You are on page 1of 2

NYA 0 (1) 450/750 VOLT

These low voltage flexible cables are applied for dry rooms, fixed installation in pipe and distribution
panel connector
Construction
Solid or stranded annealed copper conductor
Insulation
Extruded colored PVC, capable for the operating continuously maximum temperature of the cable
Sheath
Extruded white PVC suitable for the operating temperature of the cable
Identification of cores
Complying with system O/I (other colors on request)
Specification: SPLN 42-1:1991,
1:1991, SNI 04
04-2698-1992

Physical and electrical properties


cores

Cross
section

No.
of
wire

mm
0.5
0.75
1
1.5
2.5
4
6
10
16

1
1
1
1
1
1
1
7
7

Diameter
max.

Insulation
thickness

Sheath
thickne
ss

Approx
cable
diameter

Approx
cable
weight

mm

mm

mm

mm

Kg/km

2.4
2.6
2.8
3.3
3.9
4.4
4.9
6.4
8.0

8.2
11
14
20
32
47
68
117
178

0.6
0.6
0.6
0.7
0.8
0.8
0.8
1.0
1.0

Resistance at 20C
conduct
insulatio
or
n
M.ohm.k
Ohm/km
m
35.3
51
24.0
51
17.7
51
11.9
51
7.14
48
4.47
44
2.97
37
1.79
36
1.13
26

AC
voltage
test
kV/5
min
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5

Standard
length
m
100
100
100
100
100
100
100
100
500

25
35
50
70
95
120
150
185
240
300
400

7
7
19
19
19
37
37
37
61
61
61

1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6

9.8
11.0
13.0
15.0
17.0
19.0
21.0
23.5
26.5
29.5
33.5

280
377
515
720
980
1220
1505
1878
2550
3070
3910

0.712
0.514
0.379
0.262
0.189
0.150
0.122
0.0972
0.0740
0.0590
0.0461

26
22
22
19
18
16
16
16
16
15
14

2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5

500
500
500
500
500
500
500
500
500
500
500