PROTECTION SYSTEM:

FAIL

FAIL

FAIL
BB Protection

RE OC/EF Td=450-500ms

RE Z2 Td= 400ms

LE Z2 P-E + CR Td= 0ms

RE Z1 Td= 0ms

LE Z3 Td= 400ms MZ + CZ OPERATE

LE Z1 P-E Td= 0ms

LE Z2 P-E + CR Td= 0ms

LE Z2 P-P Td= 400ms

LE Z3 Td= 700ms

LE Z4(Rev) Td= 300ms

SOTF

LE OC/EF Td=450-500ms

CONCERNED TRIP BUS OPERATE

Re-initiation

86-2 SR 1 Ph TR

86-1 ER/HR 3 PH TR

96 OPERATE

Re-initiation

CB TRIP INITIATE

PERMISSIVE

I/L

A/R INITIATE

LBB INITIATE

NON PERMISSIVE

CB TRIPS30 ms

CB STUCK-UP

TIME DELAY200 ms

AR In Service

AR Out of Service

PDR Operates Td=1.5 sec (AR)

ARC QUENCHINGD.T- 1 sec

Reclose is Attempted

Elec Problem

Mech Problem

FAULT PERSISTS

FAULT CLEARS

Current Greater Than LBB Setting

LBB SCHEME RESET

FAULT CLEARS

FAULT PERSISTS

Failure of Relay To Issue a Trip Command to A Phase.

Trip Ckt Faulty


LBB Operate

Reclose Sucessful

CB Trips Reclose unsucessful

Bkr Trips On PDR

1 Shot
R.T- 25 sec

Multi R.T- 25 s Shot

AR L/O

Fault Reoccurs