ARAS 3 REINFORCED CONCRETE DESIGN

STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

DESIGN CRITERIA
Materials Fc = 20.7 MPa Fy = 275 MPa (for bars with diameter smaller than 16mm) = 414 MPa (for bars with diameter greater or equal to 16mm)

Loading Analysis

Dead Load

Live Load

Dead Load Long Span G.I Sheet..100 Pa Ceiling (Suspended Metal Lath and Gypsum Plaster)..480 Pa

Electromechanical50 Pa Bracing System..70 Pa Insulation (Polystyrene Foam, 50mm).20 Pa Weight of Purlins (LC 90x 45x 15x 2.0).29.82 N/m

P a g e | 22

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Weight of Truss (WT) WT = 35.83 + 11.78 L = 35.83 + 11.78 (10) WT = 153.63 KN/m

C1 = 3m C2 = 5m C3 = 4.5m C4 = 2.5m

a=1m b = 1.08m

P 1 = WT x a x c = 153.63 x 1 x 5 = 768.15 P2 = (100 + 70 + 20) x a x c = (100 + 70 + 20) x 1 x 5 = 950 P3 = = = 35.43 PT = P1 + P2 + P3 = 768.15 + 950 + 35.43 PT = 1753. 58 N = 876.8 N R1 = R2 =23077.91 N or 23 KN R1 = R2 = xb x1.08 F = (480 + 50) x b x c = 530 x 1.08 x 5 F = 2862 N = 1431 N

P a g e | 23

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Live Load T.A (Tributary Area) = 1.08 x 5 =5.4 < 20 Slope = 40% Therefore, live load = 750 Pa P = 750 x 5.4 P = 4050 N = 2025 N

P a g e | 24

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Loads
Dead Load Floor Finishing: Ceramic Tiles...0.77 KPa Laminated Ipe or Narra Wood Blocks (76mm) on 13mm mortar.0.77 KPa Ceiling (Suspended Metal Lath and Gypsum Plaster)..0.48 KPa Electromechanical..0.50 KPa Interior Partitions.1.0 KPa Partitions 150mm Hollow Concrete Masonry w/ full hollow grout spacing plastered on both sides (19.6 KN/m3).3.30 KPa 100mm Hollow Concrete Masonry w/ full hollow grout spacing plastered on both sides (19.6 KN/m3).3.17 KPa Railings0.50 KPa hmin = hmin = * * + +

hmin =0.1239 say 0.130 or 130 mm Weight of Slab W = 24 x 0.130 = 3.12 KPa

Slab (130 mm)3.12 KPa

Live Load Basic Floor Area1.9 KPa

P a g e | 25

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Slab S-1 S-2 S-3 S-4

L side 4 4 5 4

S side 3 4 4 2

m 0.75 1 0.8 0.5

Slab Type Two Way Slab Two Way Slab Two Way Slab One Way Slab

Slab (S-1) Total Dead Load = 5.05 KPa; Total Live Load = 1.9 KPa L side W= *
2

S side + W= W= W = 1.68 KN/m

L side Live load= 1.9 x 4= 7.6 KN/m WLL = 7.6 KN/m S side Live load= 1.9 x 3= 5.7 KN/m WLL = 5.7 KN/m

W=

32 4

= 2.05 KN/m 3.12 KPa (selfweight of slab) x 4 = 12.48KN/m WDL=14.53 KN/m

3.12 KPa (self- weight of slab) x3 = 9.36 KN/m WDL= 11.04 KN/m

Slab (S-2) Total Dead Load = 5.05 KPa; Total Live Load = 1.9 KPa

W=
W=

Live load= 1.9 x 4= 7.6 KN/m


WLL = 7.6 KN/m

W = 1.68 KN/m 3.12 KPa (self- weight of slab) x3 = 9.36 KN/m WDL= 11.04 KN/m P a g e | 26

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Slab (S-3) Total Dead Load = 6.55 KPa; Total Live Load = 1.9 KPa L side W= * W=
2

S side + W= W= W = 1.68 KN/m

L side Live load= 1.9 x 5= 9.5 KN/m

42 5

WLL = 9.5 KN/m


S side Live load= 1.9 x 4= 7.6 KN/m WLL = 7.6 KN/m

= 2.57 KN/m 3.12 KPa (selfweight of slab) x 5 = 15.6KN/m WDL=18.17 KN/m

3.12 KPa (self- weight of slab) x4 = 12.48KN/m WDL= 12.48 KN/m

Slab (S-4) Total Dead Load = 4.92 KPa; Total Live Load = 1.9 KPa L side W= W=

L side Live load= 1.9 x 4= 7.6 KN/m WLL = 7.6 KN/m

= 2.46 KN/m
3.12 KPa (selfweight of slab) x 4 = 12.48KN/m WDL=14.94 KN/m

P a g e | 27

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Dead load carried by each floor beam

P a g e | 28

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Dead load carried by each roof beam

P a g e | 29

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Live load carried by each roof beam

P a g e | 30

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Frame Analysis (Dead Load)

P a g e | 31

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

P a g e | 32

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

P a g e | 33

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

P a g e | 34

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

P a g e | 35

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

P a g e | 36

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Reactions (Dead Load)

P a g e | 37

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

P a g e | 38

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

P a g e | 39

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

P a g e | 40

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

P a g e | 41

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

P a g e | 42

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Design of Roof Beam (A 1-2)


fc = 20.7 MPa fy = 414 MPa WDL = 7.21 KN/m WLL = 6.48 KN/m WU = 1.4 DL + 1.7 LL = 1.4 (7.21) + 1.7 (6.48) WU = 21.11 KN/m

b = =

max = 0.75 b max =0.016

b =0.021 RU = MU = =

2

= RU = 5.86 MPa

MU =95 KNm =

= =0.0007

1 1

P a g e | 43

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

min = =

max > < min


Therefore, USE = min

min = 0.0034

w=

= w = 0.32

MUMAX = fc wb

(1- 0.59w) ) (1- 0.59(0.32))

= 0.9(20.7) (0.32) (200) (3 MUMAX = 87 KNm < Mu = 95 KNm

Therefore, compression steel is needed, design as double reinforced. ASMAX = MAXbd = 0.016 (200) (300) AS = 960 MU1 = MUMAX MU1 = 87 KNm MU2 = MU - MUMAX = 95 87 MU2 = 8 KNm a = 0.85c; d= 40mm 0.85fc x a x b = AS Fy 0.85(20.7) x a x 200 = 960 (414)

a =112.94
c = = =132.87mm fs = 600x

= 600x

= 419

fs = 419 >414, therefore, compression steel yields.

P a g e | 44

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

MU2 = AS fy (d- d) 8x1 = 0.9 AS (414) (300-40)

AS2 = 82.58 AS1 = 960 + 82.58 = 1042.58


N20=? = =

= 314.6 = 3.32 say 4 pcs. 20mm bar

Therefore, adopt 200mm x 300mm roof beam with 4- 20mm bar; 212mm bar.

P a g e | 45

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

VU = 62.33 21.11(0.30) VU = 56 KN

VC = = 2 7 2 3

VC = 45.5 KN < 56 KN Therefore, stirrups are needed. Vn = = Vn =65.88 KN V<


VS = Vn - VC = 65.88 45.5 VS = 20.38 KN

2 7 2

Spacing
AV = S= =

VS = 20.38 KN < 181.99 ok! = 157.1


a) 2 7 2 3

VS < 91 KN Therefore, S = =

= 150 mm

S = 957.4 mm

P a g e | 46

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Design of Floor Beam (B 3-4)


fc = 20.7 MPa fy = 414 MPa WDL = 39.22 KN/m WLL = 19 KN/m WU = 1.4 DL + 1.7 LL = 1.4 (39.22) + 1.7 (19) WU = 87.21 KN/m

b = =

max = 0.75 b max =0.016

b =0.021 RU = MU = =

2

= RU = 7.57 MPa

MU =122.56 KNm =

= =0.0009

1 1

P a g e | 47

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

min = =

max > < min


Therefore, USE = min

min = 0.0034 w=

= w = 0.32
Mumax = fc wb (1- 0.59w) ) (1- 0.59(0.32))

= 0.9(20.7) (0.32) (200) (3

Mumax = 87 KNm > Mu = 122.56 KNm Therefore, design as double reinforced. ASMAX = MAXbd = 0.016 (200) (300) AS = 960 MU1 = MUMAX MU1 = 87 KNm MU2 = MU - MUMAX = 122.56 87 MU2 = 35.56 KNm a = 0.85c; d= 40mm 0.85fc x a x b = AS Fy 0.85(20.7) x a x 200 = 960 (414) a =112.94 c = = =132.87mm fs = 600x

= 600x

= 419

fs = 419 >414, therefore, compression steel yields.

P a g e | 48

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

MU2 = AS fy (d- d) 35.56 x 1 = 0.9 AS (414) (300-40)

AS2 = 367.07 AS1 = 960 + 367.07 = 1327.07

N25 =? = =
2

= 490.87 = 2.70 say 3 pcs. 25mm bar

Therefore, adopt 200mm x 300mm floor beam with 3- 25mm bar; 225mm bar.

P a g e | 49

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

VU = 218.05 87.21(0.30) VU = 191.89 KN

VC = = 2 7 2 3

VC = 45.5 KN < 191.89 KN Therefore, stirrups are needed. Vn = = Vn =225.75 KN V>


VS = Vn - VC = 225.75 45.5 VS = 180.25 KN

2 7 2

VS = 180.25 KN < 181.99 ok!

Spacing
AV = S= =

a)

2 7 2 3

= 157.1

VS > 91 KN Therefore, S = =

= 75 mm

S = 108.25 mm

P a g e | 50

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Design of One Way Slab (S-4)

fc = 20.7 MPa fy = 275 MPa WDL = 14.94 KN/m WLL = 7.96 KN/m WU = 1.4 DL + 1.7 LL = 1.4 (14.94) + 1.7 (7.96) WU = 33.84 KN/m

d = 130 20 -

= 104mm

MU =

RU = =

MU =67.67 KNm b = =

RU = 6.95 MPa

max = 0.75 b max =0.027 b =0.037

= =0.0019

1 1

P a g e | 51

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

min = =

max > <min


Therefore, USE = min

min = 0.005
AS = bd = (0.005) (1000) (104) AS = 520 a) S= S = 217.5 mm say 215 mm b) 3 x h 3 X 130 = 390 mm c) 450 mm = per meter

Therefore, spacing equal to 215mm governed.

P a g e | 52

ARAS 3 REINFORCED CONCRETE DESIGN

Design of Axial 2 Floor Column (B-2)

STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING nd

fc = 20.7 MPa fy = 275 MPa PDL = 171.8 KN PLL = 19 KN PU = 1.4 DL + 1.7 LL = 1.4 (171.8) + 1.7 (19) PU = 282.62 KN PU = 0.80(0.85 fc (AG- AS) + (fy AS) AG = 40000 ; AST = 0.04 AG To check: PU = 0.80(0.85 fc (AG- AS) + (fy AS) = (0.70) (0.80) (0.85) (20.7) (40000- 1600) + (414 (1600)) PU = 1040.76 KN > 282.62 KN ok!

Therefore, AST = 0.04 (40000) AST = 1600 N25 =? = =

= 490.87 = 3.25 say 4 pcs. 25mm bar

Vertical spacing of ties: a) 16 x 25mm = 400mm b) 48 x 10mm = 480mm c) Least dimension of column = 200mm Therefore, vertical spacing of ties is 200mm.

P a g e | 53

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Design of Axial Ground Floor Column (B-2)

fc = 20.7 MPa fy = 414 MPa PDL = 405.57 KN PLL = 19 KN PU = 1.4 DL + 1.7 LL = 1.4 (405.57) + 1.7 (19) PU = 600.1 KN PU = 0.80(0.85 fc (AG- AS) + (fy AS) AG = 40000 ; AST = 0.04 AG To check: PU = 0.80(0.85 fc (AG- AS) + (fy AS) = (0.70) (0.80) (0.85) (20.7) (400001600) + (414 (1600)) PU = 1040.76 KN > 600.1 KN ok!

Therefore, AST = 0.04 (40000) AST = 1600 N25 =? = =

= 490.87 = 3.25 say 4 pcs. 25mm bar

Vertical spacing of ties: d) 16 x 25mm = 400mm e) 48 x 10mm = 480mm f) Least dimension of column = 200mm Therefore, vertical spacing of ties is 200mm.

P a g e | 54

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Design of Square Footing (B- 2)


fc = 20.7 MPa fy = 414 MPa PDL = 405.57 KN PLL = 19 KN YSOIL = 15.75 YCONC = 24

d = 300 75 = 225mm qEFF = qa - YU = 240 24 qEFF = 223.35 3 15 75 6

Area = =

Depth qU =
2

= 1.38 say 1.00m x 1.00m

qU =266.71 KPa

P a g e | 55

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Wide Beam Shear


1500

VU = qu ASHADED = 266.71 (1.5 x 0.45) VU = 180.03 KN VC = =


1500

bd 2 7 (1500) (225)

VC = 226 KN VU = 180.03 < 226 KN Therefore, safe!

Two Way Shear (Punching Shear)


1500

VU = qu ASHADED = 266.71 (15 VU = 504.08 KN VC = 4 4


1500

25 = 2 7 (2500) (225)

VC = 853.07 KN VU = 504.08 < 853.07 KN Therefore, safe!

P a g e | 56

ARAS 3 REINFORCED CONCRETE DESIGN


STRUCTURAL ANALYSIS AND DESIGN OF TWO STOREY RESIDENTIAL BUILDING

Steel Reinforcement
1500

MU = qU (0.65) (1.5)(

= 266.71 (0.65) (1.5) (0.325) MU = 84.51 KNm MU = RU b RU = fc w (1-0.59w)


1500

MU = fc w (1-0.59w) b 27.21 = 0.9 (20.7) w (1-0.59w) (1) (0.2252) w = 0.05 w=

;=w

= 0.05

= 0.0025

min = =

N16=? = =

= 201.06 = 6.36

min = 0.00338 < min


Therefore, USE = min

Use 8 pcs. 16mm bar

AS = bd = (0.00338) (1500) (225) AS = 1282.5 mm2

P a g e | 57