Gravity systems

ALCULATION DATA

How many ventilators are required for a particular application?


To determine the quantity of required ventilators we need to ascertain the following: a) Volume: Volume of shed to be ventilated. b) Air changes: Depending on the use of the particular shed to be ventilated choose the number of air changes per hour required. The accompanying table gives guidance to determine number of air changes suitable to your application. c) CFM of ventilator: Refer table given below. RECOMMENDED AIR CHANGES

Type of Building Assembly Hall Auditorium Bakeries Boiler Room

Air Changes Per Hour 6-12 4-12 12-20 15-60

Type of Building Chemical Plant Laundry Paper Mill Textile Mill

Air Changes Per Hour 30-60 12-30 08-30 08-15

Brewery Class Room Engine Room Factories (Light) Factories (Heavy)

8-30 10-15 12-30 10-20 20-40

Packing Room Transformer Room Paint Shop Ware House Foundry

08-30 12-30 20-30 05-08 10-30

VENTILATOR PERFORMANCE DATA

Wind Velocity
Model Mukta 24 Ventilator Size 24 inchs Height 20 Ft 30 Ft 40 Ft
To Determine Number of Ventilators Required:

8Km/Hr Exhaust Capacity 1972 CFM 2076 CFM 2164 CFM

{(Volume of shed X No. Of Air Changes) / 60} / Exhaust Capacity of Ventilator. Volume of Shed = Length X Width X Height Conversions: 1 Ft = 0.3048 Mtrs 1 Mtrs = 3.2808 Ft 1CFT = 0.028317 CUM 1 CUM = 35.315 CFT