You are on page 1of 4

CONCRETE VOLUME

Allowable Soil
Ground
Type of
Bearing
Water Table
Foundation
below N.S.L Pressure (t/m2)
A-1'
N.E.
20
A-2'
N.E.
10

A (mm)
1850
2310

B (mm)
600
600

C (mm)
800
800

H (mm)
3680
3680

t (mm)
80
80

f (mm)
350
350

F (mm)
30
25

Volume
(m3)
2.712
3.449

BAR BENDING SCHEDULE


PIECE No. 1
Type of
BAR DESG.
Foundation
No.

Qty.

R (mm)

L (mm)

A-1'

12

3833

4283

A-2'

12

3833

4283

Qty.

R (mm)

L (mm)

PIECE No. 2
Type of
BAR DESG.
Foundation
No.
A-1'

13

437

2050

A-2'

13

437

2050

SETTING OUT DIMENSIONS FOR FOUNDATION TYPE A-1, A-2'


TOWER MAKE UP
BB

BE (m)

LE (m)

(mm)

(mm)

(mm)

(mm)

BB

0.0

2.0

4750

6718

4322

6113

BB

0.0

4.0

5017

7095

4589

6490

BB

0.0

6.0

5284

7472

4856

6867

BB

0.0

8.0

5550

7849

5122

7244

BB

6.0

2.0

5550

7849

5122

7244

BB

6.0

4.0

5817

8226

5389

7621

BB

6.0

6.0

6083

8603

5655

7998

BB

6.0

8.0

6350

8980

5922

8376