MobiIe dieseI UPS system (500kVA)

Diesel backed, rotary UPS system, with a rating of


500 kVA, housed in a sound isolated standard SO
container. All necessary ancillary items such as
exhaust and fuel systems are integrated.








TechnicaI specifications
Max. rating 500-kVA p.f. 0.8 = 400kW
Nominal voltage 400/231 V
nput current nom. 660 A, max. 722 A
Output current 722 A at p.f. 0.8
578 A at p.f. 1.0
Weight 24,000 kg
Dimensions (lxwxh) 12.2 x 2.44 x 2.59 m
Min. height over exhaust 3.5 m
Fuel tank 2000 lt./1300 lt.
Max. running time at full load approx. 20 hr/13 hr
Max. sound level at 10 metre,
in mains operation 55 dB(A)
in emergency operation, half load 70 dB(A)
in emergency operation, full load 72 dB(A)
Erection place hard standing surface

Connections and operation
Cable entry via Multi Cable Transit.
Terminals for mains, load and remote alarms in the separated operating room of the container.
Operation panel in the separated operating room of the container.
Earthing facility on the skid.
Standard 40 SO containers with corner castings for easy transportation.
Fuel filling facilities on both sides of the container.


Hitec Power Protection RentaI bv
P.O. Box 65
7600 AB AImeIo
The NetherIands
Phone: +31 546 589 589
Fax: +31 546 589 489
E-maiI: info@hitec-ups.com
www.hitec-ups.com