Sl no.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Description EPB (UCB) (2 channels) Boiler trip to turbine trip (2 channels) Generator trip to turbine trip (2 channels) Lube oil pr. lo lo <1.1ksc (2/3 channels ) Condenser pr. hi hi>0.3 ksc abs.( 2/3 channels.) Fire protection (2 channels) Bushing cahmber level hi hi > 75%( 2 channels) Cold gas temp hi hi>60 *C ( 2 channels) Alarm : > 55 deg C Seal oil temp hi hi >55*C ( 2 channels) Alarm: >50 deg C Exciter hot air temp hi hi>80*C ( 2 channels) Alarm : > 75 deg C Primary water temp hi hi> 60*C ( 2 channels) Alarm : > 55 deg C Primary water flow lo lo< 14.4 dm3 ( 2 channels) Alarm : < 16.25 dm3 Bushing U-PH P.W. flow lo lo < 0.37 dm3( 2 channels) Alarm: < 0.39 dm3 Bushing V-PH P.W. flow lo lo < 0.37 dm3 ( 2 channels) Alarm: do Bushing W-PH P.W. flow lo lo < 0.37 dm3 ( 2 channels) Alarm: do HP casing middle 50% top - bottom DT hi hi >+/_ 45 * C ( 2 channels ) Alarm : >+/_ 30 deg C IP casing front 50% top - bottom DT hi hi > +/_45 *C ( 2 channels ) Alarm: do IP casing rear 50% top - bottom DT hi hi > +/_45 * C ( 2 channels ) Alarm: do HP exhaust steam temp hi hi> 500*C(2channels) Electrical Over speed