Professional Documents
Culture Documents
TANQUE DE ALMACENAMIENTO
PRESENTADO POR:
RUBEN DARIO PEREZ DAZA
PRESENTADO A:
ING CARLOS ERAZO
FACULTAD DE INGENERIA
PROGRAMA DE INGENIERIA CIVIL
NOVIEMBRE 2013
BOGOTA
Contenido
DISEO TANQUE DE ALMACENAMIENTO ........................................................................................... 3
DATOS INICIALES ............................................................................................................................. 3
DOTACIN NETA ............................................................................................................................. 3
DOTACIN BRUTA ........................................................................................................................... 3
Caudal Medio Diario Qmd ............................................................................................................... 4
Caudal Mximo Diario QMD y Caudal Mximo Horario QMH ........................................................ 4
CAPACIDAD DEL SISTEMA DE ALMACENAMIENTO ......................................................................... 4
DIMENSIONAMIENTO DEL TANQUE................................................................................................ 7
DIMENSIONES DEL TANQUE............................................................................................................ 7
CARACTERISTICAS DEL TANQUE ...................................................................................................... 7
CALCULO DE LOS LADOS DEL TANQUE DE ALMACENAMIENTO ..................................................... 7
CALCULO DE LA TUBERIA DE ENTRADA........................................................................................... 8
SALIDA DEL TANQUE DE ALMACENAMIENTO ................................................................................. 8
TUBERIA DE DESAGE ..................................................................................................................... 8
REBOSE ............................................................................................................................................ 8
ALTURA MAXIMA ............................................................................................................................ 8
MEMORIAS DE CLCULO ................................................................................................................. 9
DOTACIN NETA
La dotacin neta corresponde a la cantidad mnima de agua requerida para satisfacer las
necesidades bsicas de un habitante sin considerar las prdidas que ocurran en el sistema de
acueducto.
NIVEL DE COMPLEJIDAD
Bajo
Medio
Medio Alto
Alto
Tabla 1 Dotacin neta segn el Nivel de Complejidad del Sistema - Ras 2000
De acuerdo a la anterior tabla y el nivel de Complejidad de Villa Pinzn (BAJO), la Dotacin Neta
mxima es de 150 L*Hab/da
DOTACIN BRUTA
Se puede calcular la dotacin bruta segn el numeral B.2.6 del Ras 2000 y la tabla a continuacin:
COEFICIENTE K1
COEFICIENTE K2
Red Distribucin menor
Bajo
Medio
Medio Alto
Alto
1.30
1.30
1.20
1.20
1.60
1.60
1.50
1.50
)
(
TABLA DE CONSUMO
Consumo
QMD
QMH
Lps
34.84
55.74
3.6
m3/H
125.424
200.664
24
m3/Da
3010.176
4815.936
Hora
Aporte lps
Aporte m3/h
Aporte
Acum
Curva
Consumo
Consumo M3/hora
Consumo
acumulado m3
Dif m3
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
34.84
34.84
34.84
34.84
34.84
34.84
34.84
34.84
34.84
34.84
34.84
34.84
34.84
34.84
34.84
34.84
125.424
125.424
125.424
125.424
125.424
125.424
125.424
125.424
125.424
125.424
125.424
125.424
125.424
125.424
125.424
125.424
125.424
250.848
376.272
501.696
627.12
752.544
877.968
1003.392
1128.816
1254.24
1379.664
1505.088
1630.512
1755.936
1881.36
2006.784
0.50%
1.00%
1.50%
2.50%
4.50%
5.50%
7.00%
7.50%
6.50%
6.00%
5.50%
4.50%
4.00%
4.00%
4.50%
5.00%
24.080
48.159
72.239
120.398
216.717
264.876
337.116
361.195
313.036
288.956
264.876
216.717
192.637
192.637
216.717
240.797
24.080
72.239
144.478
264.876
481.594
746.470
1083.586
1444.781
1757.817
2046.773
2311.649
2528.366
2721.004
2913.641
3130.358
3371.155
101.344
178.609
231.794
236.820
145.526
6.074
205.618
441.389
629.001
792.533
931.985
1023.278
1090.492
1157.705
1248.998
1364.371
Numero Mx.
Numero Mn.
Volumen tanque
236.820
1965.315
2202.1
17
18
19
20
21
22
23
24
34.84
34.84
34.84
34.84
34.84
34.84
34.84
34.84
125.424
125.424
125.424
125.424
125.424
125.424
125.424
125.424
3010.176
2132.208
2257.632
2383.056
2508.48
2633.904
2759.328
2884.752
3010.176
6.00%
6.50%
5.50%
4.50%
3.00%
2.00%
1.50%
1.00%
100.00%
288.956
313.036
264.876
216.717
144.478
96.319
72.239
48.159
4816
3660.111
3973.147
4238.024
4454.741
4599.219
4695.538
4767.777
4815.936
1527.903
1715.515
1854.968
1946.261
1965.315
1936.210
1883.025
1805.760
En dicha tabla se aprecia que, para calcular el volumen, se suman los valores absolutos del mximo excedente y mximo dficit. Esto se explica
debido a que de las 0 a las 6 horas ingresa al tanque ms agua de la que se consume, por lo que se obtiene un porcentaje de acumulacin
mximo (mximo excedente); despus de las 6 horas comienza a demandarse ms agua de la que entra al tanque, por lo que empieza a hacerse
uso de la que se tena acumulada
A partir de las 7 existe un dficit, es decir se consume ms de lo que llega al tanque y no se cuenta con un volumen de almacenamiento para
cubrir lo faltante, para las 21 horas el tanque est en el momento ms crtico (mximo faltante), por lo cual se ve la necesidad de contar con un
volumen de agua almacenado equivalente al mximo dficit (1965.315 m3) y al mximo excedente (236.820). Garantizando cubrir todas las
demandas.
236.820
1965.31
2202.1
Nivel de complejidad
Numero de tanques
Caudal Mximo Diario
Caudal Mximo Horario
Volumen del tanque
Bajo
1
34.84 lps
55.74 lps
2202.1 m3
TUBERIA DE DESAGE
De acuerdo a la norma, en el literal B.9.4.10 se establecer un tiempo mximo de
vaceado no mayor 8 horas, en nuestro diseo se opta como lmite este tiempo que
equivale a 480 minutos y esto es debido a que el dimetro de la tubera de vaceado
no deber ser mayor al dimetro de la tubera de entrada del tanque que como se
indic anteriormente corresponde a 6.
REBOSE
Todo tanque de compensacin debe tener un sistema de rebose, con el fin de evacuar
los posibles caudales de exceso. El rebosadero debe estar dimensionado para evacuar
el caudal mximo de entrada, en nuestro proyecto para evitar presiones en la tapa del
tanque se deja un borde libre de 0.30 m.
ALTURA MAXIMA
De acuerdo a la topografa del terreno y la localizacin del tanque, se puede observar
que la lnea piezometrica del nivel del agua del tanque de almacenamiento est en la
cota 2734.74, que esta aproximadamente 10 mts sobre la poblacin cumpliendo con la
presin mnima de nuestro diseo
MEMORIAS DE CLCULO
PARAMETROS DE DISEO
Nivel de complejidad
(aos)
Numero de tanques
Caudal Mximo Diario
Caudal Mximo Horario
20
1
34.84
55.74
Bajo
und
lps
lps
3.2
0.3
3.5
m
m
m
Cuadrado
26.23293731 mt
27
mt
m
m
m2
m
m3
2732.09
2731.24
2731.24
2734.74
m
m
m
m
480
0.0765
0.0158
0.1419
5.6
6
min
m3/seg
m2
m2
in
in