 24 kV o 75 kV o 60 kV
Other values o _ _ _ kV o 95 kV o 75 kV
Please
Rated normal current
o 50 kV o 800 A
o 60 o 600 o 1200 operating cycles / h operating cycles / h operating cycles / h o 1 mio. operating cycles o 0.25 mio. operating cycles o 0.25 mio. operating cycles o 3 mio. operating cycles o 1 mio. operating cycles o 0.5 mio. operating cycles o 2 mio. operating cycles o 1 mio. operating cycles o ___ operating cycles o ___ operating cycles o ___ operating cycles
Your address
Company Dept. Name Street Postal code/city Phone Fax E-mail
Mechanical endurance of the contactor Mechanical endurance of the interrupter Electrical endurance of the interrupter
Equipment
Auxiliary contacts o 2 NO + 2 NC o 6 NO + 5 NC o 4 NO + 3 NC o 8 NO + 7 NC o 4 NO + 4 NC o 8 NO + 8 NC o ___
Operating voltage of the magnet coil Mechanical closing latch Operating voltage of the mechanical closing latch Operating instructions in
o _ _ _ V DC
o _ _ _ V AC, _ _ _ Hz
o with
o without
o _ _ _ V DC o German o English
Siemens AG
Dept. Name Street Postal code/city Fax
_ _ _ Please fill in
46
10 11 12
13 14
Instruction for configuration of the 3TL vacuum contactor 1st step: Definition of the primary part
Please specify the following ratings: Possible options:
n n n n
n n n n n
n n
Rated voltage (Ur) Rated lightning impulse withstand voltage (Up) Rated short-duration power-frequency withstand voltage (Ud) Rated normal current (Ir) Switching rate Mechanical endurance of the contactor
Ur: 7.2 kV to 24 kV Up: 60 kV to 95 kV Ud: 20 kV to 50 kV Ir: 400 A to 800 A 60 operating cycles / h to 1200 operating cycles / h 1 mio. to 3 mio. operating cycles
L + +
+ + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + +
Number of auxiliary contacts Operating voltage of the magnet coil Operating voltage of the closing latch Operating voltage of the shunt release Site altitude
2 NO + 2 NC up to 8 NO + 8 NC Operating voltages from 24 V DC to 440 V AC Operating voltages from 24 V DC to 380 V AC Operating voltages from 24 V DC to 230 V AC 0 m to 5000 m above sea level
3rd step: Do you have any further requirements concerning the equipment? Should you still need more options than the possible special equipment like halogen-free and flame-retardant wiring, additional rating plate, seaworthy packing, etc., please contact your responsible sales partner.
3 T L
47
Published by and copyright 2008: Siemens AG Energy Sector Freyeslebenstrasse 1 91058 Erlangen, Germany Siemens AG Energy Sector Power Distribution Division Medium Voltage Nonnendammallee 104 13623 Berlin, Germany For more information, please contact our Customer Support Center. Phone: +49 180 524 70 00 Fax: +49 180 524 24 71 (Charges depending on provider) E-mail: support.energy@siemens.com Order No. E50001-K1511-A211-A3-7600 Printed in Germany Dispo 31601 KG 08.08 6.0 50 En 6101/6501 102890
Printed on elementary chlorine-free bleached paper. All rights reserved. If not stated otherwise on the individual pages of this catalog, we reserve the right to include modifications, especially regarding the stated values, dimensions and weights. Drawings are not binding. All product designations used are trademarks or product names of Siemens AG or other suppliers. If not stated otherwise, all dimensions in this catalog are given in mm. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract.
Responsible for Technical contents: Siemens AG, E D MV C Berlin General editing: Siemens AG, E CC MCC R Erlangen
R-HG11-182.tif
www.siemens.com/energy