PROCEDURE FOR CHANGING THE MENU TEXT IN P*30 SERIES RELAYS To change the menu text in 30 series relays

first a new data model has to be created with the customised text. Step by Step Procedure: Select Micom S1 -> P*30 series. Select S&R 103 Go to File and follow the path Open C:\Program File\Areva T&D(Alstom if software is very old)\ MiCOM S1\S&R 103\Dmod (select type of file Data Model) & select open. Now select the same data model of the relay which the menu changing is required. For Ex: Gpx63302.602 Text Version Select Language 1 English/English.

Now click on Dictionary The following message will appear on the monitor Do you wish to replace the customized texts by dictionary texts Click on Yes. Now click on Original Texts The following message will appear on the monitor. Do you wish to replace the customized tests by original data model texts Click on Yes. Now click on Addresses. Select the place in which the text has to be replaced. Now in this case it is Inputs (Inp) Replace the text which needs to replaced for the required function by clicking on Customized Text cell & replace with new text after making the necessary changes click on Close. Now on the Monitor the following message will be appear. Do you wish to save the dictionary data model with updated customized text. Click on yes for both the windows. Now you will find a New data model which is created as for example. Gpx63312.602 Now establish the communication with the relay. Go to communication menu and select Send Data Model menu. Click on Yes. Select the data model type, which needs to be sent, say Gpx63312.602 Keep the screen as it is. Select the relay in load mode by switching off the Aux. Supply of the relay.

Now go to the relay. Press C & Enter keys simultaneously and powering up the relay. Enter the following password using local display. UP-DOWN-LEFT-RIGHT-DOWN-LEFT-RIGHT-UP. On the display of the relay it shows as below: Flash EPROM Program Version 2.11 Baud Rate 9600 Click on the screen. Now the new data model with changed text file shall get downloaded to the relay. After completion of downloading the data model Do you wish to restart the device now will be appearing on the monitor. Select Yes. Now on the monitor Data model transmitted successfully will appear click OK Now extract the relay settings from the relay by Device Identify device Identify Click on setting file Communication Read Value. Now read out the device settings.

You might also like