Professional Documents
Culture Documents
03a Safety Systems
03a Safety Systems
Schlumberger 2000 Schlumberger 225 Schlumberger Drive Sugar Land, Texas 77478 All rights reserved. No part of this book may be reproduced, stored in a retrieval system, or transcribed in any form or by any means, electronic or mechanical, including photocopying and recording, without prior written permission of the publisher SMP-7086-3 An asterisk (*) is used throughout this document to denote a mark of Schlumberger.
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Riser Sealing Mandrel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SenTREE 3 Test Tree System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SenTREE 3 components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Valve assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Latch assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Retainer valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Spanner joint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Subsea Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Disconnect times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Standard system features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Deep-sea hydraulic system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Deep-sea electrohydraulic system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Drift-off analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Subsea pressure and temperature carrier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Lubricator Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-Z Valve Retrievable Well Control Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3 5 8 8 10 13 15 17 19 20 20 24 26 28 29 31 33
Safety Systems
Contents
iii
Introduction
This third book in the Schlumberger Testing Services set is divided into two sections. The first describes well control equipment for offshore and land testing operations. The second section describes well test design, safety considerations and the features and selection of surface equipment. Regardless of the downhole conditions and well location, Schlumberger equipment and techniques meet the critical need for reliable well control. When drilling operations are conducted from a floating vessel (a semisubmersible or drillship), the stack of subsea pressure-control equipment typically has the following arrangement: s one or two annular blowout preventers (BOPs) at the top of the stack s one or two BOPs equipped with blind/shear rams s two or three BOPs equipped with pipe rams to close on drillpipe or test strings. The riser, which brings the mud back to the surface, is landed on top of the BOP stack with a hydraulic connector that allows disconnection (Fig. 1). The BOPs and the hydraulic connector are controlled hydraulically from the surface through hoses running in bundles outside the riser. During testing, the drillstring running through the BOP stack well is full of oil or gas. If it becomes necessary to cut pipe and pull the drilling vessel off location, the well is held in control only by the blind/shear rams, which may be damaged from cutting the pipe. In this scenario, reentry is impossible because of pressure below these rams. To avoid this set of circumstances, a subsea test tree is inserted into the test string. A subsea test tree system was originally developed to enable well testing operations from an offshore floating rig. The subsea test tree contains valves and a latch that allow fast disconnection of the vessel from the BOP stacks when there is rough weather, dragging or loss of anchor, or failure or malfunction of a dynamic positioning system. The subsea test tree system is the primary safety device and provides fast-acting and reliable means to s isolate the landing string from the test string s prevent discharge of its contents into the riser s disconnect the landing string from the test string. 1 2. 3. 4. 5. 6. The disconnection sequence is as follows: Close the valves in the subsea test tree. Close the retainer valve and bleed off the pressure between the valves. Unlatch from the subsea tree valve assembly. Pull the subsea tree latch and the string above it clear of the BOP stack. Close the BOP blind rams. Disconnect the riser. The vessel can then move off location, leaving the well under control.
Safety Systems
Introduction
Riser
Figure 1. BOP stack with riser connected (left) and disconnected (right).
Schlumberger developed the riser sealing mandrel (RSM) (Fig. 2 and Table 1) as an additional safety device to meet the requirements of Hazard and Operability (HAZOP) studies during deepwater well testing operations. With the increase in water depth, a gas or hydrocarbon leak in the landing string close to the subsea test tree (i.e., leak from inside tubing to the riser) can develop a high-volume gas kick at the surface. To safely control and divert this volume, the RSM is located at the level of the diverter BOP below the rig floor, and the diverter BOP is closed on it. All the umbilical hoses are well protected, and the seal around them is ensured with specially designed rubber hose sealing elements.
Features
s s
The 9.5-in. OD and the modular design enable using the RSM with most BOP sizes and configurations. The rig-up time is shortened with easy-to-install protective plates and specially designed rig-up tools. The protective capacity (26 hose-sealing elements) allows it to be used with various umbilical hoses: 5 hoses 6 hoses 1 2 in. 1 112 in. 2 114 in. 2 114 in. 2 38 in. 1 1 in. 2 38 in.
Safety Systems
Umbilical
Hose-sealing elements
9.5 in.
Protective plates
Johnston-Schlumberger was the pioneer in subsea systems with the introduction of the E-Z Tree* retrievable well control system in 1975. In the mid-1990s, Schlumberger launched a project to redesign the subsea test tree system to meet the latest industry requirements: s ability to close the shear rams with the latch in place s latest study requirements (HAZOP) for deep-sea operations incorporated s ability to close two BOP pipe rams around the slick joint s ability to close two shear rams. Following a very successful field test period, the SenTREE* 3 system (EZTM) was commercialized at the end of 1997. The SenTREE 3 test tree (Fig. 3) is hydraulically controlled from the surface and consists of a dual fail-safe ball valve and flapper valve and a connector (latch) that is landed in the BOP stack. Its modularity (Fig. 4) enables placement of the slick joint either below the valve assembly or between the latch and valve assembly to match even very short BOP stack configurations. A set of unique features (verified and approved by Det Norske Veritas) makes the SenTREE 3 system the preferred tree for all standard tests and the first choice for deep-sea and highpressure, high-temperature (HPHT) operations.
Features
s
Reduced length and modularity 46-in. standard configuration 16- and 32-in. split configuration HPHT tested and qualified to full pressure and temperature range Ability to unlatch at full tension, with an angle of up to 6 Backup mechanical unlatch (5 turns) Latch fishing profile and dedicated fishing tool Chemical injection below or at valve level
s s s s s
With the standard control section, the SenTREE 3 tree is operated through an umbilical hose that consists of three hydraulic control lines. At the surface, the hose is connected to an airdriven hydraulic power unit (control console). The specially designed deep-sea control systems available are described subsequently in this section. When a chemical injection hose or a four-line umbilical hose is run, the SenTREE 3 system allows injection of chemicals (such as hydrate or corrosion inhibitors) either above or below the ball valve.
Safety Systems
Riser
Retainer valve Bleed-off valve Shear rams Shear sub Latch assembly Blind rams Valve assembly
Pipe rams
BOP stack
Riser
Shear sub
Shear rams Latch assembly Pipe rams Slick joint Pipe rams
Valve assembly
BOP stack
Safety Systems
SenTREE 3 components
The SenTREE 3 test tree system includes the following components: s valve assembly (EZTV) s latch assembly (EZTH) s retainer valve (RETV) s spanner joint.
Valve assembly
The SenTREE 3 valve assembly (EZTV) (Fig. 5 and Table 2) consists of two hydraulically operated fail-safe valves. The main valve is a ball type; the second is a flapper valve. This combination has proved to be the most reliable fullbore subsea system. Sequential valve closure ensures that the flapper valve closes only after the ball valve is closed. The delay allows wireline or coiled tubing (CT) to clear the flapper after being cut by the lower ball assembly. The pump-through facility of the valve assembly permits well control if hydraulic control is lost. Positive differential pressure applied from above opens a flow area for well kill operations that is equivalent to a 114-in. line.
Table 2. SenTREE 3 Valve Assembly Specifications
Unit Service Working pressure Design temperature OD ID Test pressure (body only, valves open) Max tensile load at 90% yield and 350F [177C] Injection line working pressure Bottom connection Wireline cutting capability CT cutting capability Max torque Length Weight with centralizer
13-in.
psi [bar] F [C] in. [mm] With centralizer in. [mm] psi [bar] lbf at 0 psi [kN at 0 bar] lbf at 15,000 psi [kN at 1035 bar] psi [bar]
15,000 [1035] 4 to 350 [20 to 177] 13.0 [330] 16.1 [409] 3.0 [76] 22,500 [1550] 520,000 [2310] 255,000 [1130] 15,000 [1035] 5-in. 4 S.A. box Up to 516 in. (no assistance required) [Up to 7.9 mm (no assistance required)] Up to 112 in. 0.156 in. (hydraulic assistance 5000 psi) [Up to 38 mm 3.9 mm (hydraulic assistance 345 bar)]
OD for the bottom nut only (height 4.1 in.); SenTREE 3 body OD is 12.5 in.
Flapper
Safety Systems
Latch assembly
The latch assembly (EZTH) (Fig. 6 and Table 3) is the upper part of the subsea tree and connects the landing string to the valve assembly. If hydraulic control is lost, the latch can be disconnected mechanically. Two shear keys, which break at a known torque value, connect the latch body to the shear sub. Figure 7 shows the combined latch and valve assemblies of the SenTREE 3 test tree system.
Table 3. SenTREE 3 Latch Assembly Specifications
Unit Service Working pressure Design temperature OD ID Test pressure Max tensile load at 90% yield and 350F Top connection Max torque Length Weight with centralizer ft-lbf [Nm] in. [mm] lbm [kg] psi [bar] F [C] in. [mm] With centralizer in. [mm] psi [bar] lbf at 0 psi [kN at 0 bar] lbf at 15,000 psi [kN at 1035 bar] EZTH-DA H2S per NACE MR-01-75 15,000 [1035] 4 to 350 [20 to 177] 12.5 [318] 16.1 [409] 3.0 [76] 22,500 [1550] 520,000 [2310] 255,000 [1130] 5-in. 4 S.A. pin 7500 [10,200] 16.0 [406] 860 [390]
10
Piston
Latch dog
Skirt
Safety Systems
11
Latch assembly
Latch dog
Latch profile
Valve assembly
12
Retainer valve
The retainer valve (RETV) (Fig. 8 and Table 4) can be run above the SenTREE 3 latch assembly to retain the fluids trapped in the landing string after disconnecting from the SenTREE 3 valve assembly. When disconnecting, the retainer valve prevents the uncontrolled release of hydrocarbons from the landing string into the riser and the sea. When testing wells in deep water or when testing high-pressure gas wells, use of the retainer valve is a safety and environmental requirement. The RETV is controlled hydraulically in sequence with the subsea test tree. An integral bleedoff valve (BOV) vents the trapped pressure between the retainer valve and the test tree to the riser before unlatching. The RETV uses the same ball valve mechanism as the SenTREE 3 system and is capable of cutting 1.5-in. CT. Hydrocarbons in the landing string can be reversed out as the RETV ball valve is pumped away from its seat with greater pressure below the valve. The RETV is a fail-safe valve when closed, but in case of control line failure, the RETV ball valve can be opened by closing the annular BOP on the spanner joint and pressuring up below.
Features
s s s s s s s
Fail-safe closure Ability to cut 1.5-in. 0.15-in. CT with pressure assist Integrated bleed-off valve Pump-through facility with the spanner joint Pressure tests from above Reverse circulation (U-tube) Ports for high-rate injection
Safety Systems
13
Ball cage
Piston
Sequencing valve
BOV Open
BOV Closed
14
Spanner joint
The spanner joint (Fig. 9 and Table 5) sits on top of the retainer valve and allows closing the annular BOP. This safety feature was introduced in 1997. The spanner joint was developed to fulfill the following functions: s enable closure of the annular BOP on the landing string to pressurize the annulus to open the ball valve if hydraulic controls are lost s enable, through the hydraulic block manifold, the operating sequence of the SenTREE 3 system and the RETV valves s protect the control hoses when closing the BOP.
Table 5. Spanner Joint Specifications
Unit Service Working pressure Design temperature OD ID Test pressure Max tensile load at 90% yield and 350F Connection Max torque Sealing length ft-lbf [Nm] ft [m] psi [bar] F [C] in. [mm] in. [mm] psi [bar] lbf at 0 psi [kN at 0 bar] lbf at 15,000 psi [kN at 1035 bar] Spanner Joint H2S per NACE MR-01-75 15,000 [1035] 4 to 350F [20 to 177] 10.75 [273] 3.0 [76] 22,500 [1550] 520,000 [2310] 255,000 [1130] 5-in. 4 S.A. box with lock key 15,000 [20,300] 5 or 10 [1.5 or 3.0]
Safety Systems
15
Skirt
Hydraulic hose
Centralizer
Retainer valve
16
Accessories
Figure 10 shows the SenTREE 3 components in both a short configuration and a standard configuration. The spanner joints, retainer valve and shear sub extensions are required in both configurations.
Crossover
Safety Systems
17
The type of subsea control system used to operate the subsea test tree depends on the water depth. Schlumberger has developed three systems (Fig. 11) to accommodate different depths and optimize the disconnect time of the latch assembly: s standard system for depths to 1500 ft [457 m] s deep-sea hydraulic system for depths from 1500 to 4500 ft [457 to 1372 m] s electrohydraulic system for depths from 4,500 to 10,000 ft [1372 to 3048 m].
1500 ft
Always use with dynamically positioned vessels Figure 11. SenTREE 3 control systems.
Safety Systems
19
Disconnect times
The disconnect time for any hydraulic system depends on the landing string configuration, on whether a retainer valve is used and on the umbilical hose length. The downhole hydraulic pod system with surface accumulator was tested and qualified both onshore and offshore. Using the SenTREE 3 system and RETV, the complete cycle (close, bleedoff and disconnect) times are 41 s at 4400 ft [1341 m] and 52 s at 7400 ft [2255 m]. The electrohydraulic pod with 8500 ft [2591 m] of umbilical hose was also tested and qualified both onshore and offshore. Using the SenTREE 3 system and RETV, the complete cycle (close, bleed-off and disconnect) time is 10 s at water depths to 8500 ft.
20
Console
Reel
Spanner joint
Retainer
SenTREE 3 system
1500 ft
Safety Systems
21
CI
A B
Unlatch Latch
Latch
Unlatch
Latch connector
Figure 13. Hydraulic logic diagram for standard control system used with SenTREE 3 system.
22
CI A B C HF CI
Open Close
Close
Open
Unlatch Latch
Figure 14. Hydraulic logic diagram for standard control system used with SenTREE 3 system with retainer valve.
Safety Systems
23
24
Console
Hydraulic pod
Spanner joint
Retainer
SenTREE 3 system
4500 ft
Safety Systems
25
26
Spanner joint
Retainer
SenTREE 3 system
10,000 ft
Safety Systems
27
Drift-off analysis
Drift-off analysis defines the disconnect philosophy and establishes the times required for disconnection of stack components in the subsea test tree. As an example, consider a drift-off analysis for North Sea conditions, where a complete disconnect is required in 37 s or less, including pull-off from the BOP stack. This leaves 20 s for the complete sequence. Of the three control systems, only the electrohydraulic system is capable of making these disconnect times. In the analysis in Fig. 17, the subsea test tree must close, disconnect and clear the riser connector before the emergency disconnect sequence (ESD) procedure can begin.
Storm environment: 1-knot current, 55-knot wind
Start emergency disconnect Riser disconnect 37-s SenTREE disconnect 20 40 60 80 25-s disconnect 100
28
Safety Systems
29
Jumper cable
SRO module
UNIGAGE H-Sapphire
30
Lubricator Valve
During offshore testing where slickline, wireline or CT operations are performed, it may be advantageous to use a valve that limits lubricator height above the flowhead. The lubricator valve (LUBV), usually located about 90 ft below the flowhead, enables the upper part of the string to be used as a lubricator. The LUBV is a balanced system and remains in the position in which it was last placed (open or closed) (Fig. 19). If the valve is closed, however, application of 1800-psi differential pressure from above allows pump-through to kill the well. The LUBV can be pressure tested from above (with hydraulic pressure maintained in the closed line); the valve contains an equalizing device to remove any differential prior to opening. The LUBV can be used alone or as a backup for a conventional lubricator system. It is a surfaceoperated hydraulic valve that is run on tubing or drillpipe during testing operations (Table 10). It is normally run in conjunction with the SenTREE 3 system and its retainer valve or with an E-Z Valve* device. The LUBV can be actuated as many times as required for wireline operations. Conversely, the SenTREE 3 or E-Z Valve products are safety devices and should be actuated only in emergencies.
Table 10. Lubricator Valve Specifications
Unit Service Working pressure Working temperature Fail-safe Pump-through differential Max tensile load Shearing wireline capability Shearing CT capability Connection (box/box) Length OD ID Weight ft [m] in. [mm] in. [mm] lbm [kg] psi [bar] lbf at 0 psi [kN at 0 bar] lbf at 15,000 psi [kN at 1035 bar] psi [bar] F [C] LUBV-CC H2S 15,000 [1035] 4 to 350 [20 to 175] Closed 1800 [125] 520,000 [2310] 255,000 [1130] Up to 1532-in. [11.9 mm] 114-in. 1532 in. wall [32-mm 11.9-mm wall] 5-in. 4 S.A. 5.0 [1.5] 8.25 [210] 3.0 [76] 700 [320] 5-in. 4 S.A. 5.0 [1.5] 8.25 [210] 3.0 [76] 700 [320] LUBV-CCB H2S 10,000 [690] 4 to 350 [20 to 175] Closed 1800 [125] 520,000 [2310] 255,000 [1130]
Safety Systems
Lubricator Valve
31
Hydraulic fluid
Ball valve
Injection point
Bottom plug Valve Open Figure 19. Lubricator valve. Valve Closed Injection Line
32
The E-Z Valve (EZV) retrievable well control safety device is designed for installation in the BOP stack of a jackup or land rig during well testing when there is no unlatch facility (Table 11). The pipe rams close around a slick joint above the valve, protecting the annulus, while the E-Z Valve ball closes to secure the well at BOP level. The E-Z Valve device is normally closed by a spring and nitrogen pressure and is opened by hydraulic pressure applied from a console on the rig floor (Fig. 20). The valve is designed primarily to hold pressure from below, but it can be pressure tested from above to 5000 psi with normal hose and console or to 7500 psi with a high-pressure set. A hydrate inhibitor such as glycol or methanol can be injected below the valve. E-Z Valve closure can also be assisted by hydraulic pressure, enabling the ball to cut wireline or 114-in. CT in an emergency. Standard and two optional installations are shown in Fig. 21.
Table 11. E-Z Valve Specifications
Unit Service Working pressure Working temperature Fail-safe Shearing wireline capability Shearing CT capability Pump-through differential N2 precharge Connection (box/box) Body length Valve only length Slick joint length E-Z Valve system length OD ID Slick joint and valve weight Adjustable hanger kit weight ft [m] ft [m] ft [m] ft [m] in. [mm] in. [mm] lbm [kg] lbm [kg] psi [bar] psi [bar] psi [bar] F [C] EZV-CC H2S 15,000 [1035] 4 to 350 [20 to 175] Closed Up to 1532 in. [11.9 mm] Up to 114 in. [32 mm] 1800 [125] 1200 [83] 5-in. 4 S.A. 3.8 [1.1] 5.0 [1.5] 5.7 [1.7] 16. [5.1] 8.25 [210] 3.0 [76] 1230 [560] 1500 [680]
Safety Systems
33
Slick joint
Bottom plug Valve Open Figure 20. E-Z Valve operation. Valve Closed Valve Closed with Assistance Injection Line
34
E-Z Valve
Option 1
Safety Systems
35