Recommendations Following recommendations are made for the proposed Ground + two floors building based on the Geophysical

resistivity survey and the geotechnical analysis reports provided by the client. Geophysical resistivity survey results are considered for the generalized soil profile of the study area and the geotechnical investigation results are adopted in the foundation recommendation.

1. The generalized soil profile of the area is Bore Hole No: H4 Depth From To 0.00 4.25 4.25 9.75 10.75 12.75 17.50 9.75 10.75 12.75 17.50 18.00 Layer Type of soil thickness 4.25 Silty sand 5.50 1.00 2.00 4.75 0.50 Clay Clayey sand Clay Sand Clay Bore Hole No: S1 Depth Layer To From thickness 0.00 17.0 17.00 0 Type of soil Clay

2. Standard penetration test values

Bore Hole No: H4

Bore Hole No: S1

Depth From To 0.00 4.25 4.25 9.75 10.75 12.75 17.50 9.75 10.75 12.75 17.50 18.00

Average N value 3 8 19 9 27 14

Type of soil Silty sand Clay Clayey sand Clay Sand Clay

Depth Average From N value 11.0 7 0 11.00 14.0 18 0 14.00 15.0 9 0 15.00 17.0 23 0 17.00 19.0 14 0 19.00 22.0 24 To 0.0

Type of soil

Clay

22.00 23.00

0 23.0 0 29.0 0

14 31

3. The type of foundation recommended

Bore hole H4 S1

Load due to Type of Diameter structure/Column foundation


(Given by the client)

Depth 14.00 20.00

No of piles 5 5

200t

Pile

600cm

4. It is recommended to do pile load for each locations (H4 & S1) to confirm the safe

load carrying capacity of the individual pile. Necessary changes shall be made based on the outcome of the pile load test.