Detailed Specification for the Design of Narrow Base Tower

Type of Tower Angle of Deviation Extensions Base Width Type of Power Conductor Type of Ground wire Wind Zone Reliability level 220 KV Double Circuit tower 15 to 30 Degree 3M, 6 M and 9 M 7.0M for 9M extension Twin moose ACSR 7/3.66 Galvanised steel 2 1

Terrain category / Ground roughness coefficient - 2

Conductor Details
Conductor type Overall Diameter Gross sectional area Unit weight Ultimate tensile strength Coefficient of thermal expansion Modulus of elasticity -

ACSR Twin moose


31.77 mm 597 sq mm 1998 KG/KM 16274.67 KGs 19.3 X106 /deg C 703600 KG/sq cm

Ground wire
Conductor type Overall Diameter

Galvanised steel
10.98 mm

Gross sectional area Unit weight

73.646 sq mm 575 KG/KM 6974 KGs 11.5 X106 /deg C 1927263 KG/sq cm -

Ultimate tensile strength Coefficient of thermal expansion Modulus of elasticity

Span Details
Normal span Wind span 335 M 325 M Weight span Max 600 500 Min -200 -200

Normal condition Broken wire condition

The existing sag tension calculation of Moose conductor and earth wire may be adopted based on normal span

Moose Conductor
Sl no 1 2 3 4 5 Temperature 32 32 0 0 75 Wind factor 0 1 0 0.36 0 Vertical sag 8.565 4.959 7.27 6.46 10.18 Tension Kg 3305.17 5708.46 3893.67 4382.33 2780.87 Factor of safety 4.924 2.851 4.18 3.714 5.852

Maximum Sag - 10.18 M Max Tension - 5708.46 Kg

Ground wire 7/3.66


Sl no 1 2 3 4 Temperature 32 32 0 0 Wind factor 0 1 0 0.36 Vertical sag 7.374 3.865 6.543 5.554 tension 1104.86 2107.85 1245.08 1466.81 Factor of safety 6.312 3.309 5.601 4.755

75

7.905

1030.57

6.767

Maximum sag - 7.905 M Max Tension - 2107.85 Kg

Climatic Conditions
Everyday Temperature Minimum Temperature Maximum Temperature Conductor Maximum Temperature Ground wire 32 degree 0 degree 75 degree 53 degree

Maximum tensions
Maximum tensions are based up on following At 0 degree with 36 % full wind pressure or At 32 degree with full wind pressure whichever is more stringent

The height of Lowest cross arm may be fixed at 19.85 M from ground to suit the existing sag template for normal tower.

Base dimensions for 9M Extension Tower may be fixed as 7.0 M Length of Bottom cross arm dimension 5950 mm as per the clearance diagram may be reduced to the maximum possible.
The design of tower shall be as per IS 802 ( Part 1, 2,3,4 ) 1995