You are on page 1of 1

GUARENTEED TECHNICAL PERTICULARS

S. No. 1 2 3 4 5 6 7 8 9 10 11 PARAMETERS Battery Type Model Offered Battery Rating Overall Cell Dimension ( L x W x H ) Overall Cell Weight (approximately) Number of cells per battery bank Applicable standards Compliance Capacity Rated at Ah efficiency Wh efficiency Recommended float voltage condition Terminal voltage of charger Float charging current at 2.25V/Cell Recommended boost charging condition for quick charging at 27degreeC Design Float Life Design Cyclic Life Self Discharge Grid alloy Container & Lid material Sealing Method Safety Vent Ventilation Plate type Seperator Terminals & Inter Cell Containers Type of nuts, bolts & washers Terminals Torque Setting Battery rack type 48 V / 600 AH Battery Details Valve-Regulated Lead-Acid Battery ELT - 600 48V - 600AH (24Cells) 267mm X 166mm X 354mm (+/-10mm) 38 kg 24 IEC - 60896 2 GR BAT - 01/03 MAR 2004 Amendment-1 dt.05/01/05 10 Hrs to 1.75 ECV @ 27 * Celsius Min. 95% Min. 86% 2.25V/Cell Constant Potential with Maximum current to be limited to 20% of the rated AH 2.30V/ Cell 20 years at 27* Celsius on float under recommended charging 1200 cycles @ 80% DOD & 4000 cycles @ 20% DOD < 0.5% per week at 27degreeC High Tin Low Calcium Alloy ( HTLC) ABS Leak proof heat sealing Self Resealing Explosion Proof Pressure Regulated Safety Valve Natural Air Cooling Flat Pasted Type AGM ( Absorbent Glass Mat ) Lead Plated Brass & Lead Plated Copper Acid Resistant Stainless Steel 11 NM Acid resistant powder coated steel enclosure with CRCA channels

12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

You might also like