You are on page 1of 11

Seminar for PETROVIETNAM 18th to 19th September 2012

Seminar on Depressurization and Safety of Process Plants


Segment Survivability Analysis
Case study
Dr. Geir Berge
Petrell as Olav Tryggvasonsgt. 40 Trondheim Norway

Case study
Segment is consisting of: 1 vessel and 5 pipes

Data for vessel

Vessel
23-VG02A

Orientation OD Horizontal mm 3338

WT mm
60

Length UTS mm Material MPa


6437 CS 360 LT 545

LL mm
1000

WL mm
0

Data for pipes

Pipe name 6-PS-23-062-CS71 16-PR-23-101-CS71 6-PR-23-154-CS71 12-PS-23-051-CS71 BlowdownLine

OD WT Length UTS mm mm mm Material MPa Phase 168,3 7,11 8846 CS_235LT 420 Gass 406,4 12,7 2107 Duplex_22Cr 730 Gass 168,3 7,11 1953 CS_360LT 545 Liquid 323,8 9,53 25589 SS_6Mo 620 Liquid 219,3 3,76 5000 CS_360LT 545 Gass

MT CA Insulation layer Peak heat load Backgrond heat load % mm 1st layer mm 2nd layer mm Mantel mm kW/m2 kW/m2 12,5 0 Foamglas 20 Carbowool 50 SS 0,7 350 100 12,5 3 350 100 12,5 3 350 100 12,5 0 350 100 12,5 0 350 100

Operational conditions
Inventory conditions
Temperature 47 C Pressure 38 bar g

Fluid composition
C1 C2 C3 H2O C4 IC4 C10 C8 C5 IC5 C6 0.75868 0.100594 0.0577988 0.05 0.015507 0.00523613 0.00352432 0.00342362 0.00241668 0.00231598 0.000503474

Outside exposure
Outside conditions
Temperature 10 C Outside emissivity 0,85 Back pressure 0 bar g

Heat load
Peak heat load 350 kW/m2 Background heat load 100 kW/m2

BDV Orifice 33,44 mm

Valves

Contraction factor 0,84 Location 1 0 Open delay 1 min

PSV
type: trapezium characteristic

Equivalent opening 54 mm
Contraction factor 0,84 Location 1 0 Set pressure (opening) 42 bar g Full open pressure 44 bar g Reset pressure 30 bar g

Type of PSV

Petrell as Olav Tryggvasonsgt. 40 NO-7011 Trondheim Phone: (+47) 73 80 55 00 Fax: (+47) 73 80 55 01 E-mail: petrell.petrell.no www.petrell.no www.vessfire.com

Petrell AS Olav Tryggvasons gate 40 NO-7011 Trondheim Norway Phone: (+47) 73805500 Fax: (+47) 73805501 post@petrell.no www.petrell.no

You might also like