SprinklerSpacing andLocation
March 5, 2013
National Fire Sprinkler Association 2013
RolandAsp ManagerofTechnicalServices
asp@nfsa.org
RolandAsp ManagerofTechnicalServices
1 National Fire Sprinkler Association 2013 2
CopyrightMaterials
ThispresentationisprotectedbyUSand InternationalCopyrightlaws. Reproduction,distribution,displayanduseof thepresentationwithoutwrittenpermissionof TheNationalFireSprinklerAssociationis prohibited.
NationalFireSprinklerAssociation2013
National Fire Sprinkler Association 2013 4
ProgramDescription
Therulesfordeterminingacceptable spacingforspraysprinklerswillbe reviewed.Thisincludespendent, uprightandsidewallstyles. styles Maximum andminimumdistancesbetween sprinklersandthosefromsprinklersto wallswillbecoveredalongwiththe calculationofallowablecoverageareas persprinkler.
National Fire Sprinkler Association 2013 5
ReferenceMaterials
2ndEdition,Layout,Detail,and CalculationofFireSprinklerSystems, KennethE.Isman,P.E 2013EditionofNFPA13
LearningObjectives
At the end of this program, participants will be able to:
Whatspacesinabuildinggetsprinklers?
Everyspaceinabuildingunless thereisaspecificexceptionthat allowssprinklerstobeomitted. Sprinklerscanbeomittedfrom:
Furniture&Equipment Concealedspacesconstructedof noncombustibleandlimited combustiblematerial 16differentconcealedspacesmade ofcombustiblematerial OtherspacesasdiscussedNFPA13
7 National Fire Sprinkler Association 2013 8
1. Employ the rules for determining acceptable spacing for spray sprinklers. 2. Apply the maximum and minimum distances between sprinklers. 3. Calculate the allowable coverage areas per sprinkler. 4. Apply the small room rule correctly.
GeneralConsiderations
Heatrises sprinklershouldbe locatedclosetoceiling. Gravity waterfromthesprinkler needstoreachfire. Damage D sprinklers i kl should h ldb be locatedtoprotectfromphysical damage
Considerations
Ceilingconstruction Typeofsprinklerselected Minimumallowabledistancebetween sprinklers Placementofwallsandroomdividers Maximumallowabledistancesbetween sprinklers Hazardclassificationoftheoccupancy Obstructionstoheatflowand discharge Heatzonesnearheatsources
9 National Fire Sprinkler Association 2013 10
CeilingConstruction
ObstructedorUnobstructed
ObstructedConstruction
Panelconstructionandother constructionwherebeams, trusses,orothermembers impedeheatfloworwater distributioninamannerthat materiallyaffectstheabilityof sprinklerstocontrolorsuppress afire.
11
12
UnobstructedConstruction
Constructionwherebeams,trusses,or othermembersdonotimpedeheatflow orwaterdistributioninamannerthat materiallyaffectstheabilityofsprinklers tocontrolorsuppress afire. Horizontalstructuralmembersarenot solidandopeningsareatleast70% ofthe crosssectionareaandthedepthofthe memberdoesnotexceedtheleast dimensionoftheopening. Allconstructionwherethespacingof structuralmembersexceeds7.5ft on center.
National Fire Sprinkler Association 2013 13
Sprinklers
Conventional Residential
Spray Sprinklers
Large Drop
Extended Coverage (See Listing)
ESFR
This seminar will concentrate on standard response & quick response spray sprinklers
SprinklerSpacing BasicRules
Upright,PendentandSidewall BasicRules
ProtectionAreaofSprinkler Maximumdistancebetweensprinklers Maximumdistancetoawall
RulesforUprightandPendentSpraySprinklers
15
16
DeterminationofAreaofCoverageforEach Sprinkler(8.5.2.1)
Alongbranchlines
Chooselargerof
Distancebetweensprinklers Twicedistancetowallor obstruction L
SandLDimensionsaremeasuredtothe sprinklers,notthebranchlines
ThisdimensionisS S
Betweenbranchlines
Distancebetweenbranchlines Twicedistancetowallor obstruction
ThisdimensionisL
AreaofCoverage=AS =SxL
National Fire Sprinkler Association 2013 17 National Fire Sprinkler Association 2013 18
DetermineAreaofCoverageforEachSprinkler
Spr. 1 2 3 4 5 6 S 10 12 12 10 12 12 L 10 10 10 12 12 12 AS 100 120 120 120 144 144
19
20
DistanceFromWalls
22
MeasuringDistancestoWalls
Measureperpendiculardistance betweensprinklerandwall (8.5.3.2.2).Thisisthedimension thatisnotallowedtoexceedthe allowable distancebetween sprinklers i kl
MeasuringDistancestoWalls
Forroomswithangleslessthen90, additionalrulethatthedistancefrom sprinklertocornermustnotexceed0.75 allowable distancebetweensprinklers (8.6.3.2.3)
S
S S
23
24
MeasuringDistancestoWalls
Thedistancefromthewalltothe sprinklershallbemeasuredtothe wallbehindfurniture,suchas wardrobes,cabinets,andtrophy cases
MaximumAreaLimitationsStandardSpray SprinklersTable8.6.2.2.1(a)
Light Hazard(HydraulicallyCalculated) MaximumArea of CeilingConstruction CoverageperSprinkler
Noncombustible Unobstructed NoncombustibleObstructed NoncombustibleUnobstructed withno exposedmembers CombustibleUnobstructedwithexposed members3ftor moreoncenter CombustibleObstructedwithexposed members3ftormoreoncenter Combustible(ObstructedorUnobstructed) withmembers lessthan3ftoncenter Woodjoistortruss,specialatticrules 225sqft 225sqft 225sqft 225sqft 168sqft 130sqft 8ftx15ftor 10ftx12ft
26
25
MaximumAreaLimitationsStandardSpray SprinklersTable8.6.2.2.1(a)
Forlighthazardoccupancypipe schedulesystems,themaximum areashallnotexceed200sqftper sprinkler
MaximumAreaLimitationsStandardSpray SprinklersTable8.6.2.2.1(b)
OrdinaryHazard MaximumAreaof CalculationMethod Coverageper Sprinkler All 130sqft
27
28
MaximumAreaLimitationsStandardSpray SprinklersTable8.6.2.2.1(c)
ExtraHazard MaximumArea CalculationMethod ofCoverageper Sprinkler Pi S Pipe Schedule h d l 90sqft Hydraulically calculatedusing0.25 100sqft gpm/sq.ft.ormore Hydraulically calculatedusingless 130sq ft than0.25 gpm/sq.ft.
29
MaximumAreaLimitationsStandardSpray SprinklersTable8.6.2.2.1(d)
HighPiledStorage CalculationMethod Hydraulicallycalculated using0.25gpm/sq.ft.or more Hydraulicallycalculated usinglessthan0.25 gpm/sq.ft. Maximum Areaof Coverageper Sprinkler 100sqft
130sq ft
30
IsThisSpacingacceptableforOrdinaryHazard?
Spr. 1 2 3 4 5 6 S 10 12 12 10 12 12 L 12 10 10 12 12 12 AS 120 120 120 120 144 144
SmallRoomDefinition(3.3.21)
Roomwithinlighthazard occupancies Unobstructedconstruction Floorareasnotexceeding800sqft Eachwallcanhaveopeningswitha8 inchminimumlinteldepthandtotal widthnotexceeding8feet Singleopeningof3feetorless withoutalintelispermitted
31 32
SmallRoomRule
Withinroomsoflighthazardoccupancies havingunobstructedconstructionand floorareasnotexceeding800sqft, sprinklersshallbepermittedtobelocated notmorethan9ftfromanysinglewall Distancesbetweensprinklersand maximumarealimitationsstillapply Theareapersprinklerisdefinedasthe totalareaoftheroomdividedbythetotal numberofsprinklersintheroom
SmallRoomRule
AS = 30 x 15 2 = 225 sq ft
33
34
DeflectorDistancesBelowCeilings
UnobstructedConstruction(8.6.4.1.1.1)
112inchesbelowceiling
UnobstructedConstruction withTrussesandBarJoists
1-12
End View
Side View
National Fire Sprinkler Association 2013 35 National Fire Sprinkler Association 2013 36
DeflectorDistancesBelowCeilings
StandardSpraySprinklers
ObstructedConstruction(8.6.4.1.2)
16inchesbelowstructuralmembers Notmorethan22inchesbelowceiling Seenextfewslidesforsomeexceptions
StandardSpraySprinklers ObstructedConstruction
37
38
ExceptiontoObstructedConstructionRule
[8.6.4.1.2(2)]
ExceptiontoObstructedConstructionRule [8.6.4.1.2(3)]
Sprinklerscanbeinstalledineach bayofobstructedconstruction withdeflectors112inchesbelow theceiling
Sprinklers are allowed to be installed with deflectors at or above members where the distances meet section 8.6.5.1.2 (beam rule)
National Fire Sprinkler Association 2013 39 National Fire Sprinkler Association 2013 40
ExceptiontoObstructedConstructionRule [8.6.4.1.2(4)]
ExceptiontoUnobstructedConstructionRule [8.6.4.1.2(5)]
Deflectorsofsprinklersunder concreteteeconstructionwithstems spacedlessthan7.5ftbutmorethan 3ftoncentershall(regardlessofthe depthofthetee)bepermittedtobe locatedatorabovetheplane1inch belowthebottomofthestemsof theteesandshallcomplywiththe beamrule
42
ConcreteTeesBetween3ftand7.5ftOnCenter
Skylights(8.5.7)
Sprinklersarenotrequiredinskylightsup to32sqftinarearegardlessofthedepth andregardlessofthehazardclassification oftheoccupancy Appliesregardlessofthetypeofsprinkler Ifthereismorethanoneskylightina compartment,theyneedtobeseparated bymorethan10ftinordertoutilizethis provision
43
44
Ceilingpockets(8.6.7)
Sprinklerscanonlybeomittedfromceiling pocketswhenthefollowingaremet
Volumedoesnotexceed1000ft3 Depthofthepocketdoesnotexceed36in Floorspaceunderthepocketiscoveredby sprinklers i kl at tthe th lower l ceiling ili elevation l ti Totalsizeofallunprotectedpocketswithin10 ftofeachotherdoesnotexceed1000cubic feet Constructionisnoncombustibleorlimited combustiblefinish Quickresponsesprinklersareusedthroughout thecompartment
National Fire Sprinkler Association 2013 45
UnsprinkleredCeilingPockets
Noncombustible or limited combustible construction Volume not to Exceed 1000 ft3 Quick response sprinklers completely protect floor area using spacing rules of NFPA 13
Not to exceed 3 ft
46
CeilingPocketExample
Q Aresprinklersrequiredintheupperceilingarea iftheoccupancyislighthazardandthesprinklers areon15x15spacing?Assumeroomis20ft wideinthedimensionnotshown.
4 ft 7 ft 15 ft 2 ft ?
CeilingPocketExample
No,sprinklersarenotrequired:
3x4x20=240ft3
4 ft 7 ft 15 ft 2 ft
8 ft
11 ft
8 ft
11 ft
47
48
Nonuniformceilings
Uprightandpendentstandard sprayandextendedcoverage sprinklers Thedistancefromthesprinklerto theceilingisrequiredtobe measuredovertheentireareaof coverageforthatsprinkler
Nonuniformceilings
Whereaceilingchangeselevationand thedifferencebetweenthesprinkler deflectoratthelowelevationandthe ceilingatthehighelevationislessthan orequalto3ft
Treatthehigherelevationasapocket;or Sprinklerignoringthechangeinelevation Sprinklersinupperelevationmustmeet obstructionrulesifprotectingspaceunder lowerceilingelevation
49
50
Nonuniformceilings<36ft
Nonuniformceilings
Ifthechangeinelevationisgreater than3ft
Thehigherceilingelevationneeds tohaveitsownsprinklers;and The h place l where h the h elevation l i changesistreatedasawallforthe purposeofdeterminingsprinkler spacingandlocation
51
52
Nonuniformceilings>36ft
Slopedceilings
Measuredistancebetween sprinklersalongslope Highestsprinklermustbe within3ftverticallyatthe peak Specialrulesforvery steeplypitchedroof Specialrulesforconcealed spaces(attics)
53
54
Slopedceilings
Steeplypitchedroofs
Measure distance between sprinklers along slope Highest sprinkler 3 ft maximum from peak With steeply pitched roofs a sprinkler is permitted to be more then 3 ft from peak in order to maintain 2 ft clearance from structural members
55 National Fire Sprinkler Association 2013 56
SprinklersUnderPitchedSurfaces
Distancesbetween sprinklersaremeasured alongtheslope Fordeterminingthe amountofwaternecessary tomeetthedensity/area requirements(hydraulic calculations),theprojected areaonthefloorshallbe used.
SpecialConcealedSpace(Attic)Rules
Ifconstructioniswoodjoistorwoodtruss;and Ifmembersarespacedlessthan3ftoncenter; and Ifroofslopeexceeds4in12.Then:
Maximumcoverageareapersprinkleris120sqft 8x15with8ftdimensionmeasuredperpendicular toslope;or 10x12(with10ftdimensionmeasured perpendiculartoslope)ifpressureisatleast20psi Sprinklernearbottom,minimum 5fttothe bottomofthespace Sprinklerwithin12inchesofpeak
58
Sloped/ConcealedSpaceSprinklerSpacing
UnoccupiedAtticRules(8.6.2.2.1(a))
Choice 1 Choice 2
8 ft 10 ft
Elevation View
National Fire Sprinkler Association 2013
Elevation View
60
SidewallSprinklers
SidewallSprinklers
Section8.4.2coverswherethe sprinklerscanbeused
LightHazardoccupancieswithflat, smooth,horizontalceilings LightHazardoccupancieswithflat, smooth, h sloped l dceilings ili OrdinaryHazardoccupancieswithflat smoothceilingswherespecificallylisted forsuchuse Protectbeneathoverheaddoorsinany occupancy
Section8.7coversinstallationrules
National Fire Sprinkler Association 2013 61 National Fire Sprinkler Association 2013 62
DeterminationofAreaofCoveragefor EachSprinkler(8.7.2.1)
Alongthewall
Chooselargerof
Distancebetweensprinklers Twicedistancetowallorobstruction
StandardSidewallSprinklersTable8.7.2.2.1
LightHazard
Combustible Finish Between Sprinklers Room Width (singlerow) Maximum Area 14ft 12ft 120ft2 Noncombustible or Limited Combustible Finish 14ft 14ft 196ft2
ThisdimensionisS
Acrosstheroom
Distancetowalloppositesprinkler Midpointifsprinklersareon oppositewalls
ThisdimensionisL
AreaofCoverage=AS =SxL
National Fire Sprinkler Association 2013 63
SidewallSprinklerExample
StandardSidewallSprinklersTable8.7.2.2.1
OrdinaryHazard
Combustible Finish B t Between Sprinklers Room Width (singlerow) MaximumArea 10ft 10ft 80ft2 Noncombustible or Limited Combustible Finish 10ft 10ft 100ft2
65
Standard SidewallSprinkler
SpacingConsiderations
Sidewallsprinklersarenotallowedtobe installedbacktobackunlessprotected byacontinuouslintelorsoffit(8.7.3.1.4) Roomwidthcanbeincreasedto24ftin lighthazardand20ftinordinaryhazard withsidewallsprinklersontwoopposite walls(8.7.3.1.5) Sidewallsprinklersshallbepermittedto beinstalledonopposingoradjacent wallsaslongasnosprinkleriswithinthe maximumprotectionareaofanother (8.7.3.1.6)
National Fire Sprinkler Association 2013 67
StandardSidewallSprinklerLocations
Deflectors46fromceiling unlessotherwiselisted. HorizontalS/W612or12 18 Installedathighpointofslope, slope pointingdownwithdeflector paralleltoslope Wheresoffitsaremorethan8 wide,anadditionalsprinkleris requiredbelowthesoffit
National Fire Sprinkler Association 2013 68
TemperatureConsiderationsfor LocationofSprinklers
Ingeneral,useOrdinaryTemperature sprinklersaslongasceiling temperaturedoesnotexceed100F Usehighertemperaturesprinklersin thefollowing
Forambienttemperaturesover100F seeTable6.2.5.1 Forlocalheatsources,see8.3.2.5and Tables8.3.2.5(a) (c) SeeFigure8.3.2.5forHighTemperature ZoneandIntermediateTemperature Zonearoundunitheaters
National Fire Sprinkler Association 2013 69
ObstructionstoSprinklers
Sprinklersneedtobe locatedfarenoughaway fromobstructionstomake surethatanyfireinthe compartment p iscontrolled orsuppressed
Familiarizeyourselfwiththe obstructionruleslocatedin Chapter8ofNFPA13
70
Summary
1.Employtherulesfordetermining acceptablespacingforspraysprinklers. 2.Applythemaximumandminimum di t distances between b t sprinklers. i kl 3.Calculatetheallowablecoverageareas persprinkler. 4.Applythesmallroomrulecorrectly.