You are on page 1of 1

Dhofar Power Company SAOG

Appendix 7A2
Span Criteria
1. Suspension Towers (DS)
oto 2 (with reduced span)
]111
Particulars Normal condition Broken wire condition
Basic Span (m) 335
Maxilnum weight span (m) 670 505
Minimum weight span (m) 100 100
Maximum wind span (m) 410 310
2. Angle Tower D2
oto 20
Particulars Nonnal condition Broken wire condition
Basic Span (m) 335
Maximum weight span (m) 1340 1010
Minimum weight span (m) - 670 - 335
Maximum wind span (m) 410 310
3. Angle Tower D6
20 to 60
Particulars Normal condition Broken wire condition
Basic Span (m) 335
Maximum weight span (m) 1010 1010
Minimum weight span (m) - 335 - 335
Maximum wind span (m) 410 310
4. Angle Tower/Terminal Tower D9/DT
60 to 90 or Terminal Tower
Particulars Normal condition Broken wire condition
Basic Span (m) 335
Maximum weight span (m) 1010 1010
Minimum weight span (m) - 335 - 335
Maximum wind span (m) 410 310
(Span Criteria continued next page)
Construction of 132kV Overhead line between Awqad GSS &SFZ GSS
Rev. No. :A
and Associated Works (Package-1)
Volume 2 Overhead Line Specification Date : December 2010
Section 7 Supports Page :Page 27 of 38