You are on page 1of 11

MEDIUM VOLTAGE DIN Fuse-Links

24kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps

MV DIN

Standards/Approvals: DIN 43625, VDE 0670 part 4, VDE 0670 part 402 and IEC 60282-1 (2005) Catalogue Symbol: 24TDMEJ(amp) 24THMEJ(amp) 24TFMEJ(amp) 24TXMEJ(amp) Back-up as IEC 60282-1 (2005)
A C D Weight (Kg) 2.5 3.7 5.1 5.9

Description:

Class of Operation: Dimensional Data:


Fuse Reference TDMEJ THMEJ TXMEJ TFMEJ

Packaging:

A range of medium voltage DIN Fuses, complete with sealed striker, suitable for transformer protection. The fuses can be used even where there is no secondary LV protection, provided they are used with fuse switches fitted with instantaneous striker tripping. All fuse-links are packed individually. MOQ: 3 Packaging 100% recyclable

442 442 442 442

54 67 80 88

51 64 76 88

EJ Outline

Technical Data: DIN fuse-links 10kV - 24kV Rated voltage: Amps: 6.3A to 160A Rated breaking capacity: 50kA to 63kA Rated frequency: 50 Hz Suitable for outdoor and indoor use RoHS compliant

Striker Diagram:

E = Spring Striker 80N to IEC 60282-1 designation medium


Force x Travel diagram for 80N Din striker

100 90 80 70 60 50 40 30 20 10 0 0 4

Force (N)

12

16

Travel (mm)

20

24

28

32

36

Form No. 24kV DIN Page 1 of 11 Data sheet 720106

MEDIUM VOLTAGE DIN Fuse-Links


Table of Ratings:
Standard Approvals: Technical Data:
Part Number 24TDMEJ6.3 24TDMEJ10 24TDMEJ16 24TDMEJ20 24TDMEJ25 24TDMEJ40 24TDMEJ50 24THMEJ63 24TFMEJ80 24TFMEJ100* 24TXMEJ125* 24TXMEJ160* 24TDMEJ31.5

24kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps


DIN 43625, VDE 0670 part 4, VDE 0670 part 402 and IEC 60282-1 (2005) 6.3, 10, 16, 20. 25, 31.5, 40, 50, 63, 80, 100, 125 and 160 Amps
Breaking Capacity I1 (kA) 50 50 50 50 50 50 50 50 50 50 63 31.5 40 Minimum Breaking Capacity I3 (A) 23 34 56 73 92 118 92
Cold Resistance & Watts Loss in Free Air

MV DIN

Current Rating In (A) 6.3 10 16 20 31.5 40 50 63 100 125 160 80 25

Joule Integral (I2t)


Minimum PreArcing

Length mm 442 442 442 442 442 442 442 442 442 442 442 442 442

Diameter mm 51 51 51 51 51 51 51 51 64 76 76 88 88

Weight kg

444 262 78.2 62.4 46.8 34.3 27.0 21.1 15.7 18.0 9.60 11.0 109

20 32 34 38 49 59 79 127 153 400 340 515 98

9.8 X 101 2.8 X 102 2.6 X 102 5.2 X 102 8.1 X 102 1.4 X 103 2.4 X 103 2.8 X 103 4.3 X 103 7.9 X 103 2.8 X 104 9.7 X 104

1.0 X 103 2.3 X 103 3.9 X 103 5.4 X 103 8.4 X 103 1.5 X 104 2.5 X104 3.1 X 104 4.7 X 104 9.1 X 104 9.4 X 104 3.5 X 105 5.0 X 105

Maximum Operating

2.5 2.5 2.5 2.5 2.5

2.5 2.5 2.5 3.7 5.1

185 217 265 430 760 900

5.1 5.9 5.9

Cross-Reference
24TDMEJ6.3 24TDMEJ10 24TDMEJ16 24TDMEJ20 24TDMEJ25 24TDMEJ31.5 24TDMEJ40 24TDMEJ50 24THMEJ63 24TFMEJ80 67140.0060 67140.0100 67140.0160 67140.0200 67140.0250 67140.0320 67140.0400 67140.0500 67140.0630 67140.0800 67240.1000 67240.1250 67240.1600

* Not compliant with VDE 0670 part 402

1.3 X 105

MESA 3000613 3000613 3000613 3000613 3000613 3000613 3000613 3001413 3001413 3001413 3002213 3002213 N/A CF-24/6,3 CF-24/10 CF-24/16 CF-24/20 CF-24/25 CF-24/31.5 CF-24/40 CF-24/50 CF-24/63 CF-24/80

(80N Striker) 4256005 4256006 4256007 4256008 4256009 4256010 4256011 4253012 4253013 4253014

(50N Striker) 4255005 4255006 4255007 4255008 4255009 4255010 4255011 4255012 4255013 4255014

51006 538 M0 51006 539 M0 51006 540 M0 51006 541 M0 51006 542 M0 51006 543 M0 51006 544 M0 51006 545 M0 51006 546 M0 51006 547 M0

ES 6513-006 ES 6513-010 ES 6513-016 ES 6513-020 ES 6513-025 ES 6513-030 ES 6513-040 ES 6513-050 ES 6513-063 ES 6513-080

IB-D1 IB-D1 IB-D1 IB-D1 IB-D1 & IB-D2 IB-D1 & IB-D2 IB-D1 & IB-D2 IB-D2 IB-D2 IB-D3

1YMB531044M0001 1YMB531044M0002 1YMB531044M0003 1YMB531044M0004 1YMB531004M0004 1YMB531004M0012 1YMB531004M0005 1YMB531004M0021 1YMB531004M0022 1YMB531022M0001

Watts Loss Comparison


Lowest Watts Loss

24TFMEJ100 24TXMEJ125 24TXMEJ160

CF-24/100 N/A N/A

4253015 4253016 N/A

4255015 4255016

51006 548 M0 N/A N/A

ES 6513-100 N/A N/A

IB-D3 N/A N/A

1YMB531022M0002 1YMB531022M0003 N/A

24TDMEJ6.3 24TDMEJ10 24TDMEJ16 24TDMEJ20 24TDMEJ25 24TDMEJ31.5 24TDMEJ40 24TDMEJ50 24THMEJ63 24THMEJ80

Part Number

Watts Loss 20 32 34 38 49 59 79

Watts Loss 32 48 43 53 64 85 103

Watts Loss 31 52 59 46 56 72 106

MESA Watts loss 25 31 58 67 79 96 119

Watts Loss 29 19 33 47 61 81 97

Watts Loss 25 31 58 67 79 96 119

Watts Loss 38 36 70 73 78 83 113

Watts Loss 20 42 57 60 64 77 115

Watts Loss 91 62 72 61 79 98 106

24TFMEJ100 24TXKMEJ125 24TXMEJ160

99 127 155 400 340 515

146 163 196 400 340 515

108 132 174 234 320

136 144 200 240

81 125 151

228 301

136 144 200 240 -

148 178 215 224 -

112 140 225 260 -

130 147 165

186 234 -

Form No. 24kV DIN Page 2 of 11 Data sheet 720106

Time Current Curves

10000
CURVES RELATE TO MEAN PRE_ARCING TIMES WITH A TOLERANCE OF 10% ON CURRENT

TIME- CURRENT CHARACTERISTIC FOR 24kV FUSE-LINKS

FUSE TYPES: TFM / TXM

1000 100A 125A 160A

100

MEDIUM VOLTAGE DIN Fuse-Links

10

VIRTUAL PRE-ARCING TIME IN SECONDS

24kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps

0.1

0.01
DRN MPJ

10
DATE APPD 10/4/07

100000

DRN

DATE

DRN

APPD

DATE

APPD

100 1000 10000 R.M.S. SYMMETRICAL PROSPECTIVE CURENT IN AMPERES B


RE-DRAWN IN EXCEL. ECN11268
BURTON-ON-THE-WOLDS LEIC, LE12 5TH, UK. TEL. 01509 882600 FAX 01509 882768

PF 1236

MV DIN

Form No. 24kV DIN Page 3 of 11 Data sheet 720106

Time Current Curves

10000
CURVES RELATE TO MEAN PRE_ARCING TIMES WITH A TOLERANCE OF 10% ON CURRENT

TIME- CURRENT CHARACTERISTIC FOR 24kV FUSE-LINKS

FUSE TYPES: TDM/THM/TFM

1000

63A 50A 40A 31.5A 20A 16A 10A 6.3A 25A

80A

100

MEDIUM VOLTAGE DIN Fuse-Links

10

VIRTUAL PRE-ARCING TIME IN SECONDS

24kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps

0.1

0.01 100 1000

10

DRN DATE APPD 21/3/07

DATE

MPJ

APPD

6/4/07

MBC ADDED ECN11268 1st ISSUE ECN11220

C B
DRN HH

DRN

DATE

MPJ

R.M.S. SYMMETRICAL PROSPECTIVE CURENT IN AMPERES

10000

100000

APPD

26/3/07

Update ECN11237

BURTON-ON-THE-WOLDS LEIC, LE12 5TH, UK.

TEL. 01509 882600 FAX 01509 882786

PF 1276

MV DIN

Form No. 24kV DIN Page 4 of 11 Data sheet 720106

MEDIUM VOLTAGE DIN Fuse-Links


Cut-Off Curves

24kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps

MV DIN

REF. No. PF 2276

100000

NOTES 1. CURVES SHOW EXTREME MAXIMUM VALUES WHICH WILL NOT BE EXCEEDED UNDER CONDITIONS STATED IN 2 AND 3 BELOW. 2. FOR HIGH VALUES OF PROSPECTIVE CURRENT A SYMMETRICAL FAULT GIVES THE HIGHEST CUT-OFFCURRENT. FOR LOW VALUES OF PROSPECTIVE CURRENT, WHERE THERE IS LITTLE OR NO CURRENT LIMITATION, AN ASYMMETRICAL FAULT PASSES THE HIGHEST PEAKCURRENT. THE CURVES ARE THEREFORE BASED ON THE DEGREE OF ASYMMETRY WHICH GIVES THE MAXIMUM CUT-OFF CURRENT AT ANY PARTICULAR VALUE OF PROSPECTIVE CURRENT. 3. CURVES RELATE TO FREQUENCY OF 50 Hz AND A RECOVERY VOLTAGE EQUAL TO THE FUSE RATED VOLTAGE.

CUT-OFF CURRENT CHARACTERISTIC FOR 24kV FUSE-LINKS

FUSE TYPE TDM/THM/TFM

40A

50A

63A

80A

PEAK CUT-OFF CURRENT IN AMPERE S

10000

1000

6.3A

10A

16A

20A

25A

31.5A

100 100

R.M.S. SYMMETRICAL PROSPECTIVE CURRENT IN AMPERES

1000

10000

100000

DRN DATE APPD

DRN DATE APPD

DRN MPJ DATE 21/3/07 APPD

1st ISSUE MPJ ECN11220

BURTON-ON-THE-WOLDS, LEICS., LE12 5TH, U.K. TEL +44 (0) 1509 882600

PF2276

FAX +44 (0) 1509 882786

Form No. 24kV DIN Page 5 of 11 Data sheet 720106

MEDIUM VOLTAGE DIN Fuse-Links


Cut-Off Curves

24kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps

MV DIN

REF. No. PF 2236

NOTES 1. CURVES SHOW EXTREME MAXIMUM VALUES WHICH WILL NOT BE EXCEEDED UNDER CONDITIONS STATED IN 2 AND 3 BELOW. 2. FOR HIGH VALUES OF PROSPECTIVE CURRENT A SYMMETRICAL FAULT GIVES THE HIGHEST CUT-OFFCURRENT. FOR LOW VALUES OF PROSPECTIVE CURRENT, WHERE THERE IS LITTLE OR NO CURRENT LIMITATION, AN ASYMMETRICAL FAULT PASSES THE HIGHEST PEAKCURRENT. THE CURVES ARE THEREFORE BASED ON THE DEGREE OF ASYMMETRY WHICH GIVES THE MAXIMUM CUT-OFF CURRENT AT ANY PARTICULAR VALUE OF PROSPECTIVE CURRENT. 3. CURVES RELATE TO FREQUENCY OF 50 Hz AND A RECOVERY VOLTAGE EQUAL TO THE FUSE RATED VOLTAGE.
100000

CUT-OFF CURRENT CHARACTERISTIC FOR 24kV FUSE-LINKS

FUSE TYPE TFM TXM

100A

125A

160A

PEAK CUT-OFF CURRENT IN AMPERES

10000

1000

100 100

R.M.S. SYMMETRICAL PROSPECTIVE CURRENT IN AMPERES

1000

10000

100000

DRN DATE APPD

DRN DATE APPD

DRN MPJ DATE 20/4/07 APPD

1st ISSUE MPJ ECN11268

BURTON-ON-THE-WOLDS, LEICS., LE12 5TH, U.K. TEL +44 (0) 1509 882600 FAX +44 (0) 1509 882786

PF2236
Form No. 24kV DIN Page 6 of 11 Data sheet 720106

MEDIUM VOLTAGE DIN Fuse-Links


ASTA Certificate

24kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps

MV DIN

Form No. 24kV DIN Page 7 of 11 Data sheet 720106

MEDIUM VOLTAGE DIN Fuse-Links


KEMA Certificate

24kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps

MV DIN

Form No. 24kV DIN Page 8 of 11 Data sheet 720106

MEDIUM VOLTAGE DIN Fuse-Links


KEMA Certificate

24kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps

MV DIN

Form No. 24kV DIN Page 9 of 11 Data sheet 720106

MEDIUM VOLTAGE DIN Fuse-Links


KEMA Report

24kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps

MV DIN

This report of performance details 24kV DIN rated fuse-links tested in accordance with IEC60282-1:2005 to demonstrate correct operation on a 12kV system
Form No. 24kV DIN Page 10 of 11 Data sheet 720106

MEDIUM VOLTAGE DIN Fuse-Links


KEMA Report

24kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps

MV DIN

This report of performance details 24kV DIN rated fuse-links tested in accordance with IEC60282-1:2005 to demonstrate correct operation on a 25kV system
Form No. 24kV DIN Page 11 of 11 Data sheet 720106

You might also like