Professional Documents
Culture Documents
Wwe PM 2013
Wwe PM 2013
Stamford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: VFD O.L. Config: Bypass O.L. Config: VFD U.V. Config: System Check Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps Enable (Time) / Data X 75 F 117 F X X X *1 VFD Freq Limits: 12 TO 60 Hz 1.1.3.5 6 DC UNDERVOLTAGE LPJ-125SP 780S/110% www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 1 OVER-CURRENT Main Fuses: VFD I-Limit Setting: 59.47 KH 1 OVER-CURRENT N/A 116
AHU-1-S
ABB ACH401606032
4/13/13
Penthouse 427369
System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 487 232 5 25 Vac Vac Amps Amps C-A: C-A: C: C: 487 231 5 25 2 Vac Vac Amps Amps Vac
DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 487 231 5 24 Vac Vac Amps Amps 631 B-C: B-C: B: B: Vdc
DC Level:
AC Level:
STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: N/A N/A Vdc Vdc DC Level: DC Level: DC Level: 669 10 22 Vdc Vdc Vdc
OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 55 150 122 Vac mVac mVac Vac mVac mVac
*1=drive status LED out-changed with new bulb 4/13/13 Need to order customer 3 replacement fuses BUSSMAN 125A 170M1368. Ship fuses to Mike Parra 1241 East Main st, Stamford. 06902
WWE World HQ
Stamford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: VFD O.L. Config: Bypass O.L. Config: VFD U.V. Config: System Check Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps Enable (Time) / Data X 75 F 94 F X X X X VFD Freq Limits: 12 TO 60 Hz 1.1.3.4 2 DC OVERVOLTAGE LPJ-30SP 1050S/110% www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 2 DC OVERVOLTAGE Main Fuses: VFD I-Limit Setting: 59.50 KH 2 DC OVERVOLTAGE N/A 25.3
AHU-1-R
ABB ACH401601132
4/13/13
Penthouse 2011600167
System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 486 274 4 8.6 Vac Vac Amps Amps C-A: C-A: C: C: 485 273 4.2 9.2 2 Vac Vac Amps Amps Vac
DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 488 273 3.9 9.3 Vac Vac Amps Amps 656 B-C: B-C: B: B: Vdc
DC Level:
AC Level:
STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 672 10 24 Vdc Vdc Vdc
OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: >1 2 654 142 Vac mVac mVac Vac mVac mVac
VFD plastic cover is brittle, repaired with tape. Try to obtain a replacement cover
WWE World HQ
Stamford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: VFD O.L. Config: Bypass O.L. Config: VFD U.V. Config: System Check Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps Enable (Time) / Data X 24.4C 28.7C X X X X VFD Freq Limits: 20 TO 60 Hz 313A HEX 0 N/A 700S/110% 0 Main Fuses: VFD I-Limit Setting: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 16.93KH 0 N/A 27.7
HWP-1
ABB ACH550UH023A4
4/13/13
Penthouse 2090701202
System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 486 81.6 .5 3.2 Vac Vac Amps Amps C-A: C-A: C: C: 484 81.8 .5 3.2 6 Vac Vac Amps Amps Vac
DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 487 81.6 .5 3.2 Vac Vac Amps Amps 665 B-C: B-C: B: B: Vdc
DC Level:
AC Level:
STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: N/A N/A Vdc Vdc DC Level: DC Level: DC Level: 664 10 22 Vdc Vdc Vdc
OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 1.5 0 20 N/A Vac mVac mVac Vac mVac mVac
WWE World HQ
Stamford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: VFD O.L. Config: Bypass O.L. Config: VFD U.V. Config: System Check Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps Enable (Time) / Data X 24.4C 36.4 X X X X VFD Freq Limits: 20 TO 60 Hz 313A HEX 1 N/A 700S/110% 6 Main Fuses: VFD I-Limit Setting: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 7.12KH 6 N/A 27.7
HWP-2
ABB ACH550UH023A4
4/13/13
Penthouse 2090201478
System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 484 75 .5 * Vac Vac Amps Amps C-A: C-A: C: C: 484 75 .5 * 15.8 Vac Vac Amps Amps Vac
DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 486 75 .5 3.3 Vac Vac Amps Amps 645 B-C: B-C: B: B: Vdc
DC Level:
AC Level:
STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: N/A N/A Vdc Vdc DC Level: DC Level: DC Level: 664 10 22 Vdc Vdc Vdc
OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 2 5 600 N/A Vac mVac mVac Vac mVac mVac
WWE World HQ
Stamford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: VFD O.L. Config: Bypass O.L. Config: VFD U.V. Config: System Check Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps Enable (Time) / Data X 75 F 88 F X X X X VFD Freq Limits: 12 TO 60 Hz 1.1.3.4 0 LPJ-30SP 1050S/110% 0 Main Fuses: VFD I-Limit Setting: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 68.21KH 0 N/A 25.3
AHU-2-R
ABB ACH401601132
4/13/13
Penthouse 2011600166
System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 485 152 1.1 7.3 Vac Vac Amps Amps C-A: C-A: C: C: 483 152 1 7.1 2 Vac Vac Amps Amps Vac
DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 484 151 1 7.2 Vac Vac Amps Amps 663 B-C: B-C: B: B: Vdc
DC Level:
AC Level:
STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 672 10 24 Vdc Vdc Vdc
OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: >1 10 53 140 Vac mVac mVac Vac mVac mVac
keypad and mount broke, taped keypad in so it would stay in place. 10/29/2011
WWE World HQ
Stamford, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: VFD O.L. Config: Bypass O.L. Config: VFD U.V. Config: System Check Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps Enable (Time) / Data X 75 F 113 F X X X *1 VFD Freq Limits: 12 TO 60 Hz 1.1.3.5 1 OVER-CURRENT LPJ-125SP 780S/110% www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 1 OVER-CURRENT Main Fuses: VFD I-Limit Setting: 68.18 KH 1 OVER-CURRENT N/A 116
AHU-2-S
ABB ACH401606032
4/13/13
Penthouse 427369
System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 483 202 6.4 25 Vac Vac Amps Amps C-A: C-A: C: C: 482 203 5.2 Vac Vac Amps
DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 484 203 5.2 Vac Vac Amps B-C: B-C: B: B: Vdc
DC Level:
AC Level:
STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: N/A N/A Vdc Vdc DC Level: DC Level: DC Level: 679 10 22 Vdc Vdc Vdc
OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: >1 12 126 122 Vac mVac mVac Vac mVac mVac