996 Total kVAr 2917 Transformer rating in KVA kVAr required for Transformer compensation Rating of Large size Induction motors in HP 2500 125
0 Max Mini kVAr required for Induction motor 0 0 1) It is found economical to use individual compensation for motors having HP rating more than 15HP 2) For Individual compensation of motors any kVAr can be selected between limits of Mini to Max depending upon standard rating of the capacitor available in market If Existing PF is measured on HT side of the transformer then transformer compensation kVAr should be deducted from the Total kVAr
APFC panels: After deducting the kVAr requirement of Large size inductin motors (Individual Compensation) from Total kVAr whatever is left out should be put up as Automatic Power Factor Correction
Not Known
Transformer 2 KW known 3735 Existing PF 0.7 Target PF 0.996 Total kVAr 3475 Transformer rating in KVA kVAr required for Transformer compensation Rating of Large size Induction motors in HP 2500 125
0 Max Mini kVAr required for Induction motor 0 0 1) It is found economical to use individual compensation for motors having HP rating more than 15HP 2) For Individual compensation of motors any kVAr can be selected between limits of Mini to Max depending upon standard rating of the capacitor available in market If Existing PF is measured on HT side of the transformer then transformer compensation kVAr should be deducted from the Total kVAr
APFC panels: After deducting the kVAr requirement of Large size inductin motors (Individual Compensation) from Total kVAr whatever is left out should be put up as Automatic Power Factor Correction