Professional Documents
Culture Documents
Analysis of A Dynamic System
Analysis of A Dynamic System
BAE 3023
1
6
Controller Tuning
3/22/2006
BAE 3023
2
6
Response
A 0.25 A
Time (s)
3/22/2006
BAE 3023
3
6
Field Tuning of a controller by Quarter Decay Ratio Method Uses field method to determine Kcu and Tu (Similar to Direct Substitution)
Quarter Decay Ratio Field Method Turn OFF integral and derivative controller action Make sure controller is in closed loop mode Increase Kc setting until controlled variable oscillates with steady amplitude Gain setting Kc = Kcu Measure period as Tu Use table 7-1.1 to find controller settings (Ziegler-Nichols)
3/22/2006
BAE 3023
4
6
Quarter Decay Ratio Tuning by system model Find a first order plus dead time model for the system Ke st0
G (s)
s 1
Use step test or First Principals Model Use System ID methods described earlier
Note:
For higher order overdamped systems, if one of the time constants is much longer than the others, an effective model can be formed with the time constant of a first order model equal to the longest time constant and the dead time as the sum of the remaining time constants (and dead time)
3/22/2006
BAE 3023
5
6
3/22/2006
BAE 3023
6
6
Minimum Error Integral Tuning Method Find a first order plus dead time model for the system Use previous note for higher order overdamped systems Select integral error criteria Determine if optimizing for load changes or setpoint changes Use table 7-2.2 to determine controller settings for loads Use table 7-2.3 to determine controller settings for set-points