BATTERY CALCULATION

Date:

Project:

Category

Primary, Fire Alarm Current

Secondary, Non-Fire Alarm Current

(Amps)
Qty

X (Current Draw) =

(Amps)
Total

Qty

X (Current Draw) =

Total

HEAD END EQUIPMENT


NFS-320

0.250000

0.2500

0.250000

0.2500

NFS2-640 (CPU2-640)

0.250000

0.0000

0.250000

0.0000

NFS2-3030 (CPU2-3030D)

0.220000

0.0000

0.220000

0.0000

AMPS-24AE (Power Supply)

0.104000

0.0000

0.064000

0.0000

CHS-M3/2 (Inter Connecting Assembly)

0.002000

0.0000

0.002000

0.0000

LCM-320 (Loop Interface Board)

0.130000

0.0000

0.090000

0.0000

LEM-320 (Loop Interface Board)

0.100000

0.0000

0.060000

0.0000

NCM-F (Media Interface Board)

0.035000

0.0350

0.035000

0.0350

LDM SERIES (Lamp Driver)

0.074000

0.0740

0.042000

0.0420

0.062000

0.0000

0.062000

0.0000

FSP-851 (Photoelectronic Detector)

0.000200

0.0000

0.000200

0.0000

FST-851R (Heat Detector)

0.000200

0.0000

0.000200

0.0000

882 (Conventional Smoke Detector)

0.002000

0.0000

0.000005

0.0000

5601 (Conventional Heat Detector)

0.000000

0.0000

0.000000

0.0000

SCS SERIES (Smoke Control System)


FIELD END DEVICES

FMM-101 (Monitor Module)

0.000430

0.0069

16

0.000300

0.0048

FZM-1 (Zone Module)

16

0.000430

0.0000

0.000300

0.0000

FCM-1 (Control Module)

0.000300

0.0000

0.000300

0.0000

FSD-751PL (Duct Detector)

0.006150

0.0000

0.006150

0.0000

ISO-X (Isolator Module)

0.000450

0.0000

0.000450

0.0000

SOUNDER C/W STROBELIGHT

0.090000

0.0000

0.000000

0.0000

Total

0.3659

AMPERE

0.3318

HOURS

SECONDARY NON-FIRE ALARM LOAD


0.3318

72

23.8896

0.3659

0.36588

ACTUAL AMPERE(AH) CALCULATED

24.25548

*1.2 FACTOR (20% SPARE)

29.10658

TOTAL AMPERE HOURS REQUIRED

29

PRIMARY FIRE ALARM LOAD


(IF < 6A)