PROFIBUS is the bus system for communication in small cell networks and with field device. PROFIBUS is based on the European standard EN 50170 and is implement ed worldwide in the field envi ronment. By meeting the requirements of EN 50170, PROFIBUS ensures that it is open to the linking of components from other manufacturers which comply with the standard. Siemens supports the con nection of further field devices to PROFIBUS by marketing ASICs and submodules as well as providing technical advice for manufacturers of PROFIBUS components. Three protocol profiles are available for the various re quirements and applications in the field and cell areas: PROFIBUSDP (distributed I/Os) S PROFIBUSFMS (field bus message specification) S PROFIBUSP A (process automation)
S
Distributed I/Os
Application
PROFIBUSDP PROFIBUSDP complies with EN 50170. PROFIBUSDP is character ized by fast cyclic commu nication with small data quan tities. Data transfer rates up to 12 Mbit/s are possible. PROFIBUSDP allows distrib uted ET 200 I/O stations, hu manmachineinterfaces and field devices to communicate with the programmable con trollers. In addition with SIMATIC S7/M7, it is possible to program, startup, test and diagnose the complete au tomation system via the field bus.
PROFIBUSFMS PROFIBUSFMS complies with the PROFIBUS standard EN 50170 and is designed for communication with more complex field devices with an FMS interface and for smaller cell networks (10 to 15 stations). Data transfer rates up to 1.5 Mbit/s are possible. PROFIBUSFMS and DP All protocols are based on the same bus components and can be operated together on one line (combination master). PROFIBUSP A A is the protocol PROFIBUSP profile for process automa tion, especially for the intrinsi callysafe area. PROFIBUS provides solutions ranging from the field area to the cell area.
S7400
S5115U to 155U
PROFIBUS-FMS
S5115U to 155U PG/PC S7400 SIMATIC HMI
S7300
PROFIBUS-DP
Field devices
Fig. 6/13 Example configuration of PROFIBUS field bus for the PROFIBUSFM and DP protocol profiles
Siemens ST 50 1997
6/45
Distributed I/Os
Design
DP/ASInterface link Text displays and operator panels for operating and monitoring at the machine S MOBY identification systems S Field devices, also from oth er manufacturers, e.g. drives, valves
S S
Passive stations (slaves) S ET 200M, ET 200B, ET 200C distributed I/Os (max. 12 Mbit/s) and ET 200U, ET 200L (max. 1.5 Mbit/s)
S
Up to a 127 stations can be connected to PROFIBUSDP. Actuator sensor interface ASInterface The actuator sensor interface (ASInterface) is a field bus for connection of binary ac tuators and sensors. The ASInterface can be con nected to PROFIBUS directly to SIMATIC S5/S7 via the CP 3422 (available soon), CP 2433 or CP 2430 master modules or directly to a PC via CP 2413 and S via a DP/ASInterface link
S
S5115U, S5135U, S5155U programmable controllers, each with IM 308C (max. 12 Mbit/s) S595U programmable con troller with PROFIBUSDP slave interface (max. 1.5 Mbit/s) S7300 programmable con troller with CP 3425 or S7400 programmable con troller with CP 4435 (max. 12 Mbit/s).
The data transfer rate is se lectable in stages from 9.6 to 1.5 Mbit/s. For extremely timecritical distributed I/O applications, data transfer rates of 3, 6 and 12 Mbit/s are additionally possible. The maximum segment length depends on the data transfer rate. Optical network The fiber optic version of PROFIBUS is immune to elec tromagnetic interferences. It is suitable for long distances and offers a choice of plastic or glass fiber optic cables. The stations are connected to the optical network via an op tical bus terminal or optical link module (OLM). OLMs enable the creation of an optical network with a linear, ring or star structure.
The maximum distance be tween two OLMs is 15 km (9.3 m). The data transfer rate is selectable in stages from 9.6 to 1.5 Mbit/s. The maximum segment length for the optical version of PROFIBUS is independent of the data transfer rate. Mixed networks Mixed structures based on electrical and optical net works are possible. The transition between the two media is provided by the OLM. For communication between stations on the bus, there is no difference between the twowire and fiberoptic sys tems. Up to 127 stations can be connected to a PROFIBUS network.
6/46
Siemens ST 50 1997
Distributed I/Os
Principle of operation
Configuration
Helpful and simple tools are available for the user for con figuration, parameterization, startup and diagnosis of the PROFIBUSDP field bus sys tem. The parameterization software COM ET 200 Windows is used for the master interfaces of the SIMATIC S5.
Interface modules/software
Automationsystem S5-95U/DP master S5-115U/H S5-135U S5-155U/H TI505 PROFIBUS-DP interface module built-in interface (see Section 2) Interface module IM 308C (see Section 3) Interface module IM 308C (see Section 4) Interface module IM 308C (see Section 4) SIMATIC 505FIM (see Catalog IK 10) Configuration software COM ET 200 Windows (see Section 7) COM ET 200 Windows (see Section 7) COM ET 200 Windows (see Section 7) COM ET 200 Windows (see Section 7) TISOFT programming software (see Section 7)
Ordering data
PROFIBUS bus components IM 308-C interface module for connection of the S5115U/H, S5135U und S5155U/H pro grammable controllers to PROFIBUSDP Data transfer rate up to 12 Mbit/s SIMATIC 505-FIM interface module for connection of the SIMATIC TI505 programmable controllers to PROFIBUSDP; Data transfer rate up to 1.5 Mbit/s SINEC CP 5431 FMD/DP communications processor for connection of the S5115U/H, S5135U and S5155U/H pro grammable controllers to PROFIBUSDP and FMS; Data transfer rate up to 1.5 Mbit/s
Order No. see Section 10 see Sections 3, 4 SINEC CP 5412 (A2) communications processor for connection to the PG 730, PG 740, PG 750, PG 760 and PG 770 programming devices to PROFIBUSDP; Data transfer rates up to 1.5 Mbit/s SINEC CP 5411 communications processor for connection to the PG 730, PG 740, PG 750, PG 760 and PG 770 programming devices to PROFIBUSDP; Data transfer rates up to 12 Mbit/s SINEC CP 5511 communications processor for connection to the PG 720 programming devices to PROFIBUSDP (in acc. with PCMCIA standard); Data transfer rates up to 12 Mbit/s
see Catalog IK 10
see Section 10
see Section 10
see Section 8
Siemens ST 50 1997
6/47