DESIGNATION

AREA SERVED

QTY

COOLING CAPACITY SENSIBLE (KW) 10.7 10.7 7.8 4.7 3.1

CU-FB/B-1 FCU-FB/B-1 CU-FB/B-2 FCU-FB/B-2 - 1 FCU-FB/B-2 - 2

TOTAL (KW) Forest Bungalows Type B (Typical for 4 units) 1 12.5 Living Room 1 12.5 8.2 4.9 3.3

AIR-COOLED SPLIT AIR-CONDITIONING UNIT SCHEDULE EVAPORATOR SECTION ESTIMATED SUPPLY AIR QTY ENTERING AIR CONDITION ESTIMATED EXT. SP MOTOR (CMH) (C) DB/WB (Pa) (kW) 2460 1190 640 25.8/17.8 25.6/17.2 25.6/17.2 150 -

CONDENSER SECTION ENTERING ESTIMATED AIR MOTOR (C) DB (kW) 35 35 -

TYPE POWER CONSUMPTION (kW) 4.75 2.5 POWER SUPPLY (V//Hz) 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50

REMARK

CU/FCU Single Split Concealed Ducted Multi Split Wall Mounted Wall Mounted

Master Bedroom Master Bedroom

1 1

CU-FB/B-3 FCU-FB/B-3-1 CU-FB/B-4 FCU-FB/B-4

Bedroom 1

1 1 1 1

6.5 6.5 6.5 6.5

6.1 6.1 6.1 6.1

1510 1450

25.1/17.1 25.5/17.2

35 35 -

2.1 2.1 -

230/1/50 230/1/50 230/1/50 230/1/50

Single Split Wall Mounted Single Split Wall Mounted

Bedroom 2

CU-CV-1 FCU-CV-1 CU-CV-2 FCU-CV-2 CU-CV-3 FCU-CV-3

Corallium Villas (Typical for 150 units) 1 Living/Dining Room 1 1 1 1 1

11.6 11.6 5.4 5.4 4.5 4.5

10.3 10.3 5.0 5.0 4.1 4.1

2380 1190 980

25.9/17.7 25.5/17.3 25.6/17.4

150 -

35 35 35 -

4.75 2.1 1.78 -

230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50

Single Split Concealed Ducted Single Split Wall Mounted Single Split Wall Mounted

PROPOSED DEVELOPMENT OF FUNTASY ISLAND AT PULAU MANIS, BATAM, PROVINSI KEPULAUAN RIAU, INDONESIA - (PACKAGE A)

Bedroom 1

Bedroom 2

DESIGNATION EAF-CV-1 EAF-CV-2 EAF-CV-3

AREA SERVED Corallium Villas Bathroom 1 Bathroom 2 Bathroom 3

DESIGN FLOW (CMH) 100 100 100

ESTIMATED EXT. SP (Pa) 120 120 120

FAN TYPE In-line Centrifugal In-line Centrifugal In-line Centrifugal

MOTOR (kW) 0.1 0.1 0.1

POWER SUPPLY (V/ph/Hz) 230/1/50 230/1/50 230/1/50

REMARK

NOTES: 1. EXHAUST AIR FAN SHALL BE INTERLOCKING WITH LIGHTING SWITCH.THE EXHAUST AIR FAN SHALL BE RUNNING WHEN THE SWITCH IS ON AND VICE-VERSA.