Sepam Merlin Gerin

Series 20
Series 40
Electrical network protection
Catalogue
2003
07897411FR - REV. A0 - 1 Schneider Electric
YFJYVIIVGIT
1
Contents
Presentation 2
More solutions 2
Flexible architecture 5
User-machine interface 6
Selection table 8
Sepam series 20 8
Sepam series 40 9
Metering 10
Description 10
General settings and characteristics 11
Protection 12
Description 12
Setting ranges 14
Connection diagrams 16
Sepam series 20 16
Sepam series 40 17
Phase current inputs 18
Residual current input 19
Sepam series 20 voltage inputs 20
Sepam series 40 voltage inputs 21
Control and monitoring 22
Description 22
Logic inputs and outputs 23
Logic input / output assignment for Sepam series 20 applications 24
Logic input / output assignment for Sepam series 40 applications 25
Annunciation 26
Customization 27
Communication 28
Description and characteristics 28
Optional remote modules 30
Description 30
Connections 31
Sensors 32
LPCT type current sensors 32
Core balance CTs 33
Characteristics 34
Size and weight 34
Electrical characteristics 36
Environmental characteristics 37
Order form
2
Presentation
More solutions

The Sepam series 20 and Sepam series
40 families of protection and metering units
are designed for the operation of machines
and electrical distribution networks of
industrial installations and utility substations
for all levels of voltage.
They consist of complete, simple and
reliable solutions, suited to the following
applications:
b protection of substations (incomers and
feeders)
b protection of transformers
b protection of motors
b protection of generators
b protection of busbars.
Sepam series 20
Suitable for common applications, Sepam series 20 offers simple solutions
based on current or voltage metering.
b protection of substation incomers and feeders against phase-to-phase and
phase-to-earth short-circuits
v 16 IDMT tripping curves
v adjustable timer hold to detect recurrent faults
v switching of groups of settings to adapt to changes in the network configuration
b protection of overhead lines with built-in recloser function
b protection of transformers against overloads, with ambient temperature-
compensated RMS thermal overload protection with 2 groups of settings for different
ventilation operating rates
b protection of motors
v against overloads, with ambient temperature-compensated RMS thermal overload
protection with a cold tripping curve that can be adjusted to fit motor characteristics
v against internal faults and load-related faults
v with motor starting condition monitoring and machine operation assistance.
The Sepam series 20 B21 and B22 voltage units are suitable for the following
situations:
b monitoring of network voltage and frequency
b loss of mains detection by rate of change of frequency protection for installations
with local power generation.
Sepam series 40
M
T
1
1
0
1
7
Sepam series 40, with its current and voltage metering capabilities, offers high-
performing solutions for more demanding applications.
Sepam series 40 units perform the following funcitons in addition to those performed
by Sepam series 20:
b protection of closed ring networks or networks with parallel incomers, by
directional protection
b directional earth fault protection suitable for all earthing systems: impedant,
isolated or compensated neutral
b protection of networks with variable configurations requiring the switching of
groups of settings and logic discrimination
b all the necessary electrical measurements: phase and residual currents, phase-to-
neutral, phase-to-phase and residual voltage, frequency, power and energy, ...
b comprehensive network diagnosis assistance: 20 seconds of disturbance
recording, detailed history of the last 200 alarms, storage of the last 5 tripping
contexts
b adaptation of control functions by a logical equation editor
b customization of alarm messages to fit each application, and/or in the users
language.
M
T
1
1
0
1
7
Sepam selection guide
Selection Series 20 Series 40
criteria
Measurements I U U I and U I and U I and U
Specific
protection
functions
available
Loss of
mains
(ROCOF)
Directional
earth fault
Directional
earth fault and
phase
overcurrent
Applications Type
Substation S20 S40 S41 S42
Transformer T20 T40 T42
Motor M20 M41
Generator G40
Busbar B21 B22
Example: For motor protection and current and voltage measurements, your solution
is the M41 type Sepam.
3
Presentation
More solutions
M
T
1
1
0
2
6
More simplicity
Simple to install
b no constraints for integration in cubicles due to the compact size of the base units
and remote installation of optional modules
b universal auxiliary power supply.
Simple to commission
b all the functions are ready to use
b user-friendly, powerful PC setting software to utilize all the possibilities offered by
Sepam.
Simple to operate
With the advanced UMI, all local operations are made easier by a clear, complete
presentation of all the required information in your language.
Simple to maintain
b digital unit self-diagnosis and watchdog
b switchgear diagnosis assistance functions to assess equipment condition and
schedule preventive maintenance operations:
v cumulative breaking current
v breaking device operating and charging time.
Example: Advanced UMI customized for Chinese users.
M
T
1
1
0
2
7
Example: Standard advanced UMI in English.
M
T
1
1
0
1
9
More communication
Modbus communication
All the data needed for centralized management of your electrical network are
available with the communication option based on the open, international Modbus
protocol:
b measurement and diagnosis values
b remote indication and time-tagging of events
b remote control of the installation
b remote setting of protection functions
b reading of disturbance recording files.
Ethernet connection and Webserver
Sepam may be connected to an Ethernet high speed network by means of a
Modbus-RS 485/Modbus - Ethernet TCP/IP communication interface.
This interface allows:
b integration of Sepam in a multi-master architecture on Ethernet networks
b consultation of Web pages of data transmitted by Sepam via an Internet/Intranet
browser.
Other protocols
Sepam may be connected to communication network based on protocols other than
Modbus by using a gateway / protocol converter.
In particular, a Modbus / DNP3 converter has been qualified for the connection of
Sepam to DNP3 network.
Please consult us for more informations.
PowerLogic System
Sepam fits naturally into PowerLogic System power management systems.
Supervision of an electrical network equipped with Sepam by
means of PowerLogic System SMS software.
P
E
5
0
0
2
7
P
E
5
0
0
2
8
EGX200 Ethernet gateway.
4
Presentation
More solutions

More modularity
Sepam series 20 and Sepam series 40 are available with 2 User-Machine
Interface (UMI) levels:
b advanced UMI, with keypad and graphic LCD display
v to provide all the data required for local operation of the installation:
measurements, diagnosis information, alarms, etc.
v to set Sepam parameters and protection functions
v to be understood by all, the screens can be displayed in the users language.
The advanced UMI may be part of the base unit or installed as a remote unit in the
most convenient location for the user.
b basic UMI, with signal lamps
v for remotely operated installations, via the communication link, with no continuous
need for local operation; a PC equipped with the SFT2841 software tool may be used
for occasional operation.
In order to adapt to as many situations as possible and allow for subsequent
upgrading of the installation, Sepam may be functionally enhanced at any time
by the addition of optional modules.
b logic input/output module with parameterizable program logic
b communication module
b temperature sensor module
b analog output module.
M
T
1
0
9
9
5
M
T
1
0
9
9
7
Sepam with basic UMI. Sepam with advanced UMI.
M
T
1
0
9
9
6
Sepam with remote advanced UMI.
5
Presentation
Flexible architecture
P
E
5
0
1
2
1
1 Base unit, with different User-Machine Interface (UMI) levels:
b basic UMI
b advanced UMI with fixed or remote graphic LCD display.
2 Logic inputs/outputs module.
3 Modbus communication network connection module.
4 Low level analog output module.
5 Temperature sensor acquisition module for transformer, motor or
generator.
6 Software tools:
b Sepam parameter and protection setting and program logic customization
b display of disturbance recording files.
6
Presentation
User-machine interface

Sepam has 2 levels of UMI (user-machine
interface) suited to every operating
requirement.
Basic UMI
This UMI offers an economical solution suited to installations that do not require local
operation (managed by a remote monitoring and control system)
or to replace electromechanical or analog electronic protections units with no
additional operating needs.
The basic UMI includes:
b 2 signal lamps indicating Sepam operating status:
v green "on" indicator: device on
v red "wrench" indicator: device unavailable (initialization phase or detection of an
internal failure)
b 9 parameterizable yellow signal lamps equipped with a standard label
(1)
b "reset" button for clearing faults and resetting
b 1 connection port for the RS 232 link with the PC; the port is protected by a sliding
cover.
M
T
1
0
1
2
2
Basic UMI with standard signal lamp assignment.
Advanced UMI
D
E
5
0
5
9
5
This UMI is an optimal solution for local operation, which is made easier by its
legibility, content and access to the different data.
In addition to the basic UMI functions, this version provides:
b a "graphic" LCD display with automatic contrast adjustment and user-triggered
backlighting. It is used to display measurements, parameter/protection settings and
alarm and operating messages.
Number of lines, size of characters and symbols according to screens and language
versions.
b a 9-key keypad with two operating modes:
White keys for current operation:
display of measurements.
display of switchgear and network diagnosis data.
display of alarm messages.
resetting.
acknowledgment and clearing of alarms.
Blue keys for parameter and protection setting:
access to protection settings.
access to Sepam parameter settings
(2)
.
used to enter the 2 passwords required to change protection and parameter
settings.
The " , r, " keys ( , , ) are used to navigate in the menus, and to scroll
and accept the values displayed.
"Lamp test" key :
switching-on sequence of all the signal lamps.
Remote advanced UMI
The advanced UMI functions are also available in a remote module that is connected
to a Sepam with a basic UMI (connection by prefabricated cord of different lengths).
The module is installed on the front panel of the cubicle in the most appropriate
operating location.
(1) This removable label may be replaced by a customized label produced using the SFT2841
software tool.
(2) For parameter setting of the program logic, the expert UMI must be used.
Advanced UMI with standard signal lamp assignment.
0 off I on Trip ext I>>51 I>51 on Io>>51N Io>51N
reset
1
2
3
4 5 6 7 8 9
reset
I on ext Io>>51N Io>51N I>>51 I>51 on 0 off
clear
trip
I1 = 162A RMS
I2 = 161A RMS
I3 = 163A RMS
1
2
3
4
5
7
8
9
r
4 5 6
6
7
Presentation
User-machine interface

M
T
1
1
1
0
2
Expert UMI
This UMI is available as a complement to the basic or advanced UMI on the screen
of a PC equipped with the SFT2841 software tool and connected to the RS 232 link
on the front panel of the Sepam (operating in a Windows environment).
All the data used for the same task are grouped together in the same screen to
facilitate operation. Menus and icons are used for fast, direct access to the required
information.
Current operating mode
This UMI is the solution suited to occasional local operation for demanding personnel
who require fast access to all the information.
b display of all metering and operating data
b display of alarm messages with the time of appearance
b display of diagnosis data such as:
v tripping current
v number of switchgear operations and cumulative breaking current
b display of all protection and parameter settings made
b display of the logic status of inputs, outputs and signal lamps.
Parameter / protection setting mode

Used for the display and setting of all the parameters; input data may be prepared
ahead of time and transferred into the corresponding Sepam units in a single
operation (downloading function).
Main functions performed by SFT2841:
b changing of passwords
b entry of general settings (ratings, integration period, ) protected by a parameter
setting password
b entry of protection settings in the same page, protected by a setting password
b modification of program logic assignments
b enabling/disabling of functions
b saving of files.
Saving - printing of reports
b protection and parameter setting data may be saved
b reports may also be printed, by exporting the data into a text file.
This UMI may also be used to recover disturbance recording files and display them
using the SFT2826 software tool.
Operating assistance
Access from all the screens to a help section which contains all the technical data
required for Sepam installation and use.
SFT2841 kit
The expert UMI software tool comes in a kit which contains:
b 1 CD-ROM with:
v SFT2841 software
v SFT2826 software for disturbance recording file display
b 1 PC/Sepam serial link cord.
Minimum configuration required
SFT2841: measurement screen.
M
T
1
1
1
0
3
SFT2841: protection function 50/51 setting screen.
Processor PC compatible, Pentium 133 MHz
Operating systems Microsoft Windows 95/98/NT4.0/2000/XP
RAM 64 MB (32 MB for Windows 95/98)
Space on disk 64 MB
8
Selection table
Sepam series 20
Functions Type of Sepam
Substation Transformer Motor Busbar
Protection ANSI code S20 T20 M20 B21
(3)
B22
Phase overcurrent 50/51 4 4 4
Earth fault,
sensitive earth fault
50N/51N
50G/51G
4 4 4
Negative sequence / unbalance 46 1 1 1
Thermal overload 49RMS 2 2
Phase undercurrent 37 1
Locked rotor, excessive starting time 48/51LR/14 1
Starts per hour 66 1
Positive sequence undervoltage 27D/47 2 2
Remanent undervoltage 27R 1 1
Phase-to-phase undervoltage 27 2 2
Phase-to-neutral undervoltage 27S 1 1
Phase-to-phase overvoltage 59 2 2
Neutral voltage displacement 59N 2 2
Overfrequency 81H 1 1
Underfrequency 81L 2 2
Rate of change of frequency 81R 1
Recloser (4 cycles) 79 v
Thermostat / Buchholz 26/63 v
Temperature monitoring (8 RTDs, 2 set points per RTD) 38/49T v v
Metering
Phase current I1, I2, I3 RMS, residual current I0 b b b
Average current I1, I2, I3, peak demand current IM1, IM2, IM3 b b b
Voltage U21, U32, U13, V1, V2, V3, residual voltage V0 b b
Positive sequence voltage Vd / rotation direction b b
Frequency b b
Temperature v v
Network and machine diagnosis
Tripping current TripI1, TripI2, TripI3, TripI0 b b b
Unbalance ratio / negative sequence current Ii b b b
Disturbance recording b b b b b
Thermal capacity used b b
Remaining operating time before overload tripping b b
Waiting time after overload tripping b b
Running hours counter / operating time b b
Starting current and time b
Start inhibit time delay, number of starts before inhibition b
Switchgear diagnosis
Cumulative breaking current b b b
Trip circuit supervision v v v v v
Number of operations, operating time, charging time v v v
Control and monitoring ANSI code
Circuit breaker / contactor control
(1)
94/69 v v v v v
Latching / acknowledgment 86 b b b b b
Logic discrimination 68 v v v
Switching of groups of settings b
(2)
b
(2)
b
(2)
Additional modules
8 temperature sensor inputs - MET148-2 module v v
1 low level analog output - MSA141 module v v v v v
Logic inputs/outputs - MES114/MES114E/MES114F (10I/4O) module v v v v v
Communication interface - ACE949-2 (2-wire RS 485),
ACE959 (4-wire RS 485) or ACE 937 (fiber optic)
v v v v v
b standard, v according to parameter setting an MES114/MES114E/MES114F or MET148-2 input/output module options.
(1) For shunt trip unit or undervoltage trip unit.
(2) Exclusive choice between logic discrimination and switching from one 2-relay group of settings to another 2-relay group.
(3) Performs B20 type functions.
9
Selection table
Sepam series 40
Functions Type of Sepam
Substation Transformer Motor Generator
Protection ANSI code S40 S41 S42

T40

T42

M41

G40
Phase overcurrent 50/51 4 4 4 4 4 4 4
Voltage-restrained phase overcurrent 50V/51V 1
Earth fault,
sensitive earth fault
50N/51N
50G/51G
4 4 4 4 4 4 4
Breaker failure 50BF 1

1 1 1 1 1 1
Negative sequence / unbalance 46 2 2 2 2 2 2 2
Directional phase overcurrent 67 2 2
Directional earth fault 67N/67NC 2 2 2 2
Directional active overpower 32P 1

1 1 1
Directional reactive overpower 32Q/40 1 1
Thermal overload 49RMS 2 2 2 2
Phase undercurrent 37 1
Excessive starting time, locked rotor 48/51LR/14 1
Starts per hour 66 1
Positive sequence undervoltage 27D 2
Remanent undervoltage 27R 1
Undervoltage
(3)
27/27S 2 2 2 2 2 2 2
Overvoltage
(3)
59 2 2 2 2 2 2 2
Neutral voltage displacement 59N 2 2 2 2 2 2 2
Negative sequence overvoltage 47 1 1 1 1 1 1 1
Overfrequency 81H 2 2 2 2 2 2 2
Underfrequency 81L 4 4 4 4 4 4 4
Recloser (4 cycles) 79 v v v
Temperature monitoring (8 or 16 RTDs, 2 set points per RTD) 38/49T v v v v
Thermostat / Buchholz 26/63 v v
Metering
Phase current I1, I2, I3 RMS, residual current I0 b b b b b b b
Average current I1, I2, I3, peak demand current IM1, IM2, IM3 b b b b b b b
Voltage U21, U32, U13, V1, V2, V3, residual voltage V0 b b b b b b b
Positive sequence voltage Vd / rotation direction, neg. seq. voltage Vi b b b b b b b
Frequency b b b b b b b
Active, reactive and apparent power P, Q, S
Peak demand power PM, QM
Power factor
b b b b b b b
Calculated active and reactive energy (W.h, var.h) b b b b b b b
Active and reactive energy by pulse counting (W.h, var.h) v v v v v v v
Temperature v v v v
Network and machine diagnosis
Tripping context b b b b b b b
Tripping current TripI1, TripI2, TripI3, TripI0 b b b b b b b
Unbalance ratio / negative sequence current Ii b b b b b b b
Phase displacement 0, 1, 2, 3 b b b b b b b
Disturbance recording b b b b b b b
Thermal capacity used b b b b
Remaining operating time before overload tripping b b b b
Waiting time after overload tripping b b b b
Running hours counter / operating time b b b b
Starting current and time b
Start inhibit time delay, number of starts before inhibition b
Switchgear diagnosis
Cumulative breaking current b b b b b b b
Trip circuit supervision v v v v v v v
Number of operations, operating time, charging time v v v v v v v
CT/VT supervision 60FL b b b b b b b
Control and monitoring ANSI code
Circuit breaker / contactor control
(1)
94/69 b b b b b b b
Latching / acknowledgment 86 b b b b b b b
Logic discrimination 68 v v v v v v v
Switching of groups of settings b b b b b b b
Logic equation editor b b b b b b b
Additional modules
8 temperature sensor inputs - MET148-2 module
(2)
v v v v
1 low level analog output - MSA141 module v v v v v v v
Logic inputs / outputs - MES114/MES114E/MES114F (10I/4O) module v v v v v v v
Communication interface - ACE949-2 (2-wire RS 485),
ACE959 (4-wire RS 485) or ACE 937 (fiber optic)
v v v v v v v
b standard, v according to parameter setting an MES114/MES114E/MES114F or MET148-2 optional input/output modules
(1) For shunt trip or undervoltage trip unit.
(2) 2 modules possible.
(3) Exclusive choice, phase-to-neutral voltage or phase-to-phase voltage for each of the 2 units.
10
Metering
Description
Metering functions
The values are displayed as primary values with the
related units: A, V, Hz,C,F, W,
Current
b RMS current for each of the 3 phases in the circuit,
taking into account harmonics up to at least number 13
b residual current.
Average current and peak demand current
b average current on each of the 3 phases
b greatest average current on each of the 3 phases
(peak demand current).
The peak demand currents give the current consumed
at the time of peak loads.
The average current is calculated over a period that
may be parameterized from 5 to 60 mn, and may be
reset to zero.
Voltage
b phase-to-neutral voltages V1, V2, V3
b phase-to-phase voltages U21, U32, U13
b positive sequence voltage Vd
b residual voltage V0
b negative sequence voltage Vi.
Frequency
Power
Active, reactive and apparent power, power factor
(cos )
Peak demand power
Greatest value of active and reactive power absorbed,
over the same period as peak demand currents, with
the possibility of resetting to zero.
Energy
b 4 accumulated energy counters, calculated
according to the currents and voltages measured:
active and reactive energy, in each flow direction
b 1 to 4 additional accumulated energy counters for the
acquisition of active or reactive energy pulses delivered
by external counters.
Temperature
Measurement of the temperature of each sensor.
Network diagnosis
assistance functions
Tripping context
Storage of the tripping currents and I0, ld, U21, U32,
U13, V0, Vi, Vd, F, P and Q values at the time of the
detection of the fault. The values for the last five trips
are stored.
Tripping current
Storage of the 3 phase currents and earth current at the
time the Sepam gave the last tripping order, so as to
find out the fault current (fault analysis).
The values are stored until the next trip.
Negative sequence / unbalance
Ratio of negative sequence phase current,
characteristic of an unbalanced power supply of the
equipment to be protected.
Phase displacement
b variance in phase 1, 2, 3 between phase
currents l1, l2, l3 and voltages V1, V2, V3
b variance in phase 0 between residual current and
residual voltage.
Disturbance recording
Recording of sampled values of analog measurement signals and logic states. By
parameter setting, it is possible to choose:
b the events that will trigger a record
b the recording period prior to the occurrence of the event
b the number and duration of records (series 40 only).
Characteristics Series 20 Series 40
Number of records in
COMTRADE format
2 Adjustable from 1 to 19
Total duration of a record 86 periods (1.72 s at 50 Hz,
1.43 s at 60 Hz)
Adjustable from 1 s to 10 s
The total of all the records plus
one must not be more than
20 s at 50 Hz and 16 s at
60 Hz
Number of points per period 12 12
Duration of recording prior to
occurrence of the event
Adjustable from 0 to 85
periods
Adjustable from 0 to 99
periods
Recorded data Currents or voltages,
logic inputs, pick up
and logic output O1
Currents and voltages,
logic inputs, pick up, logic
outputs (O1 to O4)
Machine operation assistance functions
Thermal capacity used
Temperature build-up related to the load.
It is displayed as a percentage of the rated thermal capacity.
Remaining operating time before overload tripping
Indicates the time remaining before tripping by the thermal overload protection
function.
Waiting time after overload tripping
Indicates the time remaining before starting is allowed according to inhibition by the
thermal protection function.
Starting current and time / motor overload
Measurement of the maximum current consumed by the motor during a starting
sequence or an overload, as well as the duration.
Start inhibit time delay / number of starts before inhibition
Indicates the remaining number of starts allowed by the starts per hour protection
function and, if the number is zero, the waiting time before starting is allowed.
Running hours counter / operating time
Cumulative time during which the protected equipment (motor or transformer) has
been operating (I > 0.1 Ib).
The cumulative value is displayed in hours (0 to 65535 h).
Switchgear diagnosis functions
These measurements are to be compared with the data supplied by the switchgear
manufacturer.
Cumulative breaking current
The value displayed may be used to evaluate the state of the circuit breaker poles.
Number of operations
Running total of the number of opening operations performed by the device.
Device operating time
Operating time, charging time.
These data may be used to evaluate the state of the pole operating mechanism.
ANSI 60FL - CT/VT supervision
This function is used to monitor the complete measurement chain:
b CT and VT sensors
b connection
b Sepam analog inputs.
Supervision is ensured by:
b checking of the consistency of the currents and voltages measured
b acquisition of phase or residual voltage transformer protection fuse melting
contacts.
In the event of current or voltage data loss, the assigned protection functions may be
inhibited to avoid any nuisance tripping.
11
Metering
General settings and
characteristics

General settings Selection Series 20 range Series 40 range
In rated phase current
(sensor primary current)
2 or 3 1 A / 5 A CTs 1 A to 6250 A 1 A to 6250 A
3 LPCT sensors 25 A to 3150 A
(1)
25 A to 3150 A
(1)
Ib base current
(corresponds to the rated power of the
equipment)
0.4 to 1.3 In 0.4 to 1.3 In
In0 residual current sum of the 3 phase currents see In rated phase current see In rated phase current
CSH120 or CSH200 core bal. CT 2 A or 20 A rating 2 A, 5 A or 20 A rating
1 A / 5 A CT + CSH30 interposing ring
CT
1 A to 6250 A (In0 = In) 1 A to 6250 A (In0 = In)
1 A / 5 A CT + CSH30 interposing ring
CT - Sensitivity x10
- 1 A to 6250 A (In0 = In/10)
core balance CT + ACE990
(the ratio of the core bal. CT 1/n should
be such that 50 y n y 1500)
according to current to be monitored
and use of ACE990
according to current to be monitored
and use of ACE990
Unp primary rated phase-to-phase voltage
(Vnp: primary rated phase-to-neutral
voltage: Vnp = Unp/3)
220 V to 250 kV 220 V to 250 kV
Uns secondary rated phase-to-phase
voltage
3 VTs: V1, V2, V3 100, 110, 115, 120, 200, 230 V 100, 110, 115, 120, 200, 230 V
2 VTs: U21, U32 100, 110, 115, 120 V 100, 110, 115, 120 V
1 VT: U21 100, 110, 115, 120 V 100, 110, 115, 120 V
Pulse-type accumulated energy counter Increments active energy - 0.1 kW.h to 5 MW.h
Increments reactive energy - 0.1 kvar.h to 5 Mvar.h
Frequency 50 Hz or 60 Hz 50 Hz or 60 Hz
(1) Table of In values in Amps: 25, 50, 100, 125, 133, 200, 250, 320, 400, 500, 630, 666, 1000, 1600, 2000, 3150.
Functions Working ranges Accuracy series 20
(1)
Accuracy series 40
(1)
MSA141
(2)
Metering
Phase current 0.1 to 1.5 In
(4)
typically 1% typically 0.5% b
Residual current 0.1 to 1.5 In0 typically 1% typically 1% b
Average current and peak demand phase
current
0.1 to 1.5 In typically 1% typically 0.5%
Phase-to-phase voltage 0.05 to 1.2 Unp typically 1% typically 0.5% b
Phase-to-neutral voltage 0.05 to 1.2 Vnp typically 1% typically 0.5% b
Residual voltage 0.015 to 3 Vnp typically 1% typically 1%
Positive sequence voltage 0.05 to 1.2 Vnp typically 5% typically 2%
Negative sequence voltage 0.05 to 1.2 Vnp - typically 2%
Frequency series 20 50 5 Hz or 60 5 Hz 0.05 Hz - b
Frequency series 40 25 to 65 Hz - 0.02 Hz b
Temperature -30C to +200C or -22F to 392F 1C from +20 to +140C 1C from +20 to +140Cb
Active power 0.015 Sn
(3)
at 999 MW - typically 1% b
Reactive power 0.015 Sn
(3)
at 999 Mvar - typically 1% b
Apparent power 0.015 Sn
(3)
at 999 MVA - typically 1% b
Power factor -1 (CAP) to 1 (IND) - typically 1%
Peak demand active power 0.015 Sn
(3)
at 999 MW - typically 1%
Peak demand reactive power 0.015 Sn
(3)
at 999 Mvar - typically 1%
Active energy 0 to 2.1.10
8
MW.h - 1%, 1 digit
Reactive energy 0 to 2.1.10
8
Mvar.h - 1%, 1 digit
Network diagnosis assistance
Phase tripping current 0.1 to 40 In 5% 5%
Earth fault tripping current 0.1 to 20 In0 5% 5%
Unbalance / neg. seq. current li 10% to 500% Ib 2% 2%
Phase displacement 0 0 to 359 - typically 2
Phase displacement 1, 2, 3 0 to 359 - typically 2
Machine operation assistance
Running hours counter / operating time 0 to 65535 hours 1% or 0.5 h 1% or 0.5 h
Thermal capacity used 0 to 800% (100% for I phase = Ib) 1% 1% b
Remaining operating time before overload
tripping
0 to 999 mn 1 mn 1 mn
Waiting time after overload tripping 0 to 999 mn 1 mn 1 mn
Starting current 1.2 Ib 24 In 5% 5%
Starting time 0 to 300 s 300 ms 300 ms
Start inhibit time delay 0 to 360 mn 1 mn 1 mn
Number of starts before inhibition 0 to 60 1 1
Cooling time constant 5 mn to 600 mn - 5%
Switchgear diagnosis assistance
Cumulative breaking current 0 to 65535 kA 10% 10%
Number of operations 0 to 65535 1 1
Operating time 20 to 100 ms 1 ms 1 ms
Charging time 1 to 20 s 0.5 s 0.5 s
(1) In reference conditions (IEC 60255-6), typical for In or Unp.
(2) Measurements available in analog format according to parameter setting of MSA141 module.
(3) Sn: apparent power, = 3.Unp.In.
(4) Measurement up to 0.02 In for information purpose.
12
Protection
Description

Current protection functions
ANSI 50/51 - Phase overcurrent
Three-phase protection against overloads and phase-
to-phase short-circuits. The protection function
comprises four units:
b definite time (DT)
b IDMT (16 types of IDMT curves)
b instantaneous or time-delayed.
Each unit has a reset time setting that allows:
b detection of restriking faults
b coordination with electromechanical relays.
ANSI 50V/51V - Voltage-restrained overcurrent
Three-phase protection against overloads and phase-
to-phase short-circuits, suited to generator protection,
for which the tripping set point is adjusted according to
the voltage.
It may be set as follows:
b definite time (DT)
b IDMT (16 types of IDMT curves)
b instantaneous or time-delayed.
Each unit has a reset time setting that allows:
b detection of restriking faults
b coordination with electromechanical relays.
ANSI 50N/51N or 50G/51G - Earth fault or sensitive
earth fault
Protection against earth faults.
Earth faults may be detected according to parameter
setting based on:
b the three phase currents (3I sum)
b a specific CSH120 or CSH200 core balance CT
according to the required diameter; this method gives
greater sensitivity. The parameterizable choice of
ratings provides a very wide range of settings.
b a current transformer (1 A or 5 A), combined with a
CSH30 interposing ring CT.
The protection comprises four units:
b definite time (DT)
b IDMT (16 types of IDMT curves)
b instantaneous or time-delayed.
Each unit has a reset time setting that allows:
b detection of restriking faults
b coordination with electromechanical relays.
It also has harmonic 2 restraint to ensure stability
during transformer energizing.
ANSI 50 BF - Breaker failure
Backup protection that delivers a tripping order to the
upstream or adjacent breakers should the breaker that
is being commanded fail to trip, detected by
measurement of the through current after a tripping
order.
ANSI 46 - Negative sequence / unbalance
Protection against phase unbalance.
Sensitive protection to detect 2-phase faults at the end
of long lines.
Protection of equipment against temperature build-up
cause by an unbalanced supply or the inversion or loss
of a phase and against phase current unbalance. IDMT
or definite time characteristics.
Directional current protection functions
ANSI 67 - Directional phase overcurrent
This protection function is three-phase. It comprises a phase overcurrent function
associated with direction detection. It picks up if the phase overcurrent function in the
chosen direction (line or busbar) is activated for at least one of the three phases. It
operates as definite time or IDMT. It is insensitive to the loss of measurement voltage
at the time of the fault.
ANSI 67N/67NC - Directional earth fault
It has 2 types of characteristics:
b type 1, projection
b type 2, according to I0 vector magnitude.
It can operate on impedant, isolated or compensated neutral systems.
The type 1 units allow the detection of restriking faults.
The protection function comprises two units:
b definite time (DT)
b IDMT (16 types of IDMT curves) (type 2 only)
b instantaneous or time-delayed.
The type 2 units have a reset time setting that allows:
b detection of restriking faults
b coordination with electromechanical relays.
Directional power protection functions
ANSI 32P - Directional active overpower
This protection function is activated if the power flowing in one direction or the other,
according to the application (supplied or absorbed), is greater than the set point.
ANSI 32Q/40 - Directional reactive overpower
This protection function may be used to detect synchronous machine (generator or
motor) field loss.
The protection function is activated if the reactive power flowing in one direction or
the other, according to the application (supplied or absorbed), is greater than the set
point.
Machine protection functions
ANSI 49RMS - Thermal overload
Protection of equipment against thermal damage caused by overloads.
The protection may be inhibited by a logic input when required by process control
conditions.
The thermal capacity used is calculated according to a mathematical model which
takes into account:
b current RMS values
b ambient temperature
b negative sequence current, a cause of motor rotor temperature rise.
The protection function comprises 2 groups of settings, each of which includes:
b an adjustable alarm set point
b an adjustable trip set point
b the initial thermal capacity used setting, in order to accurately adapt the protection
characteristics to fit the equipments thermal withstand curves supplied by the
manufacturer.
b the equipments heating and cooling time constants.
Sepam series 40 has a function that automatically calculates the cooling time
constant based on measurement of the equipment temperature by a sensor.
Application for a transformer:
switching of groups of settings by a logic input according to the transformer
ventilation operating rate, natural or forced (ONAN or ONAF).
Application for a motor:
switching of groups of settings according to a current set point to take into account
the thermal withstand of the motor with a blocked rotor.
13
Protection
Description
Machine protection
functions (contd)
ANSI 37 - Phase undercurrent
Protection of pumps against the consequences of loss
of priming.
The protection function detects time-delayed current
drops that correspond to motor no-load operation,
characteristic of the loss of pump priming.
ANSI 48/51LR/14 - Locked rotor / excessive starting
time
Protection of motors that are liable to start with
overloads or insufficient supply voltage and/or that
drive loads that are liable to jam (e.g. crushers).
The locked rotor function is an overcurrent protection
function that is only confirmed after a time delay that
corresponds to the normal starting time.
Motor reacceleration and locked rotor detection
(detection of zero speed) may be taken into account by
logic inputs.
ANSI 66 - Starts per hour
Protection against overheating caused by too frequent
starts.
Checking of the number of:
b starts per hour (or adjustable time period)
b consecutive starts.
The protection inhibits motor energizing for a preset
time period once the permissible limits have been
reached.
Motor re-acceleration may be taken into account by a
logic input.
ANSI 26/63 - Thermostat, Buchholz, gas, pressure,
temperature detection
Protection of transformers against temperature rise and
internal faults via logic inputs linked to devices
integrated in the equipment.
ANSI 38/49T - Temperature monitoring by RTD
Protection function that detects abnormal overheating
of the windings and/or bearings of motors equipped
with RTDs.
The protection includes 2 independent set points that
are adjustable for each RTD.
ANSI 27D - Positive sequence undervoltage
Protection of motors against faulty operation due to
insufficient or unbalanced supply voltage.
Detection of reverse rotation direction.
In order for the protection to be used, voltage
transformers must be connected to Sepam to measure
U21 and U32.
ANSI 27R - Remanent undervoltage
Monitoring of the clearing of voltage sustained by
rotating machines after circuit opening. The protection
is used to prevent transient electrical and mechanical
phenomena that are caused by fast re-energizing of
motors.
It monitors phase-to-phase voltage U21 or phase-to-
neutral voltage V1.
Voltage protection functions
ANSI 27 - Phase-to-phase undervoltage
Protection used either for automated functions (transfer, load shedding) or to protect
motors against undervoltage. The protection function monitors the drop in voltage in
each of the phase-to-phase voltages measured.
ANSI 27S - Phase-to-neutral undervoltage
Protection used to detect phase-to-earth faults (isolated neutral systems).
ANSI 59 - Phase-to-phase overvoltage
Protection against abnormally high voltage or checking that there is sufficient voltage
for a power supply transfer. It operates with phase-to-phase voltage (series 20 and
series 40) or phase-to-neutral voltage (series 40 only).
ANSI 59N - Neutral voltage displacement
Detection of insulation faults in isolated neutral systems by the measurement of
neutral voltage displacement. The protection function is generally associated with
transformer incomer or busbar protection.
The function includes 2 set points.
ANSI 47 - Negative sequence voltage
Protection against phase unbalance resulting from distant faults, a phase inversion
or unbalanced power supply.
Frequency protection functions
ANSI 81H - Overfrequency
Protection against abnormally high frequency.
ANSI 81L - Underfrequency
Detection of variances with respect to the rated frequency, in order to maintain a high
quality power supply. The protection may be used for overall tripping or for load
shedding.
ANSI 81R - Rate of change of frequency (ROCOF)
Protection used for fast disconnection of a source transmitting power into a power
network when a fault occurs, or to monitor load shedding.
Recloser
ANSI 79
Automation device used to reclose the circuit breaker after tripping triggered by a
transient fault on a line (the funciton includes 1 to 4 parameterizable reclosing cycles
and can be easily adapted for different operating modes).
14
Protection
Setting ranges

Functions Settings Time delays
ANSI 50/51 - Phase overcurrent
Tripping curve Tripping time delay Reset time
Definite time DT
SIT, LTI, VIT, EIT, UIT
(1)
DT
RI DT
IEC: SIT/A, LTI/B, VIT/B, EIT/C DT or IDMT
IEEE: MI (D), VI (E), EI (F) DT or IDMT
IAC: I, VI, EI DT or IDMT
Is set point 0.1 to 24 In Definite time Inst.; 0.05 s to 300 s
0.1 to 2.4 In IDMT 0.1 s to 12.5 s at 10 Is
Reset time Definite time (DT; timer hold) Inst.; 0.05 s to 300 s
IDMT (IDMT; reset time) 0.5 s to 20 s
Confirmation
(2)
None
By negative sequence overvoltage
By phase-to-phase undervoltage
ANSI 50V/51V - Voltage-restrained phase overcurrent
Tripping curve Tripping time delay Reset time
IDMT DT
SIT, LTI, VIT, EIT, UIT DT
RI DT
IEC: SIT/A, LTI/B, VIT/B, EIT/C DT or IDMT
IEEE: MI (D), VI (E), EI (F) DT or IDMT
IAC: I, VI, EI DT or IDMT
Is set point 0.1 to 24 In Definite time Inst.; 0.05 s to 300 s
0.1 to 2,4 In IDMT 0.1 s to 12.5 s at 10 Is
Reset time Definite time (DT; timer hold) Inst.; 0.05 s to 300 s
IDMT (IDMT; reset time) 0.5 s to 20 s
ANSI 50N/51N or 50G/51G - Earth fault
Tripping curve Tripping time delay Reset time
Definite time DT
SIT, LTI, VIT, EIT, UIT
(1)
DT
RI DT
IEC: SIT/A,LTI/B, VIT/B, EIT/C DT or IDMT
IEEE: MI (D), VI (E), EI (F) DT or IDMT
IAC: I, VI, EI DT or IDMT
Is0 set point 0.1 to 15 In0 Definite time Inst.; 0.05 s to 300 s
0.1 to 1 In0 IDMT 0.1 s to 12.5 s at 10 Is0
Reset time Definite time (DT; timer hold) Inst.; 0.05 s to 300 s
IDMT (IDMT; reset time) 0.5 s to 20 s
ANSI 50 BF - Breaker failure
Presence of current 0.2 to 2 In
Operating time 0.05 s to 30 s
ANSI 46 - Negative sequence / unbalance
Definite time 0.1 to 5 Ib 0.1 s to 300 s
IDMT 0.1 to 0.5 Ib (Schneider Electric) 0.1 to 1Ib (IEC, IEEE) 0.1 s to 1 s
Tripping curve Schneider Electric
IEC: SIT/A, LTI/B, VIT/B, EIT/C
(2)
IEEE: MI (D), VI (E), EI (F)
(2)
ANSI 67 - Directional phase overcurrent
Tripping curve Tripping time delay Reset time
Definite time DT
SIT, LTI, VIT, EIT, UIT
(1)
DT
RI DT
CEI: SIT/A, LTI/B, VIT/B, EIT/C DT or IDMT
IEEE: MI (D), VI (E), EI (F) DT or IDMT
IAC: I, VI, EI DT or IDMT
Is set point 0.1 to 24 In Definite time Inst.; 0.05 s to 300 s
0.1 to 2.4 In IDMT 0.1 s to 12.5 s at 10 Is
Reset time Definite time (DT; timer hold) Inst.; 0.05 s to 300 s
IDMT (IDMT; reset time) 0.5 s to 20 s
Characteristic angle 30, 45, 60
(1) Tripping as of 1.2 Is.
(2) On series 40 only.
15
Protection
Setting ranges

Functions Settings Time delays
ANSI 67N/67NC - Directional earth fault, projection (type 1)
Characteristic angle -45, 0, 15, 30, 45, 60, 90
Is0 set point 0.1 to 15 In0 Definite time Inst.; 0.05 s to 300 s
Vs0 set point 2 to 80% of Unp
Memory time T0mem time 0; 0.05 s to 300 s
V0mem validity set point 0; 2 to 80% of Unp
ANSI 67N/67NC - Directional earth fault, according to vector magnitude (type 2)
Characteristic angle -45, 0, 15, 30, 45, 60, 90
Tripping curve Tripping time delay Reset time
Definite time DT
SIT, LTI, VIT, EIT, UIT
(1)
DT
RI DT
IEC, SIT/A,LTI/B, VIT/B, EIT/C DT or IDMT
IEEE: MI (D), VI (E), EI (F) DT or IDMT
IAC: I, VI, EI DT or IDMT
Is0 set point 0.1 to 15 In0 Definite time Inst.; 0.05 s to 300 s
0.1 to 1 In0 IDMT 0.1 s to 12.5 s at 10 Is0
Vs0 set point 2 to 80% of Unp
Reset time Definite time (DT; timer hold) Inst.; 0.05 s to 300 s
IDMT (IDMT; reset time) 0.5 s to 20 s
ANSI 32P - Directional active overpower
1 to 120% of Sn
(3)
0.1 s to 300 s
ANSI 32Q/40 - Directional reactive overpower
5 to 120% de Sn
(3)
0.1 s to 300 s
ANSI 49RMS - Thermal overload Rate 1 Rate 2
Negative sequence factor 0 - 2.25 - 4.5 - 9
Time constant Heating T1: 5 to 120 mn T1: 5 to 120 mn
Cooling T2: 5 to 600 mn T2: 5 to 600 mn
Alarm and trip set points 50 to 300% of thermal capacity used
Cold curve modification factor 0 to 100%
Switching of thermal settings condition by logic input
by Is setting adjustable from 0.25 to 8 Ib
Maximum equipment temperature 60 to 200C
ANSI 37 - Phase undercurrent
0.15 to 1 Ib 0.05 s to 300 s
ANSI 48/51LR - Excessive starting time / locked rotor
0.5 Ib to 5 Ib ST start time 0.5 s to 300 s
LT and LTS time delays 0.05 s to 300 s
ANSI 66 - Starts per hour
Starts per period 1 to 60 Period 1 to 6 h
Consecutive starts 1 to 60 Time between starts 0 to 90 mn
ANSI 38/49T - Temperature (RTDs)
Alarm and trip set points 0 to 180 C (or 32 to 356 F)
ANSI 27D - ANSI 47 - Positive sequence undervoltage
15 to 60% of Unp 0.05 s to 300 s
ANSI 27R - Remanent undervoltage
5 to 100% of Unp 0.05 s to 300 s
ANSI 27 - Phase-to-phase undervoltage
5 to 100% of Unp 0.05 s to 300 s
ANSI 27S - Phase-to-neutral undervoltage
5 to 100% of Vnp 0.05 s to 300 s
ANSI 59 - Overvoltage phase-to-phase phase-to-neutral
(2)
50 to 150% of Unp 50 to 150% of Vnp 0.05 s to 300 s
ANSI 59N - Neutral voltage displacement
2 to 80% of Unp 0.05 s to 300 s
ANS 47 - Negative sequence overvoltage
1 to 50% of Unp 0.05 s to 300 s
ANSI 81H - Overfrequency
series 20 50 to 53 Hz or 60 to 63 Hz 0.1 s to 300 s
series 40 50 to 55 Hz or 60 to 65 Hz 0.1 s to 300 s
ANSI 81L - Underfrequency
series 20 45 to 50 Hz or 55 to 60 Hz 0.1 s to 300 s
series 40 40 to 50 Hz or 50 to 60 Hz 0.1 s to 300 s
ANSI 81 R - Rate of change of frequency
0.1 to 10 Hz/s Inst.; 0.15 s to 300 s
(1) Tripping as of 1.2 Is.
(2) On series 40 only.
(3) Sn = 3.In.Unp.
16
Connection diagrams
Sepam series 20

S20 / T20 / M20 types
D
E
5
0
5
9
2
Connection to 1 A / 5 A current sensors
Connector Type Ref. Cable
A Screw-
type
CCA620 1 wire 0.2 to 2.5 mm
2

(u AWG 24-12)
2 wires 0.2 to 1 mm
2

(u AWG 24-16)
Ring lug
6.35 mm
CCA622
B Ring lug
4 mm
CCA630 1.5 to 6 mm
2
(AWG 16 to AWG 10)

C RJ45 CCA612
D RJ45 CCA770: L = 0.6 m
CCA772: L = 2 m
CCA774: L = 4 m
B21 / B22 types
D
E
5
0
5
9
3
Connector Type Ref. Cable
A Screw-
type
CCA620 1 wire 0.2 to 2.5 mm
2

(u AWG 24-12)
2 wires 0.2 to 1 mm
2

(u AWG 24-16)
Ring lug
6.35 mm
CCA622
B Screw-
type
CCT640 1 wire 0.2 to 2.5 mm
2
(u AWG 24-12)
2 wires 0.2 to 1 mm
2

(u AWG 24-16)

C RJ45 CCA612
D RJ45 CCA770: L = 0.6 m
CCA772: L = 2 m
CCA774: L = 4 m
(1) This type of connection allows the calculation of residual voltage.
17
Connection diagrams
Sepam series 40

S40 / S41 / S42 types
T40 / T42 / M41 / G40 types
D
E
5
0
5
9
6
Connection to 1 A / 5 A current sensors
Connector Type Ref. Cable
A Screw-
type
CCA620 1 wire 0.2 to 2.5 mm
2

(u AWG 24-12)
2 wires 0.2 to 1 mm
2

(u AWG 24-16)
Ring lug
6.35 mm
CCA622
B Ring lug
4 mm
CCA630 1.5 to 6 mm
2
(AWG 16 to AWG 10)

C RJ45 CCA612
D RJ45 CCA770: L = 0.6 m
CCA772: L = 2 m
CCA774: L = 4 m
E Screw-
type
CCA626 1 wire 0.2 to 2.5 mm
2

(u AWG 24-12)
2 wires 0.2 to 1 mm
2

(u AWG 24-16)
Ring lug
6.35 mm
CCA627
(1) This type of connection allows the calculation of residual voltage.
(2) Accessory for bridging terminals 3 and 5 supplied with CCA626 connector.
18
Connection diagrams
Phase current inputs
Variant 1: phase current measurement by three 1 A or 5 A CTs (standard connection)
M
T
1
0
9
9
0
Connection of three 1 A or 5 A CTs to the CCA630 connector.
The measurement of the 3 phase currents allows the calculation of residual current.
Variant 2: phase current measurement by two 1 A or 5 A CTs
M
T
1
0
7
0
0
Connection of two 1 A or 5 A CTs to the CCA630 connector.
The measurement of phase currents 1 and 3 is sufficient to ensure all the current-
based protection functions.
This arrangement does not allow the calculation of residual current.
Variant 3: phase current measurement by 3 LPCT type sensors
M
T
1
0
9
8
5
Connection of 3 Low Power Current Transducer (LPCT) type sensors to the CCA670
connector. The connection of just one or two sensors is not allowed and causes
Sepam to switch to the fallback position.
The measurement of the 3 phase currents allows the calculation of residual current.
The In parameter, primary rated current measured by an LPCT, is to be chosen from
the following values, in Amps: 25, 50, 100, 125, 133, 200, 250, 320, 400, 500, 630,
666, 1000, 1600, 2000, 3150.
Parameter to be set using the advanced UMI and the SFT2841 software tool, to be
completed by hardware setting of the microswitches on the CCA670 connector.
19
Connection diagrams
Residual current input
Variant 1: residual current calculation by sum of 3 phase currents
The residual current is obtained by taking the vector sum of the 3 phase currents I1,
I2 and I3, measured by three 1 A or 5 A CTs or by three LPCT type sensors.
See current input connection diagrams.
Variant 2: residual current measurement by CSH120 or CSH200 core balance CT (standard connection)
M
T
1
0
9
9
1
Arrangement recommended for the protection of isolated or compensated neutral
systems in which very low fault currents need to be detected.
Setting range from 0.1 In0 to 15 In0, with In0 = 2 A or 20 A (or 5 A for series 40)
according to parameter setting.
Variant 3: residual current measurement by 1 A or 5 A CT and CSH30 interposing ring CT
M
T
1
1
0
4
5
The CSH30 interposing ring CT is used to connect Sepam to 1 A or 5 A CTs to
measure the residual current.
b connection of CSH30 interposing ring CT to 1 A CT: make 2 turns through the CSH
primary winding
b connection of CSH30 interposing ring CT to 5 A CT: make 4 turns through the CSH
primary winding
b with series 40, the sensitivity can be multiplied by 10
by parameter setting of In0 = In/10.
Setting range from 0.1 In to 15 In, or 0.01 In to 1.5 In (series 40)
with In = CT primary current.
M
T
1
1
0
4
6
Variant 4: residual current measurement by core balance CT with ratio 1/n (n between 50 and 1500)
D
E
5
0
5
8
9
The ACE990 is used as an interface between a MV core balance CT with ratio 1/n
(50 < n < 1500) and the Sepam residual current input.
This arrangement makes it possible to keep the existing core balance CTs in the
installation.
Setting range from 0.1 In0 to 15 In0, with In0 = k.n,
with n = number of turns through core balance CT
and k = factor to be determined according to the wiring of the ACE990 and the
parameter setting used by Sepam, among 20 discrete values from 0.00578 to
0.26316.
20
Connection diagrams
Sepam series 20 voltage inputs
The phase and residual voltage transformer secondary circuits are connected to the
CCT640 connector (item ) on Sepam series 20, B type. The CCT640 connector
contains 4 transformers which perform isolation and impedance matching of the VTs
and Sepam input circuits.
Variant 1: measurement of 3 phase-to-neutral voltages (standard connection)
D
E
5
0
6
8
6
Phase voltage sensor parameter setting
Residual voltage sensor parameter setting
Voltages measured
Values calculated
Measurements unavailable
Protection functions unavailable
(according to type of Sepam)
3V
3V sum
V1, V2, V3
U21, U32, U13, V0, Vd, f
None
None
Variant 2: measurement of 3 phase-to-neutral voltage and residual voltage
D
E
5
0
6
8
7
Phase voltage sensor parameter setting
Residual voltage sensor parameter setting
Voltages measured
Values calculated
Measurements unavailable
Protection functions unavailable
(according to type of Sepam)
3V
External VT
V1, V2, V3, V0
U21, U32, U13, Vd, f
None
None
Variant 3: measurement of 2 phase-to-phase voltages
D
E
5
0
6
8
8
Phase voltage sensor parameter setting
Residual voltage sensor parameter setting
Voltages measured
Values calculated
Measurements unavailable
Protection functions unavailable
(according to type of Sepam)
U21, U32
None
U21, U32
U13, Vd, f
V1, V2, V3, V0
59N, 27S
Variant 4: measurement of 1 phase-to-phase voltage and residual voltage
D
E
5
0
6
8
9
Phase voltage sensor parameter setting
Residual voltage sensor parameter setting
Voltages measured
Values calculated
Measurements unavailable
Protection functions unavailable
(according to type of Sepam)
U21
External VT
U21, V0
f
U32, U13, V1, V2, V3, Vd
47, 27D, 27S
Variant 5: measurement of 1 phase-to-phase voltage
D
E
5
0
6
9
0
Phase voltage sensor parameter setting
Residual voltage sensor parameter setting
Voltages measured
Values calculated
Measurements unavailable
Protection functions unavailable
(according to type of Sepam)

U21
None
U21
f
U32, U13, V1, V2, V3, V0, Vd
47, 27D, 59N, 27S
B
21
Connection diagrams
Sepam series 40 voltage inputs
The phase and residual voltage transformer secondary circuits are connected
directly to the connector marked .
The 3 impedance matching and isolation transformers are integrated in the
Sepam series 40 base unit.
Variant 1: measurement of 3 phase-to-neutral voltages (standard connection)
M
T
1
0
9
9
2
Phase voltage sensor parameter setting
Residual voltage sensor parameter setting
Voltages measured
Values calculated
Measurements unavailable
Protection functions unavailable
(according to type of Sepam)
3V
3V sum
V1, V2, V3
U21, U32, U13, V0, Vd, Vi, f
None
None
Variant 2: measurement of 2 phase-to-phase voltages and residual voltage
M
T
1
0
9
9
3
Phase voltage sensor parameter setting
Residual voltage sensor parameter setting
Voltages measured
Values calculated
Measurements unavailable
Protection functions unavailable
(according to type of Sepam)
U21, U32
External VT
U21, U32, V0
U13, V1, V2, V3, Vd, Vi, f
None
None
Variant 3: measurement of 2 phase-to-phase voltages
M
T
1
0
9
9
4
Phase voltage sensor parameter setting
Residual voltage sensor parameter setting
Voltages measured
Values calculated
Measurements unavailable
Protection functions unavailable
(according to type of Sepam)
U21, U32
None
U21, U32
U13, Vd, Vi, f
V1, V2, V3, V0
67N/67NC, 59N
Variant 4: measurement of 1 phase-to-phase voltage and residual voltage
M
T
1
1
0
1
1
Phase voltage sensor parameter setting
Residual voltage sensor parameter setting
Voltages measured
Values calculated
Measurements unavailable
Protection functions unavailable
(according to type of Sepam)
U21
External VT
U21, V0
f
U32, U13, V1, V2, V3, Vd, Vi
67, 47, 27D, 32P, 32Q/40, 27S
Variant 5: measurement of 1 phase-to-phase voltage
M
T
1
1
0
1
6
Phase voltage sensor parameter setting
Residual voltage sensor parameter setting
Voltages measured
Values calculated
Measurements unavailable
Protection functions unavailable
(according to type of Sepam)

U21
None
U21
f
U32, U13, V1, V2, V3, V0, Vd, Vi
67, 47, 27D, 32P, 32Q/40,
67N/67NC, 59N, 27S
E
22
Control and monitoring
Description
Sepam performs the basic control and monitoring functions necessary for the
operation of the electrical network, thereby reducing the need for auxiliary relays.
The control and monitoring functions may be parameterized using the SFT2841
software tool, however each type of Sepam has parameter setting by default which
allows easier commissioning in the most frequent applications.
ANSI 94/69 - Circuit breaker/contactor control
Sepam is used to control breaking devices equipped with different types of closing
and tripping coils:
b circuit breakers with shunt trip or undervoltage trip units
b latching contactors with shunt trip units.
The breaking device control function processes all the circuit breaker closing and
tripping conditions based on:
b breaking device status information
b remote control orders
b protection functions
b program logic specific to each application (e.g. recloser).
This function also inhibits breaking device closing according to the operating
conditions.
With Sepam series 20, it is necessary to use an MES114 module in order to have all
the required logic inputs.
Switching of groups of settings
Used to switch from one group of phase overcurrent and earth fault protection
settings to another group of settings. Switching may be performed by a logic input or
via the communication link.
Inhibition of thermal protection
Thermal protection tripping may be inhibited via a logic input.
Re-acceleration
Allows a logic input to take into account the restarting of an unstopped motor.
ANSI 68 - Logic discrimination (SSL)
This function allows quick, selective tripping of the definite time or IDMT phase
overcurrent and earth fault protection relays, without requiring the use of time
intervals between upstream and downstream protection devices. The downstream
relay transmits a blocking input signal if the protection device set points are
exceeded.
The upstream relay receives the blocking input signal on the logic input used for the
inhibition function. A saving mechanism ensures the operation of the protection in the
event of an inhibition link failure.
ANSI 86 - Latching / acknowledgment
Output relay latching may be parameterized. Latched tripping orders are stored and
must be acknowledged in order for the device to be put back into service. The user
acknowledges via the keypad or remotely via a logic input or the communication link.
Latching is stored in the event of a power outage.
Trip circuit supervision
Detects trip circuit faults (shunt trip units). Detects open/closed position discrepancy
faults (undervoltage trip units).
Watchdog
Indicates Sepam unavailability via output O4.
Output relay test
This function is used to activate each output relay.
23
Control and monitoring
Logic inputs and outputs

M
T
1
0
6
8
0
M
T
1
0
6
8
1
4 output relays on the base unit
The 4 relay outputs O1, O2, O3 and O4 on the base unit are connected to
connector .
Connector of the base unit may be either of the following:
b CCA620 screw-type connector
b CCA622 ring lug connector.
O1 and O2 are 2 control outputs used by the breaking device control function for:
b O1: breaking device tripping
b O2: inhibition of breaking device closing.
O3 and O4 are indication outputs, only O4 can be activated by the watchdog function.
CCA620 connector
(screw-type terminal block for
straight fittings).
CCA622 connector
(terminal block for ring lugs)
M
T
1
0
6
8
3
Optional input/output modules
The 4 outputs on the base unit may be completed by adding an MES114 10 input/
4 output module on the back of the base unit.
3 modules are offered, MES114, MES114E or MES114F, to suit the different input
voltage supply ranges.
The modules offer different switching thresholds as well.
The MES114 module is fully compatible with the MES108 (4 input/4 output) module
which is no longer commercialized.
Input characteristics
b 10 potential-free inputs
b external power source.
Logic inputs MES114 MES114E MES114F
Voltage 24
to 250 V DC
110
to 125 V DC
110 V AC 220
to 250 V DC
220
to 240 V AC
Range 19.2
to 275 V DC
88
to 150 V DC
88
to 132 V AC
176
to 275 V DC
176
to 264 V AC
Frequency - - 47 to 63 Hz - 47 to 63 Hz
Typical consumption 3 mA 3 mA 3 mA 3 mA 3 mA
Typical switching
threshold
14 V DC 82 V DC 58 V AC 154 V DC 120 V AC
MES114 module (10 inputs / 4 outputs).
Output characteristics
b 4 relay outputs O11, O12, O13, O14
v O11: control output, used for breaking device closing
v O12, O13, O14: indication outputs.
Connection to screw-type connectors
b 1 wire with cross-section 0.2 to 2.5 mm (u AWG 24-12)
b or 2 wires with cross-section 0.2 to 1 mm (u AWG 24-16).
M
T
1
0
6
8
4
M
T
1
0
6
8
5
Wiring of the breaking device trip circuit
Wiring to be used when the "CB control" function is activated.
Wiring for shunt trip coil.
With monitoring of trip circuit
and open/closed matching.
Wiring for undervoltage trip
unit.
With monitoring of open /
closed matching.
A
A
A
5
4 O1
M
1
2
5
I11
I12
4
D
+
A
5
4 O1
M
1
2
5
I11
I12
4
D
+
24
Control and monitoring
Logic input / output assignment
for Sepam series 20 applications

Chart of logic input and output assignments
for Sepam series 20 applications
The use of the preset control and monitoring functions requires exclusive parameter
setting and particular wiring of the inputs according to the application and type of
Sepam. Input assignment and parameter setting of the control and monitoring
functions may be done on the advanced UMI or using the SFT2841 software tool.
Since a current input may only be assigned to a single function, not all the functions
are available at the same time.
Example: when the logic discimination function is used, the switching of groups of
settings function may not be used.
Functions S20 T20 M20 B21, B22 Assignment
Logic inputs
Open position b b b b I11
Closed position b b b b I12
Logic discrimination, receive blocking input
Switching of groups of settings A/B
b b I13
b b b
External reset
External tripping 4
(1)
b
b
b
b
b
b
b
b
I14
External tripping 1
(1)
External network synchronization
b
b
b
(2)
b
b
b
b
b
I21
External tripping 2
(1)
Motor re-acceleration
b b
(3)
b
b
b I22
External tripping 3
(1)
Thermistor tripping
(1)
Buchholz alarm
(1)

Rotor direction detection
b b
(4)
b
b
b
b
b
b I23
End of charging position
Thermostat alarm
(1)

Thermistor alarm
(1)
b b
b
b
b
b
I24
Inhibit remote control
(1)

SF6-1
b
b
b
b
b
b
b
b
I25
SF6-2
Switching of thermal settings
Inhibit thermal overload
Inhibit recloser
b
b
b
b
b
b
b
b
b I26
Logic outputs
Tripping b b b b O1
Inhibit closing b b b b O2
Watchdog b b b b O4
Close order b b b b O11
NB: all of the logic inputs are available via the communication link and are accessible in the SFT2841 matrix for other non predefined applications.
(1) These inputs have parameter setting with the prefix "NEG" for undervoltage type operation.
(2) Buchholz/Gaz trip message.
(3) Thermostat trip message.
(4) Pressure trip message.
25
Control and monitoring
Logic input / output assignment
for Sepam series 40 applications

Chart of logic input and output assignments
for Sepam series 40 applications
The functions defined in the chart below are associated with a logic input by
configuration. This means that the functions used may be adapted to suit needs
within the limits of the logic inputs available. They may be reversed for undervoltage
type operation.
Functions S40, S41 S42 T40, T42 M41 G40 Assign-
ment
Logic inputs
Open position b b b b b I11
Closed position b b b b b I12
Logic discrimination, receive blocking input 1 b b b b Free
Logic discrimination, receive blocking input 2 b Free
Switching of groups of settings A/B b b b b b I13
External reset b b b b b Free
External tripping 1 b b b b b Free
External tripping 2 b b b b b Free
External tripping 3 b b b b b Free
Buchholz/gas tripping b Free
Thermostat tripping b Free
Pressure tripping b Free
Thermistor tripping b b b Free
Buchholz/gas alarm b Free
Thermostat alarm b Free
Pressure alarm b Free
Thermistor alarm b b b Free
End of charging position b b b b b Free
Inhibit remote control b b b b b Free
SF6 b b b b b Free
Inhibit recloser b b Free
External synchronization b b b b b I21
Inhibit thermal overload b b b Free
Switching of thermal settings b b b Free
Motor re-acceleration b Free
Rotor rotation detection b Free
Inhibit undercurrent b Free
Inhibit closing b b b b b Free
Open order b b b b b Free
Close order b b b b b Free
Phase voltage transformer fuse melting b b b b b Free
Residual voltage transformer fuse melting b b b b b Free
External positive active energy counter b b b b b Free
External negative active energy counter b b b b b Free
External positive reactive energy counter b b b b b Free
External negative reactive energy counter b b b b b Free
Logic outputs
Tripping b b b b b O1
Inhibit closing b b b b b O2
Watchdog b b b b b O4
Close order b b b b b O11
NB: all of the logic inputs are available via the communication link and are accessible in the SFT2841 matrix for other non predefined applications.
26
Control and monitoring
Annunciation

ANSI 30 - Front panel indications
The appearance of alarms is indicated locally by:
b messages on the advanced UMI display, available in 2 language versions:
v in English, factory-set messages, non-modifiable
v in the local language, according to the version delivered.
The language version is chosen at the time of parameter setting.
b signal lamps on the front panel.
Signal lamp addressing may be parameterized via the SFT2841 software tool.
Remote annunciation
Used to transfer data to the control room via the communication link.
Information such as circuit breaker position, SF6 fault alarm, etc.
Alarm processing on advanced UMI
b when an event appears, the signal lamp goes on and the related message is
displayed
b to clear the message from the display, the user presses the "clear" key
b after the fault disappears and the user presses the "reset" key, the signal lamp
goes off and the protection unit is reset
b the list of alarm messages remains accessible ( key) and may be cleared by
pressing the "clear" key.
List of main messages
(1)
Functions English (factory-set) Local language (e.g. French)
Phase overcurrent PHASE FAULT DEFAUT PHASE
Earth fault EARTH FAULT DEFAUT TERRE
Breaker failure BREAKER FAILURE DEF. DISJONCTEUR
Negative sequence / unbalance UNBALANCE I DESEQUIFREE I
Directional phase overcurrent DIR. PHASE FAULT DEFAUT PHASE DIR.
Directional earth fault DIR. EARTH FAULT DEFAUT TERRE DIR.
Active overpower REVERSE P RETOUR P
Thermal overload THERMAL ALARM ECHAUF
T
. ALARME
THERMAL TRIP ECHAUF
T
. DECL
T
.
Locked rotor / ROTOR BLOCKING BLOCAGE ROTOR
Rotor locked at starting ST
RT
LOCKED ROT
R
. BLOC ROTOR DEM.
Excessive starting time LONG START DEMARRAGE LONG
Starts per hour START INHIBIT DEMARRAGE INHIBE
Phase undercurrent UNDER CURRENT CURRENT <<
Overvoltage OVERVOLTAGE VOLTAGE >>
Undervoltage UNDERVOLTAGE VOLTAGE <<
Positive sequence undervoltage UNDERVOLT. PS VOLTAGE Vd <<
ROTATION ROTATION
Residual overvoltage V0 FAULT DEFAUT V0
Overfrequency OVER FREQ. FREQUENCE >
Underfrequency UNDER FREQ. FREQUENCE <
Negative sequence overvoltage UNBALANCE V DESEQUIFREE V
Temperature (RTDs) OVER TEMP. ALM. T ALARME
OVER TEMP. TRIP T. DECL
T
.
RTDS FAULT DEFAUT SONDES
Thermostat THERMOS
T
. ALARM THERM
OT
. ALARME
THERMOS
T
. TRIP THERMOS
T
. DECL
T
.
Buchholz BUCHHOLZ ALARM BUCHH ALARME
BUCHH/GAS TRIP BUCHH/GAZ DECL
T
.
Pressure PRESSURE TRIP PRESSION DECL
T
.
PRESSURE ALM. PRESSION ALARME
External tripping x (1 to 3) EXT. TRIP x (1 to 3) DECL
T
. EXT. x (1 3)
Trip circuit supervision TRIP CIRCUIT CIRCUIT DECL
T
.
Breaker control CONTROL FAULT DEFAUT COM
DE
.
SF6 SF6 LOW BAISSE SF6
(1) According to the type of Sepam and Sepam equipped with advanced UMI, or SFT2841.
!
27
Control and monitoring
Customization

Each Sepam has a logic scheme by default according to the type chosen (S20,
T20,...).
The default program logic links the data derived from the protection functions to the
signal lamps and output relays to fit the units most frequently used application.
It may be adapted for specific operations using the SFT2841 software tool, which
offers the following customization functions:
b customization of the control matrix
b logical equation editor (for Sepam series 40 only)
b modification of message wording (for Sepam series 40 only).
M
T
1
1
1
0
4
Control matrix
The control matrix as a simple way to assign the input data derived from:
b protection functions
b control and monitoring functions
b logic inputs
to the following output data:
b 9 signal lamps on the front panel of Sepam
b output relays
b triggering of disturbance recording.
SFT2841: control matrix.
M
T
1
1
1
0
5
Logical equation editor
(Sepam series 40)
Sepam series 40 includes a logical equation editor which may be used to adapt the
standard control functions to suit various specific cases by programming the
additional functions required.
A logical equation editor groups logic input data derived from:
b protection functions
b logic inputs
using the Boolean operators AND, OR, XOR, NOT, and automation functions such
as time delays, bistables and time programming.
The result of an equation may then be:
b assigned to a logic output, a signal lamp, a message via the control matrix
b transmitted by the communication link, as a new remote indication
b utilized by the circuit breaker/contactor control function to trip, close or inhibit
closing of the breaking device
b used to inhibit or reset a protection function.
The entry of equations is assisted, and a syntax check is carried out systematically.
SFT2841: logical equation editor (series 40).
Alarm and operating messages
(Sepam series 40)
The wording of Sepam alarm and operating messages may be customized using the
SFT2841 software tool.
The new messages are added to the list of existing messages and may be assiged
via the control matrix.
28
Communication
Description and characteristics

With Modbus communication,
Sepam units may be connected to a remote
monitoring and control system equipped
with a master Modbus communication
channel.
To connect Sepam to a communication
network, an interface module is required:
b ACE949-2, interface for connection to a
2-wire RS 485 network
b ACE959, interface for connection to a
4-wire RS 485 network
b ACE937, interface for connection to a
fiber optic communication star system.
Data available
The data available depend on the type of Sepam. All of the data used by the remote
monitoring and control system are grouped together so as to be available in a single
readout.
Readout of measurements and diagnosis information
All of the values measured by Sepam are available in the control room:
b phase and earth fault currents, peak demand currents
b phase-to-phase, phase-to-neutral and residual voltages, frequency
b active and reactive power, peak demand power, accumulated energy
b temperatures
b switchgear diagnosis data: cumulative breaking current, operating time and
number of operations, circuit breaker charging time, etc.
b machine operating assistance data: motor starting time, remaining operating time
before overload tripping, waiting time after tripping, etc.
Remote indications
b reading of digital remote indication data.
Remote indications are preassigned to the protection or control functions and
depend on the type of Sepam.
b reading of the status of 10 logic inputs.
Remote control orders
Writing of 16 pulse-type remote control orders (TC):
b in direct mode
b or in SBO (Select Before Operate) mode.
The remote control orders are preassigned to the metering, protection or control
functions and depend on the type of Sepam.
Time-tagging of events
b time-tagged data: logic inputs, remote indications.
b time-tagging of event within a ms
b synchronization by Modbus network or by external signal received by logic input I21.
Remote setting
b reading of Sepam configuration identification
b reading of protection function settings (remote reading)
b writing of protection function settings (remote setting).
Protection setting writing may be inhibited by parameter setting.
Other functions available via the communication link
b remote control of the MSA141 optional analog output
b transfer of disturbance recording data.
P
E
5
0
0
2
9
ACE949-2 2-wire RS 485 network connection interface.
P
E
5
0
0
2
4
Characteristics
Sepam Modbus communication port
Type of transmission Asynchronous serial
Protocol Modbus
Response time < 15 ms
Maximum number of slaves 25
ACE937 fiber optic connection interface. Data format 10 bits: 1 start, 8 data, 1 stop
or 11 bits: 1 start, 8 data, 1 parity, 1 stop
Parameters
Slave address 1 to 255
Transmission rate 4800, 9600, 19200, 38400 bauds
Parity check None, even, odd
RS 485 electrical interface
Standard EIA 2-wire RS 485 differential (ACE949-2)
EIA 4-wire RS 485 differential (ACE959)
Distributed power supply External, 12 V DC or 24 V DC 10 %
Consumption 16 mA in receiving mode / 40 mA max. in sending mode
Number
of Sepam units
Max. length of RS 485 network
with 12 V DC power supply
Max. length of RS 485 network
with 24 V DC power supply
5 320 m 1000 m
10 180 m 750 m
20 160 m 450 m
25 125 m 375 m
Fiber optic interface
Wavelength 820 Nm (infra-red)
Type of connector ST
Fiber type Multimode glass
Fiber optic
diameter (m)
Numerical
aperture (NA)
Max. attenuation
(dBm/km)
Min. optical power
available (dBm)
Max. length
of fiber (m)
50 / 125 0.2 2.7 5.6 700
62.5 / 125 0.275 3.2 9.4 1800
100 / 140 0.3 4 14.9 2800
200 (HCS) 0.37 6 19.2 2600
29
Communication
Description and characteristics

Connection of the ACE949-2
interface for 2-wire RS 485 networks
Implementation of the Modbus network
M
T
1
1
0
4
8
RS 485 network
A set of adapted accessories is used for fast, dependable implementation of the
communication network from both the electrical and environmental (electromagnetic
compatibility) viewpoints.
M
T
1
0
7
1
2
Network connection interface, to be supplied by 12 V DC or 24 V DC distributed
power supply
b ACE949-2 for 2-wire RS 485 networks
b or ACE959 for 4-wire RS 485 networks.
CCA612 cord for connection of the interface to the C port of the Sepam base
unit.
Interface for connection of the RS 485 network to the Modbus master, with
distributed power supply to the ACE949-2 interfaces and polarization/termination of
the communication link
b ACE909-2, RS 232/2-wire RS 485 converter
b or ACE919CA (110 V AC or 220 V AC) 2-wire RS 485/2-wire RS 485 interface
b or ACE919CC (24 V DC or 48 V DC) 2-wire RS 485/2-wire RS 485 interface.
Modbus network cable
b for 2-wire RS 485 network: two shielded twisted pairs
(1 RS 485 pair, 1 pair for power suuply)
b for 4-wire RS 485 ntework: three shielded twisted pairs
(2 RS 485 pairs, 1 pair for power supply)
b with tinned copper braiding shielding, coverage: > 65%
b characteristic impedance: 120
b gauge: AWG 24
b resistance per unit length: < 100 /km
b capacitance between conductors: < 60 pF/m
b capacitance between conductor and shielding: < 100 pF/m
b maximum length: 1300 m.
Example of standard cable (for 2-wire RS 485 network):
b supplier: BELDEN reference: 9842
b supplier: FILOTEX reference: FMA-2PS.
High-performance cable (for 2-wire RS 485 network):
b supplier: FILECA reference: F2644-1 (cable distributed by Schneider Electric in
60 m strands, reference CCR301).
For more information, refer to the "Sepam - RS 485 network connection guide"
PCRED399074EN.
Fiber optic network
Connection of the ACE959
interface for 4-wire RS 485 networks
M
T
1
1
0
4
9
Rx+, Rx-: Sepam receiving (eq IN+, IN-)
Tx+, Tx-: Sepam transmitting (eq OUT+, OUT-)
D
E
5
0
5
9
0
(1) Distributed power supply with separate wiring or included in
the shielded cable (3 pairs).
(2) Terminal block for connection of the distributed power
supply module.
Connection of the ACE937 fiber optic interface
D
E
5
0
2
7
4
ACE937 fiber optic connection interface.
CCA612 cord for connection of the interface to the C port of the Sepam base
unit.
Optical star.
Fiber optic.
1
2
3
4
1
2
3
4
30
Optional remote modules
Description

M
T
1
0
9
9
6
DSM303 remote advanced UMI module
The DSM303 module provides the same functional features as the fixed advanced
UMI.
Associated with a Sepam with a basic UMI, it may be installed on the front panel of
the cubicle in the most suitable operating location.
b reduced depth of 30 mm
b a single module for each Sepam with a basic UMI, to be connected by one of the
CCA772 or CCA774 prefabricated cords (2 or 4 meters). This module may not be
connected to Sepam units with integrated advanced UMIs.
DSM303 remote advanced UMI module.
M
T
1
1
0
0
9
MSA141 analog output module
The MSA141 module converts Sepam measurements into analog signals.
b selection of the measurement to be converted by parameter setting
b 0-10 mA, 4-20 mA or 0-20 mA analog signal according to parameter setting
b connection of the analog output to a screw-type connector:
v 1 wire with cross-section 0.2 to 2.5 mm (u AWG 24-12)
v or 2 wires with cross-section 0.2 to 1 mm (u AWG 24-16)
b a single module for each Sepam base unit, to be connected to one of the CCA770,
CCA772 or CCA774 prefabricated cords (0.6, 2 or 4 meters).
MSA141 analog output module.
M
T
1
1
0
1
0
MET148-2 temperature sensor module
Temperature measurement (e.g. in transformer or motor windings) is utilized by the
following protection functions:
b thermal overload (to take into account the ambient temperature)
b temperature monitoring.
With the MET148-2 module, 8 temperature sensors may be connected.
b type of temperature sensor Pt100, Ni100 or Ni120 according to parameter setting
b 3-wire temperature sensors
b connection of temperature sensors to screw-type connectors:
v 1 wire with cross-section 0.2 to 2.5 mm (u AWG 24-12)
v or 2 wires with cross-section 0.2 to 1 mm (u AWG 24-16)
b a single module for each Sepam series 20 base unit, to be connected to one of the
CCA770, CCA772 or CCA774 prefabricated cords (0.6, 2 or 4 meters)
b 2 modules for each Sepam series 40 base unit, to be connected to one of the
CCA770, CCA772 or CCA774 prefabricated cords (0.6, 2 or 4 meters).
MET148-2 temperature sensor module.
31
Optional remote modules
Connections

Connection of DSM303
remote advanced UMI
Wiring of inter-module links
Different module connection combinations are possible and the modules are
connected by prefabricated cords which come in 3 different lengths:
b CCA770 (L = 0.6 m)
b CCA772 (L = 2 m)
b CCA774 (L = 4 m).
The modules are linked by cords which provide the power supply and act as
functional links with the Sepam unit (D connector to Da connector Da, Dd to Da, ...).
The DSM303 module may only be connected at the end of the link.
M
T
1
0
7
1
3
Connection of MSA141
remote analog output
D
E
5
0
6
1
0
M
T
1
0
7
1
4
Connection of the MET148-2
8 temperature sensor inputs
M
T
1
0
7
1
5
Maximum configuration
Three modules at the most may be connected to the base unit in accordance with the
order and maximum lengths of connections specified in the chart below:
Base Cord Module 1 Cord Module 2 Cord Module 3
series 20 CCA772 MSA141 CCA770 MET148-2 CCA774 DSM303
series 40 CCA772 MSA141 CCA770 MET148-2 CCA774 DSM303
series 40 CCA772 MSA141 CCA770 MET148-2 CCA772 MET148-2
series 40 CCA772 MET148-2 CCA770 MET148-2 CCA774 DSM303
32
Sensors
LPCT type current sensors

M
T
1
1
0
0
3
CLP1 LPCT sensors
CLP1 sensors are voltage-output current sensors of the Low Power Current
Transducer (LPCT) type, compliant with the IEC 60044-8 standard.
CLP1 sensors are designed to measure rated currents between 25 A and 1250 A,
with a ratio of 100 A / 22.5 mV, and may be used on networks with a maximum of
17.5 kV.
The secondary winding of the CLP1 sensor is pre-equipped with a 5-m long shielded
cable fitted with an RJ45 connector, which is connected to the 9-pin sub-D connector
on Sepam via a CCA670 interface connector, mounted on the rear panel of the
Sepam base unit.
Characteristics
Rated primary current 100 A
Rated secondary voltage 22.5 mV
Rated primary extended current 1250 A
Measurement accuracy class 0.5 0.5 % between 100 and 1250 A
0.75 % at 20 A
1.5 % at 5 A
Protection accuracy class 5P
Rated accuracy limit primary current 40 kA
CLP1 sensor. Accuracy burden u 2 k
Rated thermal short-circuit current 31.5 kA x 4 s - 40 kA x 3 s
Rated voltage (Um) 17.5 kV
Rated power frequency withstand voltage 38 kV - 42 kV
Rated lightning impulse withstand voltage 95 kV
Weight 8 kg
ACE917 injection adapter
D
E
5
0
6
9
3
The ACE917 adapter is used to test the protection chain with a standard injection
box, when Sepam is connected to LPCT sensors.
The ACE917 adapter is inserted between:
b the standard injection box
b the LPCT test plug:
v integrated in the Sepam CCA670 connector
v or transferred by means of the CCA613 accessory.
The following are supplied with the ACE917 injection adapter:
b 220 V AC power supply cord
b 3-meter ACE917 / LPCT test plug on CCA670 or CCA613 connection cord.
Accessory connection principle.
CCA613 remote test plug
The CCA613 test plug, panel-mounted on the front of the cubicle and fitted with a 3-
meter cord, is used to transfer data from the integrated test plug to the CCA670
interface connector on the rear panel of Sepam.
M
T
1
1
0
2
2
M
T
1
1
0
5
6
M
T
1
1
0
2
8
Front view with cover lifted. Right side view. Cutout.
B
67,5
44
69
46
33
Sensors
Core balance CTs

M
T
1
0
3
1
5
CSH120, CSH200 core balance CTs
The specifically designed CSH120 and CSH200 core balance CTs are used for direct
residual current measurement. The only difference between them is the diameter.
Characteristics:
b accurancy: 5% at 20C
b transformation ratio: 1/470
b maximum permissible current: 20 kA - 1 s
b operating temperature: - 25C to +70C
b storage temperature: - 40C to +85C
b drift in accuracy related to temperature: 1%
b the wiring resistance should be < 4 .
CSH120 and CSH200 core balance CTs.
M
T
1
1
0
5
7
Dimensions (mm) Weight
(kg)
A B D E F H J K L
CSH120 120 164 44 190 76 40 166 62 35 0.6
CSH200 200 256 46 274 120 60 257 104 37 1.4
M
T
1
1
0
5
8
CSH30 interposing ring CT
The CSH30 interposing ring CT is used as an interface when the residual current is
measured using 1 A or 5 A current transformers.
It should be installed near the Sepam input (L < 2 m).
b weight: 0.12 kg
b mounted on symmetrical DIN rail.
M
T
1
0
7
2
0
ACE990 core balance CT interface
The ACE990 interface is used to adapt measurements between a MV core balance
CT with a ratio of 1/n (50 y n y 1500), and the Sepam residual current input.
Characteristics
b weight: 0.64 kg
b mounted on symmetrical DIN rail
b accuracy:
v amplitude: 1%
v phase: < 2
b maximum permissible current: 20 kA 1 s (on the primary winding of a
MV core balance CT with a ratio of 1/50 that does not saturate)
b operating temperature: -5C to +55 C.
b storage temperature: -25 C to +70 C.
34
Characteristics
Size and weight
Sepam base unit
Front panel-mounted
Top view Side view Cutout
M
T
1
1
0
5
9
M
T
1
1
0
6
0
M
T
1
1
0
6
1
Mounting shown with advanced UMI and optional MES114
module.
Weight series 20 =1.2 kg without option.
1.7 kg with option.
Weight series 40 =1.4 kg without option.
1.9 kg with option.
Mounting plate thickness < 3 mm.
Cutout accuracy must be complied with to ensure good
Sepam mechanical withstand.
M
T
1
1
0
6
2
"Terminal block" mounting with AMT840 plate
Used to mount Sepam at the back of the compartment
with access to the connectors on the rear panel.
Mounting associated with the use of the remote
advanced UMI (DSM303).
35
Characteristics
Size and weight

DSM303 module
b Weight: 0.3 kg
Cutout for panel-mounting (mounting plate thickness < 3 mm)
Side view Cutout
D
E
5
0
6
9
2
M
T
1
1
0
6
3
M
T
1
1
0
6
4
ACE949-2 module
b weight: 0.1 kg
b mounted on symmetrical DIN rail
ACE959 module
b weight: 0.25 kg
b mounted on symmetrical DIN rail
ACE937 module
b weight: 0.1 kg
b mounted on symmetrical DIN rail
M
T
1
0
7
2
5
M
T
1
0
7
2
6
D
E
5
0
6
8
5
MET148-2 module
b weight: 0.2 kg
b mounted on symmetrical DIN rail
MSA141 module
b weight: 0.2 kg
b mounted on symmetrical DIN rail
M
T
1
0
7
2
7
M
T
1
0
7
2
8

(1) Depth with CCA77x connection cord: 70 mm.
36
Characteristics
Electrical characteristics

Analog inputs
Current transformer input impedance < 0.001
1 A or 5 A CT (with CCA630) consumption < 0.001 VA at 1 A
1 A to 6250 A ratings < 0.025 VA at 5 A
rated thermal withstand 3 In
1-second overload 100 In
Voltage transformer input impedance > 100 k
220 V to 250 kV ratings input voltage 100 to 230/3 V
rated thermal withstand 230 V (1.7 Unp)
1-second overload 480 V (3.6 Unp)
Temperature sensor input (MET148-2 module)
Type of sensor Pt 100 Ni 100 / 120
Isolation from earth none none
Current injected in sensor 4 mA 4 mA
Logic inputs MES114 MES114E MES114F
Voltage 24 to 250 V DC 110 to 125 V DC 110 V AC 220 to 250 V DC 220 to 240 V AC
Range 19.2 to 275 V DC 88 to 150 V DC 88 to 132 V AC 176 to 275 V DC 176 to 264 V AC
Frequency - - 47 to 63 Hz - 47 to 63 Hz
Typical consumption 3 mA 3 mA 3 mA 3 mA 3 mA
Typical switching threshold 14 V DC 82 V DC 58 V AC 154 V DC 120 V AC
Control output relays (O1, O2, O11 contacts)
Voltage DC 24 / 48 V DC 127 V DC 220 V DC
AC (47.5 to 63 Hz) - - - 100 to 240 V AC
Rated current 8 A 8 A 8 A 8 A
Breaking capacity resistive load 8 / 4 A 0.7 A 0.3 A
L/R load < 20 ms 6 / 2 A 0.5 A 0.2 A
L/R load < 40 ms 4 / 1 A 0.2 A 0.1 A
resistive load - - - 8 A
p.f. load > 0.3 - - - 5 A
Making capacity < 15 A for 200 ms
Indication output relays (O3, O4, O12, O13, O14 contacts)
Voltage DC 24 / 48 V DC 127 V DC 220 V DC
AC (47.5 to 63 Hz) - - - 100 to 240 V AC
Rated current 2 A 2 A 2 A 2 A
Breaking capacity L/R load < 20ms 2 / 1 A 0.5 A 0.15 A
p.f. load > 0.3 - - - 1 A
Power supply Sepam series 20
range deactivated consumption
(1)
max. consumption
(1)
inrush current
24 / 250 V DC -20% +10% 2 to 4.5 W 6 to 8 W < 10 A for 10 ms
110 / 240 V AC -20% +10% 3 to 9 VA 9 to 15 VA < 15 A for 1
st
half-period
47.5 to 63 Hz
brownout withstand 10 ms
Power supply Sepam series 40
range deactivated consumption
(1)
max. consumption
(1)
inrush current
24 / 250 V DC -20% +10% 3 to 6 W 7 to 11 W < 28 A 100 s
110 / 240 V AC -20% +10% 3 to 6 VA 9 to 25 VA < 28 A 100 s
47.5 to 63 Hz
brownout withstand 20 ms
Analog output (MSA141 module)
Current 4 - 20 mA, 0 - 20 mA, 0 - 10 mA
Load impedance < 600 (wiring included)
Accuracy 0.50%
(1) According to configuration.
37
Characteristics
Environmental characteristics

Electromagnetic comptability IEC / EN standard Level / Class Value
Emission tests
Disturbing field emission EN 55022 / CISPR22 A
Conducted disturbance emission EN 55022 / CISPR22 B
Immunity tests Radiated disturbances
Immunity to radiated fields 60255-22-3 / 61000-4-3 III 10 V/m
Electrostatic discharge 60255-22-2 / 61000-4-2 III 8 kV air
6 kV contact
Immunity tests Conducted disturbances
Immunity to conducted RF disturbances 61000-4-6 III 10 V
Fast transient bursts 60255-22-4 / 61000-4-4 IV
1 MHz damped oscillating wave 60255-22-1 III 2.5 kV MC
1 kV MD
Impulse waves 61000-4-5 III
Voltage interruptions 60255-11 series 20: 100 % 10 ms
series 40: 100 % 20 ms
Mechanical robustness IEC / EN standard Level / Class Value
In operation
Vibrations 60255-21-1 2 1 Gn
Shocks 60255-21-2 2 10 Gn / 11 ms
Earthquakes 60255-21-3 2
De-energised
Vibrations 60255-21-1 2
(1)
2 Gn
Shocks 60255-21-2 2
(1)
30 Gn / 11 ms
Jolts 60255-21-2 2
(1)
20 Gn / 16 ms
Climatic withstand IEC / EN standard Level / Class Value
In operation
Exposure to cold 60068.2.1 series 20: Ab
series 40: Ad
-25 C
Exposure to dry heat 60068.2.2 series 20: Bb
series 40: Bd
+70 C
Continuous exposure to damp heat 60068.2.3 Ca 93 % RH; 40 C
10 days
Temperature variation with specified variation rate 60068.2.14 Nb 25 C +70 C
5 C/min
Salt mist 60068-2-52 Kb / 2
Influence of corrosion 60654-4 Clean industrial air
In storage
(4)
Exposure to cold 60068.2.1 Ab -25 C
Exposure to dry heat 60068.2.2 Bb +70 C
Continuous exposure to damp heat 60068.2.3 Ca 93 % RH; 40 C
56 days
Safety IEC / EN standard Level / Class Value
Enclosure safety tests
Front panel tightness 60529 IP52 Other panels closed, except for
rear panel IP20
NEMA Type 12
with gasket supplied
Fire withstand 60695-2-11 650 C with glow wire
Electrical safety tests
Earth continuity 61131-2 30 A
1.2/50 s impulse wave 60255-5 5 kV
(2)
Power frequency dielectric withstand 60255-5 2 kV 1 mn
(3)
Certification
e Harmonized standards:
b Series 20: EN 50081-2
b Series 40: EN 50263
European directives:
b 89/336/EEC Electromagnetic Comptability (EMC) Directive
v 92/31/EEC Amendment
v 93/68/EEC Amendment
b 73/23/EEC Low Voltage Directive
v 93/68/EEC Amendment
UL - UL508 - CSA C22.2 n 14-95 File E212533
CSA CSA C22.2 n 14-95 / n 94-M91 / n 0.17-00 File 210625
(1) Results given for intrinsic withstand, excluding support equipment
(2) Except for communication: 3 kV in common mode and 1kV in differential mode
(3) Except for communication: 1 kVrms
(4) Sepam must be stored in its original packing.
38
Notes
39
Notes
40
Notes
07897411FR - REV. A0 - 1 Schneider Electric
YFJYVIIVGIT
Schneider Electric Industries SAS
Postal address:
Electrical Distribution Communication
F - 38050 Grenoble cedex 9
France
Tel : +33 (0)4 76 57 60 60
http://www.schneider-electric.com
http://www.sepamrelay.com
As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.
This document has been printed
on ecological paper.
Design: Ameg
Publication: Schneider Electric
Printed:
04-2003 ART.08535
P
C
R
E
D
3
0
1
0
0
4
E
N
/
2


2
0
0
3


S
c
h
n
e
i
d
e
r

E
l
e
c
t
r
i
c

-

A
l
l

r
i
g
h
t

r
e
s
e
r
v
e
d
Order form
Sepam series 20
Sepam series 40

To make it easier for you to choose your equipment and fill in your order form, it is
advisable to use the Schneider Electric electronic catalogue (please consult us)
or to attach this page to your order, indicating the requested quantities in the spaces
and checking off the boxes that correspond to your choices.
Base units Additional modules and accessories
Sepam series 20 Input / output modules
Type User-Machine Quantity Designation Reference Quantity
of application Interface 10 inputs + 4 outputs module (24-250 V DC) MES114
S20 basic 10 inputs + 4 outputs module (110-125 V DC and V AC) MES114E
advanced 10 inputs + 4 outputs module (220-250 V DC and V AC) MES114F
T20 basic Remote modules and connection cords
advanced Designation Reference Quantity
M20 basic 8 temperature sensor module MET148-2
advanced Analog output module MSA141
B21 basic Remote advanced UMI module DSM303
advanced Remote module connection cord L = 0.6 m CCA770
B22 basic Remote module connection cord L = 2 m CCA772
advanced Remote module connection cord L = 4 m CCA774
Working language Mounting plate AMT840
English / French Communication accessories
English / Spanish Designation Reference Quantity
English / Local
(1)
2 wire, RS 485 network interface, without CCA612 cord ACE949-2
Type of phase current sensor 4-wire, RS 485 network interface, without CCA612 cord ACE959
(for S20, T20 and M20) Fiber optic interface, without CCA612 cord ACE937
1 A / 5 A CT Network interface connection cord L = 3 m CCA612
LPCT RS 232/RS 485 converter ACE909-2
Type of main connector RS 485/RS 485 interface (AC) ACE919CA
Screw-type connector RS 485/RS 485 interface (DC) ACE919CC
Ring lug connector Core balance CTs
Sepam series 40 Designation Reference Quantity
Type User-Machine Quantity Residual current sensor (diameter 120) CSH120
of application Interface Residual current sensor (diameter 200) CSH200
S40 basic Interposing ring CT for residual current input CSH30
advanced Core balance CT interface ACE990
S41 basic LPCT phase current sensors
advanced Designation Reference Quantity
S42 basic LPCT phase current sensor CLP1
advanced LPCT injection adapter ACE917
T40 basic Remote LPCT test plug CCA613
advanced Software tools and documentation
T42 basic Designation Reference Quantity
advanced PC parameter setting and operation software kit
with CCA783 cord
SFT2841 kit
M41 basic
advanced Notice dutilisation Sepam srie 20 PCRED301005FR
G40 basic Sepam series 20 users manual PCRED301005EN
advanced Notice dutilisation Sepam srie 40 PCRED301006FR
Working language Sepam series 40 users manual PCRED301006EN
English / French
English / Spanish
English / Local
(1)

Type of phase current sensor
1 A / 5 A CT
LPCT
Type of connectors and
Screw-type connector
Ring lug connector
(1) Please consult us.
A
A E