Conclusion: This calculation is prepared for calculating required flow and pressure for the additional racks located

@ Hub Area. The piping for sprinklers in additional racks is connected by utilizing the existing flanged wet riser header. Anyhow, calculation shall be prepared from tapping point of existing main hydrant pipe monitored by Alarm Check Valve (AVH-6) to most remote and demanding area, which is sprinklers in additional racks, as a reason, remote location in piping arrangement has changed from existing rack area to additional rack area. Based on the above criteria, we prepared hydraulic calculation for remotest in-rack sprinklers only (Our Scope of Work) and the result shows 1234.31 LPM @ 3.92 BAR, which is less than existing pump flow & pressure. Existing pump flow and pressure _______________________________ Accordingly, we hereby confirm the existing pump flow and pressure is adequate to support additional rack sprinklers (Our Scope of Work) located in HUB area.