COLUMN DESIGN

Design Data: fy = f'c =

275 MPa 21 MPa

rg = rmin = Max Column Force

0.002 0.00507

m b1 f

= = =

15.4622 0.8500 0.65 - 0.90

Column:

Typical

Clear Height, ht = Longitudinal Bars, db = Lateral Ties, dbt =

2.70 m 16 mm 10 mm

No. of bars:

8 pcs

Col. Dim. : 300 mm B = 300 mm H =

from the attached column design: r = 1.79 % Use: Design of Ties: A. size = 10 mm B. Spacing: Smax: 16 db 48dbt least column dim. Smax = 300 x

Total steel area = 300 with

1608.5 mm2 8 pcs - 16 mm dia. Bars

Cover = 40 mm 256 mm 480 mm 300 mm 150 mm lo = Seismic Requirements: Max. Member Dim., lo 300 mm ht/6 450 mm 450 mm 450 mm hx = 210 mm s = 70 mm hc = 210 mm Ag = 0.09 m
2 2

Ach = 0.048 m

Spacing for S1: (1/4)*bmin 6db So S1 = no. of ties =

75 mm 96 mm 147 mm 70 mm 6 pcs

No. of Tie/s 1@ 6@ Rest @

Spacing 50 mm 70 mm 150 mm

C. Cross-ties Req'd total area of ties, Ash = 0.3 (s hc fc' / fy) [Ag/Ach) - 1] and 0.09 (s hc fc' / fy) 2 289.4 mm Req'd total area of ties, Ash = Req'd no. of cross tie legs = 0 additional leg(s)