Over current
Short circut
Earth fault

Current setting
1 In
5 In (tr)
0.2 In (ct)

Over current
Short circut
Earth fault

Current setting
1 In
5 In (tr)
0.2 In (ct)

Over current

Current setting
1 In

Time setting
0.7 sec (700 ms)
0.0
0.7 sec (700 ms)

/2
Time setting
0.3 sec (300 ms)
0.0
0.3 sec (300 ms)


Time setting
7.5 sec

/3
( )
Over current
Short circut
Earth fault

Current setting
1 In

Time setting
0.1 sec (100 ms)

0.2 In (ct)

0.1 sec (100 ms)

( )
Over current
Short circut
Earth fault

Current setting
1 In

Time setting
0.5 sec (500 ms)

0.2 In (ct)

0.5 sec (500 ms)


Over current
Short circut
Earth fault

Current setting
0.75 In
3 In(ct)

Time setting
0.3 sec (300 ms)
0.0


11/66 ( O.C)
66
Current setting
Over current
Short circuit

[(1.5* Irated)/ c.t.R]* In


[(1.6* Irated)/ (Z%*c.t.R]* In

Earth fault

0.3In

0.1In

1.1 sec

[(1.5* Irated)/ c.t.R]* In


[(1.3* Irated)/ (Z%*c.t.R]* In
0.3In

0.1In

Earth fault

1.1sec
0.0
1.1 sec

11
Current setting
Over current
Short circuit

Time setting

Time setting
1.0sec
0.0
1.0 sec
1.0 sec

:
Power Transformer 66/11
C.T (66)
C.T (11)
Percentage impedance

25 MVA
300/1
1500/1
10 % = 0.1

M VA

I66=

3* KV

= [(25* 106)/ (3*66*103)] =218.7 A

M VA

I11=

3* KV

= [(25* 106)/ (3*11*103)] =1312.2 A

I (O.C) 66= [(1.5* Irated)/ c.t.R]* In= [(1.5* 218.7)/ 300]* In=1.09 In
I (O.C) 11= [(1.5* Irated)/ c.t.R]* In= [(1.5* 1312.2)/ 1500]* In=1.312 In
I (S.C) 66= [(1.6* Irated)/ (Z%*c.t.R]* In=[(1.6* 218.7)/ (0.1*300]* In = In
I (S.C) 11= [(1.3* Irated)/ (Z%*c.t.R]* In=[(1.3* 1312.2)/ (0.1*1500]* In = In


(T.L) ( O.C)
distance relay back up protection
220 2.5 sec 66 1.5sec
. 800 66 ( O.C)
. 1200 220 ( O.C)
:
--- F
---or 220kv T.L, c.t 800/5
Over current setting (primary) = (1200/ 800)* In
= 1.5 In
(Secondary value)= 1.5*5 = 7.5 A

-------For 220kv, c.t 800/1


Over current setting (primary) = (1200/ 800)* In
= 1.5 In
(Secondary value)= 1.5*1 = 1.5 A

-------For 66kv, c.t 800/1


Over current setting (primary) = (800/ 800)* In
= 1 In
(Secondary value)= 1*1 = 1 A

0.3
2.5

220kv

2.5

2.2

220/66
kv

1.5

66kv

1.5

1.1

66/11
kv

1.0

0.7

0.3