Appendix A
10A Rating
230 VAC Inductive load according to IEC 947--5--1 AC15 from 0A to 3A 24 VDC Inductive load according to IEC 947--5--1 DC13 from 0A to 2A Resistive 230 VAC load Resistive 24 VDC load
10,000
1,000
100
Figure A-1
Technical Specifications
All S7-200 CPUs and expansion modules conform to the technical specifications listed in Table A-1. Notice When a mechanical contact turns on output power to the S7-200 CPU, or any digital expansion module, it sends a 1 signal to the digital outputs for approximately 50 microseconds. You must plan for this, especially if you are using devices which respond to short duration pulses.
Table A-1 Technical Specifications
Environmental Conditions Transport and Storage EN 60068--2--2, Test Bb, Dry heat and EN 60068--2--1, Test Ab, Cold EN 60068--2--30, Test Db, Damp heat EN 60068--2--14, Test Na, Temperature Shock EN 60068--2--32, Free fall --40 C to +70 C 25 C to 55 C, 95% humidity --40 C to +70 C dwell time 3 hours, 2 cycles 0.3 m, 5 times, product packaging Environmental Conditions Operating Ambient Temperature Range (Inlet Air 25 mm below unit) Atmospheric pressure Concentration of contaminants EN 60068--2--14, Test Nb, Temperature change EN 60068--2--27 Mechanical shock EN 60068--2--6 Sinusoidal vibration 0 C to 55 C horizontal mounting, 0 C to 45 C vertical mounting 95% non-condensing humidity 1080 to 795 hPa (Corresponding to an altitude of --1000 to 2000 m) S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% non-condensing 5 C to 55 C, 3 C/minute 15 G, 11 ms pulse, 6 shocks in each of 3 axis Panel mount: DIN rail mount: 0.30 mm from 10 to 57 Hz; 2 G from 57 to 150 Hz 0.15 mm from 10 to 57 Hz; 1 G from 57 to 150 Hz 10 sweeps each axis, 1 octave/minute
Protects against finger contact with high voltage as tested by standard probes. External protection is required for dust, dirt, water, and foreign objects of < 12.5 mm in diameter.
393
Table A-1
EN 61000--4--2 Electrostatic discharge EN 61000--4--3 Radiated electromagnetic field EN 61000--4--4 Fast transient bursts
EN 61000--4--6 Conducted disturbances EN 61000--4--11 Voltage dips, short interruptions and voltage variations VDE 0160 Non-periodic overvoltage
0.15 to 80 MHz, 10 V RMS, 80% AM at 1kHz >95% reduction for 8.3 ms, 83 ms, 833 ms, and 4167 ms At 85 VAC line, 90 phase angle, apply 390 V peak, 1.3 ms pulse At 180 VAC line, 90 phase angle, apply 750 V peak, 1.3 ms pulse
Electromagnetic Compatibility Conducted and Radiated Emissions per EN 61000-6-32 and EN 61000-6-4 EN 55011, Class A, Group 1, conducted1 0.15 MHz to 0.5 MHz 0.5 MHz to 5 MHz 5 MHz to 30 MHz EN 55011, Class A, Group 1, radiated1 30 MHz to 230 MHz 230 MHz to 1 GHz EN 55011, Class B, Group 1, conducted2 0.15 to 0.5 MHz 0.5 MHz to 5 MHz 5 MHz to 30 MHz EN 55011, Class B, Group 1, radiated2 30 MHz to 230 kHz 230 MHz to 1 GHz < 79 dB (V) Quasi-peak; < 66 dB (V) Average < 73 dB (V) Quasi-peak; < 60 dB (V) Average < 73 dB (V) Quasi-peak; < 60 dB (V) Average 40 dB (V/m) Quasi-peak; measured at 10 m 47 dB (V/m) Quasi-peak; measured at 10 m < 66 dB (V) Quasi-peak decreasing with log frequency to 56 dB (V); < 56 dB (V) Average decreasing with log frequency to 46 dB (V) < 56 dB (V) Quasi-peak; < 46 dB (V) Average < 60 dB (V) Quasi-peak; < 50 dB (V) Average 30 dB (V/m) Quasi-peak; measured at 10 m 37 dB (V/m) Quasi-peak; measured at 10 m High Potential Isolation Test 24 V/5 V nominal circuits 115/230 V circuits to ground 115/230 V circuits to 115/230 V circuits 230 V circuits to 24 V/5 V circuits 115 V circuits to 24 V/5 V circuits
1
500 VAC (optical isolation boundaries) 1,500 VAC 1,500 VAC 1,500 VAC 1,500 VAC
Unit must be mounted on a grounded metallic frame with the S7-200 ground connection made directly to the mounting metal. Cables are routed along metallic supports. Unit must be mounted in a grounded metal enclosure. AC input power line must be equipped with a EPCOS B84115-E-A30 filter or equivalent, 25 cm max. wire length from filters to the S7-200. The 24 VDC supply and sensor supply wiring must be shielded.