You are on page 1of 4

Doc. No.

Ver: 1.01 Rev: 1

CB Link

FS -8700-23

DESCRIPTION

The CB-Link driver allows the FieldServer to transfer data to and from devices over RS-485 using CB-Link protocol. Refer to Model 833-2771 CB-Link Manual #65-0216 and Model 833-2757 General Purpose Interface ControlBus Module Manual #65-0220 from Cleaver Brooks. Command/SubCommand Supported:

FORMAL DRIVER TYPE

Serial Server Only

COMPATIBILITY MATRIX
Compatible with this driver Yes Yes No Yes Yes No No No No No No

FieldServer Model FS-x2010 FS-x2011 FSx25 FS-x30 FS-x40 SlotServer ProtoNode ProtoCessor FPC-FO2 ProtoCessor FPC-FD2 QuickServer FS-QS-1010 QuickServer FS-QS-1011

CONNECTION INFORMATION
Connection type: Baud Rates: Parity: Parity: Multidrop Capability RS-485 (Two wire, Half-Duplex) 9600 (Vendor Limitation) None (Vendor Limitation) None (Vendor Limitation) Yes

DEVICES TESTED
Tested (FACTORY, SITE) SITE

Device Cleaver Brooks Hawk, EC78XX Honeywell Link

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 1 of 4

Doc. No.

Ver: 1.01 Rev: 1

CB Link

FS -8700-23

CONNECTION CONFIGURATIONS
CLEAVER BROOKS MODEL 833-2771 CB LINK or HONEYWELL Q7700 NETWORK INTERFACE UNIT

833-2425

833-2757

AKA: ASCII INTERFACE EMS INTERFACE BDI CARD QS7850 GPI (GENERALPURPOSE INTERFACE)

FURTHER CB-LINKS

SLOT

6 A B C

C1

C2

POSSIBLE DEVICES BCS7700 CB-HAWK RM7800 RM7800 QS7X00X PULSATROL, Q7700 BURNER CONTROL BURNER CONTROL BURNER CONTROL EXPANDED ANNUNCIATOR CARDS (QM40XX, TRAPSCAN) NETWORK INTERFACE. etc

RS485 9600 N81

CONFIG PC (RUISYS)

RS-485 Opto Isolated

Gnd _ + FG Gnd _ +

CB HAWK

FieldServer

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 2 of 4

Doc. No.

Ver: 1.01 Rev: 1

CB Link

FS -8700-23

COMMUNICATIONS FUNCTIONS - SUPPORTED FUNCTIONS AT A GLANCE:

The FieldServer can accept any information transmitted by the CB Hawk, including: Program, operate, auto, man, rem modes Flame failure Gas pressure Sensor high/low Fuel selection Atomizing air off Steam pressure, water temperature, oil pressure sensor information Lockout and pre-ignition interlock AC line frequency Excess AC line noise Damper motor Replace battery Fuel selection, recycle limits, oil pressure, oil temperature, lockout/interlock, open oil drawer hold Standby, prepurge, pilot ignition, fuel change, main ignition, run, post purge, safety shutdown Low fire cutoff, flame detected, test switch, damper motor holds Call CB service.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 3 of 4

Doc. No.

Ver: 1.01 Rev: 1

CB Link

FS -8700-23

DEVICE INFORMATION TABLE

NETWORK INTERFACE UNIT MAKE MODEL NAME Honeywell Q7700 Network Interface Unit Cleaver Brooks 833-2771 CB-Link CONTROL MODULES MAKE MODEL No. OF MODULE NAME MODULE BCS7700 7800 SERIES Control QM40XX Data Acquisition Module Trapscan System PulsaFeeder PULSAtrol S7830 Expanded Annunciator S7800 Keyboard/Display Module ST7800 Relay Module RM7800E,G,L,M Relay Modules RM7840E,G,L,M Relay Modules Q7700A,B Display Module Data Control Module CB 783 CB 780 CB 784 N/A Bus N/A ON REQUEST ON REQUEST ON REQUEST N/A N/A ON REQUEST ON REQUEST ON REQUEST Requires 833-2727 or 833-2729 on module PROPERTY FILE CONFIGURATION NAME (.BP1;.BP2) NAME (.CSV) N/A N/A ON REQUEST ON REQUEST PULSA S7830 S7800 ST7800 RM78XX RM78XX RM78XX RM78XX N/A N/A QM40XX ON REQUEST PULSA S7830 S7800 Requires S7800 module Expanded Annunciator Data Modules Acquisition FILE NOTES

Honeywell QS7700A Honeywell QS7800A Honeywell QS7800C Armstrong QS7800D Honeywell QS7800E Honeywell QS7800A Honeywell QS7800A Honeywell QS7800A Honeywell Honeywell Honeywell N/A CB-Link 833-2727 CB-Link CB-Link CB-Link CB-Link 833-2729 833-2734 833-2734 833-2734

Note: SYSNet is the generic name for networks of the listed modules. Controlbus is the generic name for the networks in a NIM/CBLink configuration

This is the chassis that the above modules plug into FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 4 of 4