Cross Flow MFV Troubleshooting
Cross Flow MFV Troubleshooting
FO Inlet
Drain Port
The only 3 seals on each cartridge valve that prevent cross contamination between fuel oil and control oil
With the MFV fuel oil lines removed, close off the control head return port and apply 500 psi of control oil Once applied, cycle all solenoids on and off to build of back pressure and watch all inlet, outlet, and drain ports for the fuel oil and ensure no leakage is occurring
Pressure and return ports for control oil return port to be closed off when performing back pressure test