You are on page 1of 12

UCHC MARB

Farmington,CT 06030
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: N/A VFD O.L. Config: 1050s/100% Bypass O.L. Config: VFD U.V. Config: System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 18c 30.4c X X X X VFD Freq Limits: 12 TO 58 Hz www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 136.4a

RTU-1-SF
ABB ACH550UH125A4 None 202C Hex 0

3/23/13
Roof 2043001250 None 71.95kh 0

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 483 340 40 58 Vac Vac Amps Amps C-A: C-A: C: C: 479 340 40 58 5.2 Vac Vac Amps Amps Vac

/ Data X N/A N/A X X X X X 44.3 HZ

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 481 340 40 58 Vac Vac Amps Amps 662 641.3 B-C: B-C: B: B: Vdc

Display 176 Vac Display 60 Amps 634 0 670 N/A N/A N/A N/A N/A Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 661 10 23 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 17 48 9 Vac mVac mVac

Replaced bad keypad(backlight was burned out, handed old one into operations) 3-23-13 DML

While removing the control panel to gain access for servicing I noted a brittle control brd ribbon cable(used to connect VFD to con

UCHC MARB
Farmington,CT 06030
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: N/A VFD O.L. Config: 1050s/100% Bypass O.L. Config: VFD U.V. Config: System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 18c 30.4c X X X X VFD Freq Limits: 12 TO 58 Hz www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 136.4a

RTU-1-SF
ABB ACH550UH125A4 None 202C Hex 0

3/23/13
Roof 2043001250 None 71.95kh 0

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 483 340 40 58 Vac Vac Amps Amps C-A: C-A: C: C: 479 340 40 58 5.2 Vac Vac Amps Amps Vac

/ Data X N/A N/A X X X X X 44.3 HZ

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 481 340 40 58 Vac Vac Amps Amps 662 641.3 B-C: B-C: B: B: Vdc

Display 176 Vac Display 60 Amps 634 0 670 N/A N/A N/A N/A N/A Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 661 10 23 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 17 48 9 Vac mVac mVac

Replaced bad keypad(backlight was burned out, handed old one into operations) 3-23-13 DML

While removing the control panel to gain access for servicing I noted a brittle control brd ribbon cable(used to connect VFD to con

UCHC MARB
Farmington,CT 06030
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: N/A VFD O.L. Config: 1050s/100% Bypass O.L. Config: VFD U.V. Config: System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 18c 30.4c X X X X VFD Freq Limits: 12 TO 58 Hz www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 136.4a

RTU-1-SF
ABB ACH550UH125A4 None 202C Hex 0

3/23/13
Roof 2043001250 None 71.95kh 0

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 483 340 40 58 Vac Vac Amps Amps C-A: C-A: C: C: 479 340 40 58 5.2 Vac Vac Amps Amps Vac

/ Data X N/A N/A X X X X X 44.3 HZ

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 481 340 40 58 Vac Vac Amps Amps 662 641.3 B-C: B-C: B: B: Vdc

Display 176 Vac Display 60 Amps 634 0 670 N/A N/A N/A N/A N/A Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 661 10 23 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 17 48 9 Vac mVac mVac

Replaced bad keypad(backlight was burned out, handed old one into operations) 3-23-13 DML

While removing the control panel to gain access for servicing I noted a brittle control brd ribbon cable(used to connect VFD to con

UCHC MARB
Farmington,CT 06030
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: N/A VFD O.L. Config: 1050s/100% Bypass O.L. Config: VFD U.V. Config: System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 18c 30.4c X X X X VFD Freq Limits: 12 TO 58 Hz www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 136.4a

RTU-1-SF
ABB ACH550UH125A4 None 202C Hex 0

3/23/13
Roof 2043001250 None 71.95kh 0

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 483 340 40 58 Vac Vac Amps Amps C-A: C-A: C: C: 479 340 40 58 5.2 Vac Vac Amps Amps Vac

/ Data X N/A N/A X X X X X 44.3 HZ

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 481 340 40 58 Vac Vac Amps Amps 662 641.3 B-C: B-C: B: B: Vdc

Display 176 Vac Display 60 Amps 634 0 670 N/A N/A N/A N/A N/A Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 661 10 23 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 17 48 9 Vac mVac mVac

Replaced bad keypad(backlight was burned out, handed old one into operations) 3-23-13 DML

While removing the control panel to gain access for servicing I noted a brittle control brd ribbon cable(used to connect VFD to con

UCHC MARB
Farmington,CT 06030
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: N/A VFD O.L. Config: 1050s/100% Bypass O.L. Config: VFD U.V. Config: System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 18c 30.4c X X X X VFD Freq Limits: 12 TO 58 Hz www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 136.4a

RTU-1-SF
ABB ACH550UH125A4 None 202C Hex 0

3/23/13
Roof 2043001250 None 71.95kh 0

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 483 340 40 58 Vac Vac Amps Amps C-A: C-A: C: C: 479 340 40 58 5.2 Vac Vac Amps Amps Vac

/ Data X N/A N/A X X X X X 44.3 HZ

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 481 340 40 58 Vac Vac Amps Amps 662 641.3 B-C: B-C: B: B: Vdc

Display 176 Vac Display 60 Amps 634 0 670 N/A N/A N/A N/A N/A Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 661 10 23 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 17 48 9 Vac mVac mVac

Replaced bad keypad(backlight was burned out, handed old one into operations) 3-23-13 DML

While removing the control panel to gain access for servicing I noted a brittle control brd ribbon cable(used to connect VFD to con

UCHC MARB
Farmington,CT 06030
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: N/A VFD O.L. Config: 1050s/100% Bypass O.L. Config: VFD U.V. Config: System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 18c 30.4c X X X X VFD Freq Limits: 12 TO 58 Hz www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 136.4a

RTU-1-SF
ABB ACH550UH125A4 None 202C Hex 0

3/23/13
Roof 2043001250 None 71.95kh 0

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 483 340 40 58 Vac Vac Amps Amps C-A: C-A: C: C: 479 340 40 58 5.2 Vac Vac Amps Amps Vac

/ Data X N/A N/A X X X X X 44.3 HZ

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 481 340 40 58 Vac Vac Amps Amps 662 641.3 B-C: B-C: B: B: Vdc

Display 176 Vac Display 60 Amps 634 0 670 N/A N/A N/A N/A N/A Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 661 10 23 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 17 48 9 Vac mVac mVac

Replaced bad keypad(backlight was burned out, handed old one into operations) 3-23-13 DML

While removing the control panel to gain access for servicing I noted a brittle control brd ribbon cable(used to connect VFD to con

UCHC MARB
Farmington,CT 06030
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: N/A VFD O.L. Config: 1050s/100% Bypass O.L. Config: VFD U.V. Config: System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 18c 30.4c X X X X VFD Freq Limits: 12 TO 58 Hz www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 136.4a

RTU-1-SF
ABB ACH550UH125A4 None 202C Hex 0

3/23/13
Roof 2043001250 None 71.95kh 0

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 483 340 40 58 Vac Vac Amps Amps C-A: C-A: C: C: 479 340 40 58 5.2 Vac Vac Amps Amps Vac

/ Data X N/A N/A X X X X X 44.3 HZ

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 481 340 40 58 Vac Vac Amps Amps 662 641.3 B-C: B-C: B: B: Vdc

Display 176 Vac Display 60 Amps 634 0 670 N/A N/A N/A N/A N/A Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 661 10 23 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 17 48 9 Vac mVac mVac

Replaced bad keypad(backlight was burned out, handed old one into operations) 3-23-13 DML

While removing the control panel to gain access for servicing I noted a brittle control brd ribbon cable(used to connect VFD to con

UCHC MARB
Farmington,CT 06030
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: N/A VFD O.L. Config: 1050s/100% Bypass O.L. Config: VFD U.V. Config: System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 18c 30.4c X X X X VFD Freq Limits: 12 TO 58 Hz www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 136.4a

RTU-1-SF
ABB ACH550UH125A4 None 202C Hex 0

3/23/13
Roof 2043001250 None 71.95kh 0

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 483 340 40 58 Vac Vac Amps Amps C-A: C-A: C: C: 479 340 40 58 5.2 Vac Vac Amps Amps Vac

/ Data X N/A N/A X X X X X 44.3 HZ

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 481 340 40 58 Vac Vac Amps Amps 662 641.3 B-C: B-C: B: B: Vdc

Display 176 Vac Display 60 Amps 634 0 670 N/A N/A N/A N/A N/A Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 661 10 23 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 17 48 9 Vac mVac mVac

Replaced bad keypad(backlight was burned out, handed old one into operations) 3-23-13 DML

While removing the control panel to gain access for servicing I noted a brittle control brd ribbon cable(used to connect VFD to con

UCHC MARB
Farmington,CT 06030
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: N/A VFD O.L. Config: 1050s/100% Bypass O.L. Config: VFD U.V. Config: System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 18c 30.4c X X X X VFD Freq Limits: 12 TO 58 Hz www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 136.4a

RTU-1-SF
ABB ACH550UH125A4 None 202C Hex 0

3/23/13
Roof 2043001250 None 71.95kh 0

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 483 340 40 58 Vac Vac Amps Amps C-A: C-A: C: C: 479 340 40 58 5.2 Vac Vac Amps Amps Vac

/ Data X N/A N/A X X X X X 44.3 HZ

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 481 340 40 58 Vac Vac Amps Amps 662 641.3 B-C: B-C: B: B: Vdc

Display 176 Vac Display 60 Amps 634 0 670 N/A N/A N/A N/A N/A Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 661 10 23 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 17 48 9 Vac mVac mVac

Replaced bad keypad(backlight was burned out, handed old one into operations) 3-23-13 DML

While removing the control panel to gain access for servicing I noted a brittle control brd ribbon cable(used to connect VFD to con

UCHC MARB
Farmington,CT 06030
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: N/A VFD O.L. Config: 1050s/100% Bypass O.L. Config: VFD U.V. Config: System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 18c 30.4c X X X X VFD Freq Limits: 12 TO 58 Hz www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 136.4a

RTU-1-SF
ABB ACH550UH125A4 None 202C Hex 0

3/23/13
Roof 2043001250 None 71.95kh 0

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 483 340 40 58 Vac Vac Amps Amps C-A: C-A: C: C: 479 340 40 58 5.2 Vac Vac Amps Amps Vac

/ Data X N/A N/A X X X X X 44.3 HZ

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 481 340 40 58 Vac Vac Amps Amps 662 641.3 B-C: B-C: B: B: Vdc

Display 176 Vac Display 60 Amps 634 0 670 N/A N/A N/A N/A N/A Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 661 10 23 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 17 48 9 Vac mVac mVac

Replaced bad keypad(backlight was burned out, handed old one into operations) 3-23-13 DML

While removing the control panel to gain access for servicing I noted a brittle control brd ribbon cable(used to connect VFD to con

UCHC MARB
Farmington,CT 06030
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: N/A VFD O.L. Config: 1050s/100% Bypass O.L. Config: VFD U.V. Config: System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 18c 30.4c X X X X VFD Freq Limits: 12 TO 58 Hz www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 136.4a

RTU-1-SF
ABB ACH550UH125A4 None 202C Hex 0

3/23/13
Roof 2043001250 None 71.95kh 0

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 483 340 40 58 Vac Vac Amps Amps C-A: C-A: C: C: 479 340 40 58 5.2 Vac Vac Amps Amps Vac

/ Data X N/A N/A X X X X X 44.3 HZ

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 481 340 40 58 Vac Vac Amps Amps 662 641.3 B-C: B-C: B: B: Vdc

Display 176 Vac Display 60 Amps 634 0 670 N/A N/A N/A N/A N/A Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 661 10 23 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 17 48 9 Vac mVac mVac

Replaced bad keypad(backlight was burned out, handed old one into operations) 3-23-13 DML

While removing the control panel to gain access for servicing I noted a brittle control brd ribbon cable(used to connect VFD to con

UCHC MARB
Farmington,CT 06030
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: N/A VFD O.L. Config: 1050s/100% Bypass O.L. Config: VFD U.V. Config: System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 18c 30.4c X X X X VFD Freq Limits: 12 TO 58 Hz www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 136.4a

RTU-1-SF
ABB ACH550UH125A4 None 202C Hex 0

3/23/13
Roof 2043001250 None 71.95kh 0

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 483 340 40 58 Vac Vac Amps Amps C-A: C-A: C: C: 479 340 40 58 5.2 Vac Vac Amps Amps Vac

/ Data X N/A N/A X X X X X 44.3 HZ

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 481 340 40 58 Vac Vac Amps Amps 662 641.3 B-C: B-C: B: B: Vdc

Display 176 Vac Display 60 Amps 634 0 670 N/A N/A N/A N/A N/A Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 661 10 23 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 17 48 9 Vac mVac mVac

Replaced bad keypad(backlight was burned out, handed old one into operations) 3-23-13 DML

While removing the control panel to gain access for servicing I noted a brittle control brd ribbon cable(used to connect VFD to con