Power Quality
Contents General The risks of high inrush current Single capacitor connection, inrush current calculation Parallel capacitor connection, inrush current calculation Various solutions for limiting inrush current serial aircoils Detuning reactors, connection cable selection Capacitor contactors with damping resistors Functionality / comparison Comparison Capacitor bank switching under various conditions 3 4 6 7 7 8 9 10 11
EPCOS AG
1 xc = 2**f*c
Eq1: Switching operation: f xc 0 200 * Ir
M 3~
12.5 kVAr
KLK1709-W
25 kVAr
25 kVAr
25 kVAr
25 kVAr
25 kVAr
25 kVAr
187,5 kVAr
High inrush current for grid, high balancing currents for capacitors
LV-PFC capacitor bank Inrush current (pulse) is a factor of: a Remaining capacitor voltage due to fast switching in automatic capacitor banks a Shortcircuit power of supply transformer a Output of capacitor switched in parallel to others already energized a Fault level of supply network a Output of capacitors already energized a Ohmic resistance of capacitor itself and distribution switch gear, connection cables or conductors
25 kVAr
EPCOS AG
73.8
74.5
75.1
75.7
76.3
77.0
77.6 t (ms)
The risks of high inrush current Connecting LV-PFC capacitors without damping to an AC grid stresses the capacitor like a shortcircuit. To avoid negative effects and to improve a capacitors life time, adequate damping of inrush current is highly recommended. Influence of high inrush current and resulting distortion: a High stress on the capacitor reduced lifetime a Welding or fast wearing out of the main contacts of contactors a Negative effects on power quality (eg. voltage transients) a Overvoltage: insulation problems defects of electronic equipment production stop a Undervoltage/voltage zero crossing measurement failure problems with numerical control equipment production stop due to computer failure a High cost of maintenance and production standstill 4
EPCOS AG
10
20
30
40
50
100 t (ms) High peak voltage (transients) occurrence > UINS risk of shortcircuit 0 V results in wrong measurements causing control failures
60
70
80
90
Switching of power factor correction (PFC) capacitors is not only related to high currents but also to high voltage transients (ref. capacitor switching-on steps 1 6), causing degradation of power quality, if the negative influence is not prevented by damping. Capacitor sample, contact surface damaged by high inrush currents High inrush current occurrences due to insufficient damping caused high electromechanical forces within the capacitor. Especially the contact area between electrodes (windings) and the metal-spray layer was extremely stressed by high current forces. The example shows that a fraction of metal-spray layer separated from the windings. Even the MKK capacitor with excellent pulse current capability and enhanced contactability due to wavy cut and heavy edge design of the film shows that extensive power can cause failures.
EPCOS AG
UN
L1 L2 L3
KLK1706-7
Eq 2
Calculation example
Terms Peak inrush current Transformer shortcircuit power Rated capacitor output Rated capacitor current Rated voltage Ohmic resistance = 3 * UN2* (1/Q1 + 1/Q2) Grid impedance = o * L () including contactor fuse busbars ^ i Sk Q IN UN XC XI A kVA kVAr A V ^ i= Given parameters: Grid connection of a single 50 kVAr capacitor, no other capacitor connected: a Grid 400 V/50 Hz a Transformer shortcircuit voltage: 5% a Transformer output: 1600 kVA a Capacitor Q = 50 kVAr; IN = 72 A 2* 1600 kVA 0.05 = 2575 A *72 A 50 kVAr
Result
Typical inrush currents are 1040 times the rated current for single capacitors during connection.
Grid
EPCOS AG
Various Solutions
for Limiting Inrush Current
Parallel connecting of capacitor:
UN
L1 L2 L3
^ i= 2*UN
Grid
Contactor C2 C3 C2 C3 Capacitor C1 Q1 C1 Q2
^ i= 2*UN
Kn
K2
Xc*XL
Eq 3
Xc*(XL1+ XL2)
Qn
Ln
L2
L1
KLK1707-F
Q2
Q1
KLK1708-N
Eq 4
Given parameters: Connection of a 50 kVAr capacitor, other 300 kVAr capacitors are already connected: a Grid 400 V/50 Hz a Transformer shortcircuit voltage: 6% a Transformer output: 630 kVAr a Q1 = 50 kVAr a Q2 = 300 kVAr a IN = 72 A ; VN = 400 V ; f = 50 Hz 1 1 a XC = 3 * U2N * ( Q + Q ) = 11.2 2 1 a L /phase = 0.4 H (empirical) a XL = o * L = 2 * * f * L = 0.125 m ^ i= 2*400 V = 15118.6 A 1 1.2 *0.125*103
Given parameters: Parallel connection of a 50 kVAr capacitor with cable turns (serial aircoils) for damping, other 300 kVAr capacitors are already connected, 400 V/50 Hz, shortcircuit power 10.5 MVA, rated capacitor current 72 A: damping with approx. 6 H with turns. a Xc = 11.2 a XL1 = 2 * * f * L = 2 * * 50 * 6 H = 1.88 m a XL2 = 2 * * f * L = 0.125 m a XL total = 0.125 + 1.88 = 2 m a L /phase = 0.4 H (empirical value) 1) ^ i= 2*400 V = 3780 A 1 1.2 *2 *103
The inrush current is approximately 50 times the rated current. This means only about a quarter compared to a capacitor without damping (turns). This example shows that some cable turns in series with the capacitor contribute to reducing inrush current (to 50 times rated current). This improves capacitor life cycle.
Typical inrush currents are 100250 times rated current for single capacitors in parallel connection to other capacitors in operation.
This example shows that cable turns in series between contactor and capacitor reduce the inrush current. Contactor suppliers recommend inductivity of 6 8 H for damping inrush current. To achieve this inductivity, the following table provides tips for selecting the required turns, diameters and cross sections.
Grid
EPCOS AG
This table should help to find the appropriate cable and required turns. Our PFC-CDROM (available upon request) contains calculation software which enhances precise calculation of the application (capacitors and switch gear).
Detuning reactors (series anti-harmonic reactors) In detuned capacitor banks the inductivity of filter circuit reactors provides an excellent damping effect for limiting inrush current. The following diagrams show the connection of a detuned and non-detuned (reactor and capacitor) system. The peak current of a conventional capacitor is higher than 4000 A. The peak current of detuned capacitors is only approx. 500 A. The purpose of filter circuit reactors is of course not the damping of inrush current, but this example shows that in the case of detuned capacitors no additional damping measures are required.
= 190 * IN
= 24 * IN
Fig. 1: 25 kVAr (21 A /690 V) vertical: 2000 A /div horizontal: 0.625 ms /div
Because of the high inductance in the circuit, the breaking quality of the contactor is important to avoid restriking during switch-off. Especially large contactors (oversized motor contactors) may be too slow and are therefore critical.
EPCOS AG
How does it work? The series damping resistors are switched by socalled precontacts or auxiliary contacts. The precontact closes before main contacts and preloads the capacitor. a Reduced voltage differences. a The peak current is limited. a The resistor is temporarily in the circuit and has no thermal losses. a The total resistance of the resistor wires is mainly ohmic in nature, its inductance can be neglected. The coiling up of the damping resistors is only a matter of construction. a During operation (main contacts are closed) the resistor wires are disconnected or shorted out, and do not cause any permanent losses at all. Due to the very short operation time (a few milliseconds only) during switch-on of the contactor, a long life cycle of the damping resistors is ensured.
Grid/ Mains
Auxiliary switched contact with serial resistor (precontacts) Capacitor contactor (main contacts)
Capacitor
on 2...10 ms
Note: Due to pre-loading via aux. contacts the capacitors voltage difference will be reduced. Consequently also the capacitor current according to the formula: Eq 5
d ^ i = C* V dt
EPCOS AG
Comparison
The following two diagrams show the difference between a capacitors inrush current without and with damping series resistors when a capacitor is switched in parallel to an already energized capacitor bank/unit: Without damping resistors
i = 1200 A
i = 260 A
Fig. 3: 12.5 kVAr (18 A /400 V) vertical: 250 A /div horizontal: 0.5 ms /div
Fig. 4: 12.5 kVAr (18 A /400 V) vertical: 250 A /div horizontal: 0.5 ms /div
Facts and conclusion a Rated current of a 12.5 kVar/400 V capacitor is 18 A a Peak inrush current without series resistors is 1200 A a Peak inrush current with series resistors is only 260 A a 1200 A is equal to 66 times the rated current a Inrush current with series resistors is only one fifth of that of the standard contactor a Substantial difference also in terms of power (integrated area) a Superior switching behavior of contactor with series resistors compared with a standard contactor, results in extended life cycle of contactors as well as of capacitors a Improved power quality ensures trouble-free and safe operation of the PFC system and application
10
EPCOS AG
Comparison
Capacitor bank switching under various conditions
Without precontacts (non-detuned capacitor) Without precontacts (detuned capacitor) With precontacts (detuned capacitor)
i > 4000 A
i = 500 A
i < 200 A
Fig. 5: 25 kVAr (21A /690 V) vertical: 2000 A /div horizontal: 0.625 ms /div
Facts and conclusion The peak current during switching without using precontacts (Fig. 5) exceeds 4000 A If capacitors are detuned (Fig. 6) the peak is only 500 A The latter case shows the influence of inductivity and precontacts of a capacitor contactor, the peak current (Fig. 7) is reduced to approx. 200 A
EPCOS AG
11
Herausgegeben von EPCOS AG, Marketing Kommunikation Postfach 801709, 81617 Mnchen, DEUTSCHLAND (089) 636-09, FAX (089) 636-2 2689 EPCOS AG 2000. Alle Rechte vorbehalten. Vervielfltigung, Verffentlichung, Verbreitung und Verwertung dieser Broschre und ihres Inhalts ohne ausdrckliche Genehmigung der EPCOS AG nicht gestattet. Mit den Angaben in dieser Broschre werden die Bauelemente spezifiziert, keine Eigen-schaften zugesichert. Bestellungen unterliegen den vom ZVEI empfohlenen Allgemeinen Lieferbedingungen fr Erzeugnisse und Leistungen der Elektroindustrie, soweit nichts anderes vereinbart wird. Diese Broschre ersetzt die vorige Ausgabe. Fragen ber Technik, Preise und Liefermglichkeiten richten Sie bitte an den Ihnen nchstgelegenen Vertrieb der EPCOS AG oder an unsere Vertriebsgesellschaften im Ausland. Bauelemente knnen aufgrund technischer Erfordernisse Gefahrstoffe enthalten. Ausknfte darber bitten wir unter Angabe des betreffenden Typs ebenfalls ber die zustndige Vertriebsgesellschaft einzuholen.
Published by EPCOS AG, Marketing Communications P.O.B. 801709, 81617 Munich, GERMANY ++49 89 636-09, FAX (089) 636-2 2689 EPCOS AG 2000. All Rights Reserved. Reproduction, publication and dissemination of this brochure and the information contained therein without EPCOS prior express consent is prohibited. The information contained in this brochure describes the type of component and shall not be considered as guaranteed characteristics. Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers Association), unless otherwise agreed. This brochure replaces the previous edition. For questions on technology, prices and delivery please contact the Sales Offices of EPCOS AG or the international Representatives. Due to technical requirements components may contain dangerous substances. For information on the type in question please also contact one of our Sales Offices.