PROJECT NO.:44NY7300 PROJECT NAME: 65 MTPD CROSS PLY TYRE PLANT CLIENT: CEAT BANGLADESH LIMITED SPECIFICATION: N.D.T.

REQUIREMENTS FOR PIPING REFERENCE DOC.: IND-WI-L-212, REV.2

Vendor shall follow NDT test requirement (Default + other applicable Test) for Piping as mentioned below:
1) DEFAULT TEST GHJDYE PENETRANT TEST - of all root passes. DYE PENETRANT TEST - of all complete fillet and intersection welds. DYE PENETRANT TEST - of all complete girth and longitudinal welds.

2) APPLICABLE TEST
MATERIAL (Wall Thickness 19 mm (") max.) Carbon Steel 150# -29 C to 186 C -20 F TO 366 F below -29 C (-20 F) over 186 C (366 F) -29 C to 186 C -20 F to 366 F below -29 C (-20 F) over 186 C (366 F) ANSI B31.3 Material P.No. 1 1 1 1 PRESS RATING CLASS ANSI B16.5 150 lbs Shop Test R R N R M R M Q

Classes (1) Field Test Classes (1) R A B R N A B R M A B R M Q A B

Carbon Steel 300#

TEST CLASSES APRELIM AIR or INERT GAS TEST - at 1.75 bar g for major leaks. Test may be waived if testing engineer is satisfied that a major leak is not likely to occur. HYDROSTATIC TEST (As per ASME B31.3) 1. At 1.5 times design pressure (from line list). 2. For design temperatures above the test temperature, the minimum test pressure shall be as calculated by following equation, except that the value of ST/S shall not exceed 6.5 PT = 1.5 x P x ST S P = Internal design gage pressure (Minimum hydrostatic gage pressure)

B-

ST S

PROJECT NO.:44NY7300 PROJECT NAME: 65 MTPD CROSS PLY TYRE PLANT CLIENT: CEAT BANGLADESH LIMITED SPECIFICATION: N.D.T. REQUIREMENTS FOR PIPING REFERENCE DOC.: IND-WI-L-212, REV.2 = Allowable stress at test pressure = Allowable stress at design temperature

If the test pressure as defined above would produce a stress in excess of the yield strength at test temperature or a pressure more than 1.5 times the component rating at test temperature, the test pressure may be reduced accordingly. For Calculation sheet refer Attachment 7.3 MNCOMPLETE RADIOGRAPHY - of one finished buttweld in 10 made by each welder. RADIOGRAPHY - of all buttwelds by each welder for a third of pipe circumference, or 300mm, whichever is less. MAGNETIC PARTICLE TEST - of all complete welds. VISUAL INSPECTION

QRNotes : 1)

All pressures quoted are gage pressures.