SPRINKLERS AND ACCESSORIES A. General: 1. 2. Minimum sprinkler orifice size shall be 1/2 inch.

Sprinklers in non-public spaces such as mechanical/electrical equipment, and storage rooms and sprinklers on exposed piping shall have brass finish unless noted otherwise. Sprinklers and escutcheons in finished areas to have polished brass or white finish or finish as noted on plans. Style, size, and temperature rating to be type specifically approved for such use. Thermo sensitive glass bulbs to be of all one color for a given temperature classification. For each sprinkler style, all sprinklers to be of same type (fusible link or glass bulb). Provide Dry type sprinklers in all cold rooms.

3. 4. 5. 6. 7.

B. Upright Sprinklers: 1. 2. 3. 4. Thermo sensitive glass-bulb or fusible solder/alloy standard response. Thermo sensitive glass-bulb quick response. Fusible solder/alloy quick response. Installation style: a. Exposed: No escutcheon C. Pendent Sprinklers: 1. 2. 3. 4. Thermo sensitive glass-bulb or fusible solder/alloy response. Thermo sensitive glass-bulb quick response. Fusible solder/alloy quick response. Installation style: a. Exposed: No escutcheon. D. Sprinkler Guards: Metal with red finish. E. Spare Sprinkler Cabinet: Wall mounted. Storage capacity of not less than minimum designated by.