My first project using Vijeo Citect 7.0

Goal of this document


To help the Vijeo Citect 7.0 new user to design his first project, starting from scratch To help the Vijeo Citect 7.0 new user to take benefits of the packaged features that are Unity SpeedLink and OFS

Automation Business Unit SCADA Department Patrick Bourges - October 2007

Vijeo Citect 7.0: features


Vijeo Citect 7.0 proposes a new native tool to directly populate the Vijeo Citect 7.0 tags database from the variables of a Unity application This tool is the Unity SpeedLink Static The preferred communication link between Vijeo Citect 7.0 and the Unity PLC is OFS 3.31 that comes with Vijeo Citect 7.0 Of course, advanced users can still define other communication architectures according to their needs Vijeo Citect 7.0 now manages clusters, and a cluster must be defined even for a stand alone system

Automation Business Unit SCADA Department Patrick Bourges - October 2007

Steps described in this document


Vijeo Citect 7.0 installation Creation of a new project, and PC configuration in order to run it; an I/O device, and its tags definition from the PLC variables Definition of Alarms and Trends Pages Users Introduction to Genies Device

Automation Business Unit SCADA Department Patrick Bourges - October 2007

Tools used
Vijeo Citect 7.0 OFS 3.31, that comes with Vijeo Citect 7.0 Unity 3.0 The Unity Pro 3.0 Demo application for the M340 PLC

Automation Business Unit SCADA Department Patrick Bourges - October 2007

Vijeo Citect 7.0: before the installation


If you already have OFS installed and registered on the PC, first uninstall it In Windows, Start Settings Control Panel

Select Add/Remove Programs Uninstall OPC Factory Server Uninstall OFS Configuration Tool

Automation Business Unit SCADA Department Patrick Bourges - October 2007

Vijeo Citect 7.0: before the installation


Uninstall Vijeo Citect 6.1 Uninstall all the companion tools you installed with Vijeo Citect 6.1
Web Server Knowledge base

Automation Business Unit SCADA Department Patrick Bourges - October 2007

Vijeo Citect 7.0: installation


Run the SETUP

Automation Business Unit SCADA Department Patrick Bourges - October 2007

Vijeo Citect 7.0: installation


Take time to read the documentation, then <Next>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

Vijeo Citect 7.0: installation


Accept the license agreement, then <Next>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

10

Vijeo Citect 7.0: installation


Select <Server> environment, then <Next>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

11

Vijeo Citect 7.0: installation


Unselect <Web Server> feature if Internet Information Services is not installed on the PC, then <Next>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

12

Vijeo Citect 7.0: installation


Select the installation folders, then <Next>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

13

Vijeo Citect 7.0: installation


Select the options folder, then <Next>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

14

Vijeo Citect 7.0: installation


Click <Install> to start the installation

Automation Business Unit SCADA Department Patrick Bourges - October 2007

15

Vijeo Citect 7.0: installation


If Dot Net 2.0 is missing, the installer will install it

Automation Business Unit SCADA Department Patrick Bourges - October 2007

16

Vijeo Citect 7.0: installation


After the completion of the installation, click <Finish>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

17

Vijeo Citect 7.0: Project Explorer


Start the Vijeo Citect Explorer

Automation Business Unit SCADA Department Patrick Bourges - October 2007

18

Vijeo Citect 7.0: Project Explorer


Right click on <My Projects> <New Project>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

19

Vijeo Citect 7.0: Project Explorer


Give your <XP_Style> project name and description

Automation Business Unit SCADA Department Patrick Bourges - October 2007

20

Vijeo Citect 7.0: Project Explorer


Switch to the Project Editor tool

Automation Business Unit SCADA Department Patrick Bourges - October 2007

21

Vijeo Citect 7.0: Cluster definition


A cluster is a discrete group of alarms servers, trends servers, reports servers, and I/O servers It would usually also possess local Vijeo Citect display clients For a plant comprising several individual sections or systems, multiple clusters can be used, one cluster for each section

Automation Business Unit SCADA Department Patrick Bourges - October 2007

22

Vijeo Citect 7.0: Cluster definition


From the <Servers> menu, select <Clusters>, even for a Stand Alone architecture

Automation Business Unit SCADA Department Patrick Bourges - October 2007

23

Vijeo Citect 7.0: Cluster definition


Give the cluster a name and a comment, then <Add>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

24

Vijeo Citect 7.0: Network Addresses definition


From the <Servers> menu, select <Network Addresses>, enter the IP address of the PC, then <Add>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

25

Vijeo Citect 7.0: IOServer definition


From the <Servers> menu, select <I/O Servers>, select the cluster, enter a name, select the network address, then <Add>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

26

Vijeo Citect 7.0: Alarm Server definition


From the <Servers> menu, select <Alarm Servers>, select the cluster, enter a name, select the network address, then <Add>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

27

Vijeo Citect 7.0: Trend Server definition


From the <Servers> menu, select <Trend Servers>, select the cluster, enter a name, select the network address, then <Add>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

28

Vijeo Citect 7.0: from Unity variables to tags


For each PLC application variable, Unity proposes a <Custom> field you can use to store any comment Vijeo Citect 7.0 SpeedLink uses this Unity <Custom> to filter the PLC variables intended to be tags in the SCADA project Let <Custom> blank for no tag from this variable, or set it to VJC to create a tag, to VJA to create an Alarm, to VJT to create a Trend

Automation Business Unit SCADA Department Patrick Bourges - October 2007

29

Vijeo Citect 7.0: from Unity variables to tags


This is what can be defined

Automation Business Unit SCADA Department Patrick Bourges - October 2007

30

Unity 3.0: exporting data from the PLC project


Right click on <Variables & FB instances> export

Automation Business Unit SCADA Department Patrick Bourges - October 2007

31

Unity 3.0: exporting using XSY format

Automation Business Unit SCADA Department Patrick Bourges - October 2007

32

Unity 3.0: set autosaving Unity files options

Automation Business Unit SCADA Department Patrick Bourges - October 2007

33

OFS 3.31 configuration tool: define M340 alias

Select the XVM file as symbols file

Automation Business Unit SCADA Department Patrick Bourges - October 2007

34

OFS 3.31 configuration tool: define network and address for the Unity Simulator

Automation Business Unit SCADA Department Patrick Bourges - October 2007

35

OFS 3.31 testing client: check the alias before using it in the SCADA

Automation Business Unit SCADA Department Patrick Bourges - October 2007

36

Vijeo Citect 7.0: creating an I/O Device


Use the Express I/O Device Setup wizard

Automation Business Unit SCADA Department Patrick Bourges - October 2007

37

Vijeo Citect 7.0: creating an I/O Device


This wizard will configure the I/O device

Automation Business Unit SCADA Department Patrick Bourges - October 2007

38

Vijeo Citect 7.0: creating an I/O Device


Use the already defined I/O Server

Automation Business Unit SCADA Department Patrick Bourges - October 2007

39

Vijeo Citect 7.0: creating an I/O Device


Create a new I/O Device

Automation Business Unit SCADA Department Patrick Bourges - October 2007

40

Vijeo Citect 7.0: creating an I/O Device


Select a new External I/O Device

Automation Business Unit SCADA Department Patrick Bourges - October 2007

41

Vijeo Citect 7.0: creating an I/O Device


Select OPC as the driver communication model

Automation Business Unit SCADA Department Patrick Bourges - October 2007

42

Vijeo Citect 7.0: creating an I/O Device


Click <Next> to accept OFS as OPC server

Automation Business Unit SCADA Department Patrick Bourges - October 2007

43

Vijeo Citect 7.0: creating an I/O Device


Do not link the I/O Device

Automation Business Unit SCADA Department Patrick Bourges - October 2007

44

Vijeo Citect 7.0: creating an I/O Device


Click on <Finish> to commit the configuration

Automation Business Unit SCADA Department Patrick Bourges - October 2007

45

Vijeo Citect 7.0: communication model


1 3

Set this parameter to 1000 for a 1000 ms OFS group rate

Automation Business Unit SCADA Department Patrick Bourges - October 2007

46

Vijeo Citect 7.0: importing tags


From Projects Explorer, select Tools Import Tags

Automation Business Unit SCADA Department Patrick Bourges - October 2007

47

Vijeo Citect 7.0: importing tags


Define the parameters as below, click <Import> Reminder: Unity Pro XSY export format is available from any Unity Pro 3.0 grade but STU link is only available From Unity Pro 3.0 XL!
Automation Business Unit SCADA Department Patrick Bourges - October 2007

Add ExCustom=?*;

48

Vijeo Citect 7.0: configuring the computer


From <Tools>, run the <Computer Setup Editor>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

49

Vijeo Citect 7.0: adding OPC parameters


Add OPC, UseOPC2, value 1 Add OPCAccessPaths, <IOServer> <IODevice> = <OFS Alias> File Save to save your changes
Automation Business Unit SCADA Department Patrick Bourges - October 2007 50

Vijeo Citect 7.0: creating the first page


Switch to Graphics Builder

Automation Business Unit SCADA Department Patrick Bourges - October 2007

51

Vijeo Citect 7.0: creating the first page


Switch to Graphics Builder, add a new page

Automation Business Unit SCADA Department Patrick Bourges - October 2007

52

Vijeo Citect 7.0: creating the first page


Select a <normal> template using the <XP_Style>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

53

Vijeo Citect 7.0: adding the first graphic object


Add a rectangle, select <Filled> appearance option

Automation Business Unit SCADA Department Patrick Bourges - October 2007

54

Vijeo Citect 7.0: adding the first animation


In the <Fill> tab, select <On/Off> type, and browse the tags

Automation Business Unit SCADA Department Patrick Bourges - October 2007

55

Vijeo Citect 7.0: saving the page


Close and save the page

Automation Business Unit SCADA Department Patrick Bourges - October 2007

56

Vijeo Citect 7.0: compiling the project


Compile the project before choosing it as the project to run

Automation Business Unit SCADA Department Patrick Bourges - October 2007

57

Vijeo Citect 7.0: defining a role for the computer


Run the <Computer Setup Wizard>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

58

Vijeo Citect 7.0: choosing <Setup> and project


Run the <Computer Setup Wizard>, select <Express Setup>, select the project to run

Automation Business Unit SCADA Department Patrick Bourges - October 2007

59

Vijeo Citect 7.0: network setup


Select <Server and Display Client>, then <No networking>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

60

Vijeo Citect 7.0: committing setup


Select <Finish>, the PC is ready to run the project!

Automation Business Unit SCADA Department Patrick Bourges - October 2007

61

Vijeo Citect 7.0: running the project


Right click on <Project>, select <Run>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

62

Vijeo Citect 7.0: DEMO mode


With no license key, the system will prompt

Click <OK> to run the project in DEMO mode during 15 minutes

Automation Business Unit SCADA Department Patrick Bourges - October 2007

63

Vijeo Citect 7.0: OFS debug window


OPC group for Vijeo Citect OPC client

Group rate as defined in the Board

Automation Business Unit SCADA Department Patrick Bourges - October 2007

64

Vijeo Citect 7.0: what is automatically created


From the Unity variables, the <Import> feature creates tags

Automation Business Unit SCADA Department Patrick Bourges - October 2007

65

Vijeo Citect 7.0: what is automatically created


From the variables stamped VJA or VJT, the <Import> feature creates Digital Alarms and Trends

Automation Business Unit SCADA Department Patrick Bourges - October 2007

66

Vijeo Citect 7.0: completing trend definition


From the project Editor, click on Main Menu Tags Trend Tags Press <F2> to display the lower half of the form, then complete the trend as shown

1 second sampling periodic sampling 2 external files filled in 24 hours (circular buffers)

Automation Business Unit SCADA Department Patrick Bourges - October 2007

67

Vijeo Citect 7.0: check DATA folder


Run the project, then list the files located in DATA folder

Automation Business Unit SCADA Department Patrick Bourges - October 2007

68

Vijeo Citect 7.0: display trend page


Open the <Single Trend> page and right click on the first pen to select it

Automation Business Unit SCADA Department Patrick Bourges - October 2007

69

Vijeo Citect 7.0: select a pen


Select the trend for this pen

Automation Business Unit SCADA Department Patrick Bourges - October 2007

70

Vijeo Citect 7.0: changing the scale


Select the trend for this pen

Click there to set 100% scale value

Automation Business Unit SCADA Department Patrick Bourges - October 2007

71

Vijeo Citect 7.0: creating a user


From the project editor, select Main Menu System Users

Automation Business Unit SCADA Department Patrick Bourges - October 2007

72

Vijeo Citect 7.0: creating a user


From the project editor, select Main Menu System Users Define a <kernel> with a password and all the 8 distinct privileges The < kernel > user can browse the project with no restriction

Automation Business Unit SCADA Department Patrick Bourges - October 2007

73

Vijeo Citect 7.0: Administrator logon


Run the project Log on the SCADA system using <kernel> account Once the user is logged, his name is displayed

Automation Business Unit SCADA Department Patrick Bourges - October 2007

74

Vijeo Citect 7.0: Administrator logon


Once the user with privileges is logged, a right click on an alarm line displays the Alarm menu, from which you can Acknowledge them

Automation Business Unit SCADA Department Patrick Bourges - October 2007

75

Vijeo Citect 7.0: creating a genie


A Genie is a combination of several objects grouped and saved as a single object to be reused from a library You can define a Genie when you plan to use a lot of times the same group of object A variable can be directly assigned to an animation in a Genie A Genie also accepts string substitution to be substituted when an instance of the Genie is created

Automation Business Unit SCADA Department Patrick Bourges - October 2007

76

Vijeo Citect 7.0: creating a genie


From the Graphics Builder, select <NEW> then <Genie>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

77

Vijeo Citect 7.0: creating a genie


Paste a symbol, select a tank from a <Tanks> library, then draw a rectangle inside the tank

Automation Business Unit SCADA Department Patrick Bourges - October 2007

78

Vijeo Citect 7.0: creating a genie


Set <Filled> appearance option for the rectangle

Automation Business Unit SCADA Department Patrick Bourges - October 2007

79

Vijeo Citect 7.0: creating a genie


Select a tag to fill the level

Automation Business Unit SCADA Department Patrick Bourges - October 2007

80

Vijeo Citect 7.0: creating a genie


Replace M340_Material_A by %PLC%_%PROCESS%

Automation Business Unit SCADA Department Patrick Bourges - October 2007

81

Vijeo Citect 7.0: creating a library


Close and save the Genie You are prompted to create a new library

Automation Business Unit SCADA Department Patrick Bourges - October 2007

82

Vijeo Citect 7.0: saving the Genie


Create the new library then save the Genie

Automation Business Unit SCADA Department Patrick Bourges - October 2007

83

Vijeo Citect 7.0: creating instances of the Genie


Open the page previously created and select the genie from the library

Automation Business Unit SCADA Department Patrick Bourges - October 2007

84

Vijeo Citect 7.0: creating instances of the Genie


You are prompted to substitute %PLC% and %PROCESS% in order to assign a valid tag name used for the animation!

Automation Business Unit SCADA Department Patrick Bourges - October 2007

85

Vijeo Citect 7.0: creating instances of the Genie


Copy and paste a second instance of the genie, then assign %PLC% and %PROCESS% in order to bind a second valid tag

When you assign strings for substitution, the resulting tag is immediately checked!

Automation Business Unit SCADA Department Patrick Bourges - October 2007

86

Vijeo Citect 7.0: devices


Mouse or keyboard input can trigger a message to be sent to a log device via the MsgLog field The log device must also be defined with MsgLog as one of the format fields

Automation Business Unit SCADA Department Patrick Bourges - October 2007

87

Vijeo Citect 7.0: devices


From the Project Editor, open the Devices Editor

Automation Business Unit SCADA Department Patrick Bourges - October 2007

88

Vijeo Citect 7.0: devices


Device an ASCII device as shown below

Format: {Date,10,R} {Time,8,R},{MsgLog,32},{Arg1,6,R},{UserName,16},{Page,16}


Automation Business Unit SCADA Department Patrick Bourges - October 2007 89

Vijeo Citect 7.0: command from graphics


Open the previous page and add a <Number>

Automation Business Unit SCADA Department Patrick Bourges - October 2007

90

Vijeo Citect 7.0: command from graphics


Define an <Input> key sequence for the <Enter> command and a Log message

Automation Business Unit SCADA Department Patrick Bourges - October 2007

91

Vijeo Citect 7.0: tool tip text and Log Device


In the <Access> tab, enter a tool tip text and select the Log Device

Automation Business Unit SCADA Department Patrick Bourges - October 2007

92

Vijeo Citect 7.0: command from graphics


Run the project, log on using <kernel> account, then set the value

Automation Business Unit SCADA Department Patrick Bourges - October 2007

93

Vijeo Citect 7.0: Log file


From DATA folder, open the CommandLog.TXT file

Automation Business Unit SCADA Department Patrick Bourges - October 2007

94