SPECIFICATION PREFACE SHEET

DEPARTMENT:

Engineering / Electrical

SHEET

OF

8 REV: C2

AREA: Norurl Grundartangi Reduction Plant

SPEC No: 00/07/TS001

STANDARD TECHNICAL SPECIFICATION FOR INSTRUMENTATION

GENERAL OVERVIEW

This Standard Technical Specification is subject to change without prior notice. The most current issue will at all times be located on the Nordural web site, www.nordural.is

REV C1 C2

BY HRY IMJ

DATE 01/03/1999 29.3.2004

CHKD GP TDS/J

APPROVED TMS J

REVISIONS Issued for Construction Issued for Construction

NORURL - ENGINEERING

NORURL
NORDIC ALUMINUM

STANDARD TECHNICAL SPECIFICATION 00/07/TS001

CONTENTS SPECIFICATION PREFACE SHEET _________________________________________ 1

TECHNICAL SPECIFICATION__________________________________________ 3
1.0 2.0 3.0 4.0 5.0 5.2 5.3 GENERAL ________________________________________________________________ 3 REFERENCE STANDARDS _________________________________________________ 5 HAZARDOUS AREAS ______________________________________________________ 6 INSTRUMENT AIR SUPPLY ________________________________________________ 6 DOCUMENTATION ________________________________________________________ 7 LOOP DIAGRAM __________________________________________________________ 7 INSTRUMENT INDEX______________________________________________________ 7

NORURL -2-

29.3.2004, REV. C2

NORURL
NORDIC ALUMINUM

STANDARD TECHNICAL SPECIFICATION 00/07/TS001

TECHNICAL SPECIFICATION
1.0 GENERAL
In this Document the following words and expressions shall have the meaning hereby assigned to them except where the context otherwise requires: Engineer: The Owner or any person or organization employed or engaged at any time by the Owner and authorized by the Owner, in writing, from time to time to act on behalf of the Owner in the execution of the items covered by this Document, in whole or in any part, for any or all purposes provided in this Technical Specification. Owner: Norurl hf (Nordic Aluminum Corporation Ltd.), an independent legal entity owned by Century Aluminum. This Specification covers the general requirements for instrumentation and control of type and manufacture. The objective shall be to standardise all measurement and control equipment throughout the plant in order to rationalise operation, maintenance and spares holding. Reference shall be made to the Preferred Vendors list (see Appendix 1). Equipment to be supplied and not covered or which do not conform to this list due to the manufacturers own standards shall be submitted for approval. In addition to the requirements of this specification all equipment offered to meet the requirements of instrumentation and control shall also comply where appropriate with other general technical requirements of associated specifications as defined in Section 6.0 of this specification. A consistent control and instrumentation philosophy shall apply throughout the plant and shall be implemented in terms of a range of equipment exhibiting a minimum diversity Generally equipment shall be supplied from one composite range of measurement and control equipment as marketed by a reputable manufacturer of international standing. The equipment shall be of modern compact design incorporating the latest developments in proven technology. Data Acquisition/Logging facilities with recording and indicating instruments shall be provided for those parameters whose trends are considered necessary for product quality, optimum plant operation and plant performance records. Integrating or totalising facilities shall be provided for selected flow measurements especially those related to plant performance and output.

NORURL -3-

29.3.2004, REV. C2

NORURL
NORDIC ALUMINUM

STANDARD TECHNICAL SPECIFICATION 00/07/TS001

All instrument control panels shall be provided with internal lights and utility sockets at 230 VAC 50 Hz. Analogue signals shall be standardised at 4-20 mA Any other analogue signal levels proposed shall be submitted for approval. Direct current plant status and alarm signals shall be standardised on a d.c. voltage level between 22 to 50 volts. Pneumatic transmission and control signals where offered, shall be of the 0.2 - 1 Bar. Measurement and control instrumentation shall have high electro- magnetic and radio frequency interference immunity and shall not be affected by portable radio transmitters operated in the vicinity of the equipment. Any limitations shall be stated by the Supplier. All instruments whether for local indication or remote transmission shall be of good quality and shall have an accuracy and repeatability appropriate to their duty. The supplier shall state the accuracy and repeatability of each instrument offered which shall be certified, when supplied, by means of supporting documentation. All electronic devices shall be protected against transient voltage levels that would otherwise damage the device. The ranges of all instruments shall be arranged, where practicable, so that normal working indication is at approximately 75% of full-scale deflection. Measurement and control instruments shall be matched to the main plant equipment ratings in all aspects. Instrument ranges, installation codes of practice and precautionary measures for safety of the Plant and the operating and maintaining personnel shall be observed. All instruments and devices to which electrical connections are made shall have approved type of terminations, connections and cable entries and cable glanding where applicable. Each instrument shall be properly labelled, and shall be identified by appropriate tag numbers; permanent non- perishable nameplates attached to each instrument shall be used for this purpose. The instrument duty or nameplate shall be mounted on the panel front and rear beneath the instrument. A similar label shall be fitted beneath each of the instrument modules

NORURL -4-

29.3.2004, REV. C2

NORURL
NORDIC ALUMINUM

STANDARD TECHNICAL SPECIFICATION 00/07/TS001

mounted in cubicles. These shall be of laminated plastic or transparent plastic back engraved with black writing on a white background. All field junction boxes shall be to IP66 rating with hinged door.

2.0

REFERENCE STANDARDS
The following references cover the standards referred to in the Specifications of Section 5.0. Icelandic Government Electrical Codes and Regulations no:264/1971 Icelandic Government Health and Safety at Work Act no:46/1980 ISA S5.1: Instrumentation Symbols and Identification IEC 60617 Symbols on Electrical drawings DIN 2403 Identification of process pipes and systems EN 60146: Semiconductor convertors BS 1042 Methods for the measurement of fluid flow in pipes. EN 837.1/2/3 Bourdon tube pressure and vacuum gauges. EN 60751 Industrial platinum resistance thermometer elements. BS 3693 Recommendations for the design of scales and indexes. ISO 10816 Basis for specifying evaluation standards for rotating macines with operating speeds from 10 to 200 revolutions per second.

NORURL -5-

29.3.2004, REV. C2

NORURL
NORDIC ALUMINUM

STANDARD TECHNICAL SPECIFICATION 00/07/TS001

ISO 2954 Requirements for instruments for measuring vibration severity. IEC 60079 Code of practice for the selection, installation and maintenance of electrical apparatus for use in potentially explosive atmospheres (other than mining applications or explosive processing and manufacture).

EN 60584 Iternational Thermocouple Reference Tables. EN 61131.1/2/3 Programmable Logic Controllers API 670 Vibration, Axial Position and Bearing Temperature Monitoring Systems The Nordural Standard Technical Specifications

3.0

HAZARDOUS AREAS
All equipment for use in hazardous areas shall meet the requirements of EN60079 or equivalent standard. Either the use of I.S. barriers or explosion proof construction will be acceptable, however all equipment for use in these areas shall have the necessary certification by the appropriate certifying body and will comply fully with all the conditions of said body.

4.0

INSTRUMENT AIR SUPPLY


Dried oil-free compressed air shall be distributed to those instruments and actuators using air. Unless otherwise specified the dewpoint of dried air shall be down to at least 40C. All instruments installed external to control houses shall be provided with individual reducing regulators and air filter sets.

NORURL -6-

29.3.2004, REV. C2

NORURL
NORDIC ALUMINUM

STANDARD TECHNICAL SPECIFICATION 00/07/TS001

Where a common reducing regulator and filtering assembly is fitted, it shall be duplicated and the system provided with block valves to enable one unit to be on standby service. Safety relief and pressure indicator shall be provided on the reduced air side of the system. Air receivers shall have a capacity such that the maximum safety rundown period for the plant shall be carried out at the full-required pressure of the instrument and actuator system. Compressors provided for instrument air supply shall be of the dry cylinder type, i.e. which use no oil on the parts exposed to the compressed air. The installation of leads, pneumatic, electrical, shall be so as to minimise the possibility of damage by fire, mechanical shock and continuous vibration.

5.0

DOCUMENTATION
Documentation shall include but not be limited to the following: (a) Instrument Data Sheets (b) Loop Diagrams (c) P & ID's (d) Installation Details (Electrical and Mechanical Hook-up Details) (e) Instrument Index (f) Cable Schedule (g) Location Diagram (Plot Plan) (h) Trip and Alarm Schedule (i) Material Schedule The specific requirements for Loop Diagrams and the Instrument Index are given below.

5.2

LOOP DIAGRAM
Instrument loop diagrams shall be provided for all instrument loops as scheduled and supplied. The diagrams shall identify all instruments, their location, their wire connections including any intermediate stages of marshalling and giving all core references in such a way that each loop may be followed from its sensing element to its final indicating or actuating element without reference to any additional documentation.

5.3

INSTRUMENT INDEX

NORURL -7-

29.3.2004, REV. C2

NORURL
NORDIC ALUMINUM

STANDARD TECHNICAL SPECIFICATION 00/07/TS001

Instrument index shall be provided listing all instruments for each system including loop items of equipment and shall include but not limited to Recorders, Controllers, Transmitters, Receiver Gauges, Air Sets, Control Valves and Solenoid Valves. The Instrument Index is required to conform with ISO 9002 procedures and shall contain all relevant information for each item of equipment such as the tag number, functional group/functional subgroup reference, location, manufacturer, requisition number, type or style, size, hook-up drawing, location drawing etc. Each instrument or items of an instrument loop shall be supplied with a tag or identification number in accordance with ISA and this number shall be used for all reference purposes.

NORURL -8-

29.3.2004, REV. C2