ODIN Meter An electricity energy meter from ABB

Technical documentation

ODIN Meter

Contents
General description .............................................................................................................. 2 OD4165 direct connection, 3 phase meter up to and including 65 A ............................... 3 OD4110 transformer connection, 3 phase meter ............................................................... 4 Accessories .......................................................................................................................... 5 Wiring diagrams ................................................................................................................... 6 Device dimensions ................................................................................................................ 7 Examples of connections ...................................................................................................... 8

ABB

ODIN Meter
General Description

ODIN Meter is a compact electricity energy meter made for measuring active electrical energy and designed to be mounted on a DIN rail in distribution boards or in standard cabinets. During the development process creating SIMPLICITY was the number one priority. The ODIN Meter shall be perceived as easy to install, use and distribute.
St375010

Examples of this can already be seen on the front of the electricity energy meter, clear marking, strong screws in the connecting terminal and an easy to read display. Enclosed in the carton are easy to understand instructions, which use text and diagrams to describe in detail how the installation should be carried out. The ODIN Meter is certified according to the international standard IEC 61036. The standard covers several technical requirements including climate, mechanics, electronics, EMC and accuracy. Furthermore the ODIN Meter has a national approval from Swedens Test and Research Institute (SP) as a revenue meter. This guarantees the ODIN Meter is highly reliable, has a long life expectancy and maintains its measuring accuracy.

ABB

ODIN Meter
OD4165 direct connection, 3 phase meter up to and including 65 A
Article number 2CMA131024R1000 Technical Data
St375010

Type OD4165

Voltage (V) 230/400V

Pulse output frequency 100 imp./kWh

Voltage: Voltage range Max current Start current Power consumption of current circuits Frequency Accuracy of measurement Standard Temperature range Material of front cover Material of back cover Resistance to heat and fire Protection against penetration of dust and water Connection area in the current connecting terminals Pulse output Connection area in the connecting terminal External pulse voltage Max. current Pulse length Pulse frequency Standard LED Pulse frequency Pulse length Display 100 imp/kWh 40 ms LCD with 7 digits without a decimal place, 6 mm 0.5 2.5 mm2 5 40 V DC 100 mA 100 ms 2.5 ms 100 imp/kWh IEC 62053-1 (S0) 3x230/400 V AC -20% to +15% 65 A 25 mA < 3 VA/phase 50/60 Hz Class 2 (2%) IEC 61036 -25 to +55oC Polycarbonate Polycarbonate/glass fibre Equivalent to IEC 695-2-1 IP 20 1 16 mm2

Front view

Direct connection
Type description Wiring diagram

OD4165

LED frequency
St375004

Drestromzahler 5(65)A Kl.2 Electricity meter 5(65)A Cl.2

Phase indicator Load indicator

Identification No.

National approval symbol (SP)

Pulse output frequency

ABB

ODIN Meter
OD4110 connection via external current transformers, 3 phase meter
Article number 2CMA131025R1000 Type OD4110 Voltage (V) 230/400V Pulse output frequency 1 imp./kWh

St375010

Technical Data Voltage: Voltage range Max. current Starting current Power consumption of current circuits Power consumption of voltage circuits Frequency Accuracy of measurement Standard Temperature range Programmable transformer ratios

3x230/400 V AC
-20% to +15% 10 A 15 mA < 0.02 VA/phase < 2 VA/phase 50/60 Hz Class 2 (2 %) IEC 61036 -25 to +55oC 5/5, 75/5, 100/5 150/5, 200/5, 250/5, 300/5, 400/5, 500/5, 600/5, 700/5 750/5, 800/5, 900/5 A/A Polycarbonate Polycarbonate/glass fibre Equivalent to IEC 695-2-1 IP 20 1 16 mm2 0.5 6 mm2

Material of front cover Material of back cover Resistance to heat and fire Protection against penetration of dust and water Connection area in the current connection terminal Connection area in the voltage connection terminal Pulse output Connection area in the connection terminal External pulse voltage Max. current Pulse length Pulse frequency Standard LED Pulse frequency Pulse length Display

0.5 2.5 mm2 5 40 V DC 100 mA 100 ms 2.5 ms 1 imp/kWh IEC 62053-1 (S0)

1000 imp/kWh 40 ms LCD with 7 digits whitout a decimal place, 6 mm

Front view

Connection via current transformer


Type description Adjustable transformer ratio Wiring diagram

LED frequency
St375005

Phase indicator Load indicator

Identification No.

National approval symbol (SP)

Pulse output frequency

ABB

ODIN Meter
Accessories

Article number 09 809 25 09 811 84


St375002

Type Protective sealable flap Front mounting kit Enclosure (6 modules)

Use When sealing For panel mounting For wall mounting

Picture No.

2 3

09 809 50

Picture No. 2

45,5
St375003

106 161
Mt375003

Picture No. 3

160

St375001

180

175

ABB

80
92 Mt375001

ODIN Meter
Wiring diagrams

Wiring diagrams Direct connection Connection via current transformer

L1 L2 L3
St375006

P1 P1 P1

P1 S1

P2 S2

N PE
2 5 8
St375007

11

20 21

+ -

11

Pulse output

St375008

St375009

ABB

ODIN Meter
Device dimensions

Device dimensions

6.6
7.1

5.7

4,7

57.4 8.75 17.5 44

O 5.3

O 7.4

85

45

O 4.4

24.8 105

20

63,4

Mt375002

ABB

ODIN Meter
Examples of connections

Connections with cables

The electricity meter will function correctly with the neutral connected to either the upper or lower terminal

Connections with cables and busbar

ABB

ABB Automation Technology Products AB Cewe Box 1005 S-611 29 Nykping, Sweden Phone Int +46 155-29 50 00 Fax Int +46 155-28 81 10

29551 Eng Oct 01 ODIN Meter