Hasil pengukuran Total Harmonics Distortion

Lokasi : ER 57 Tools : Fluke 434 Power Quality Analyzer

Hari/Tgl : Rabu / 14-11-2012 Jam : 11:30 s/d 12:15 WITA

Point Pengukuran : Input VFD 544FN04 (690 VAC) LINE L1 L2 L3 VOLTAGE THD (%) 5.5 5.3 5.3 CURRENT THD (%) 43.0 44.6 44.6

Point Pengukuran : Output VFD 544FN04 (690 VAC) LINE L1 L2 L3 VOLTAGE THD (%) 11.8 11.0 11.1 CURRENT THD (%) 9.5 9.3 8.9

LAMPIRAN : Input VFD 544FN04

Output VFD 544FN04

Hasil pengukuran Total Harmonics Distortion

Lokasi : ER 57 Tools : Fluke 434 Power Quality Analyzer

Hari/Tgl : Rabu / 14-11-2012 Jam : 11:30 s/d 12:15 WITA

Point Pengukuran : Input 582ER57LV04 (690 VAC) LINE L1 L2 L3 VOLTAGE THD (%) 4.8 4.9 4.9 CURRENT THD (%) 40.3 40.3 40.8

Point Pengukuran : Input 582ER57LV02 (400 VAC) LINE L1 L2 L3 VOLTAGE THD (%) 1.6 1.6 1.7 CURRENT THD (%) 2.8 3.2 3.2